title: "CT ratio and connection for 11/132 kV"
subject: "Switchgear and Protection"
chapter: 7
key: "semester_6/switchgear_and_protection:differential-ct-11-132kv"
source: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/differential-ct-11-132kv
site: BCT Engineering
---

# CT ratio and connection for 11/132 kV

Switchgear and Protection · Chapter 7: Protective Relays

- Asked in: 2073 Bhadra, 6 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/differential-ct-11-132kv
- Whole chapter: https://www.bctengineer.com/md/semester_6/switchgear_and_protection/chapter-7

## Question

A three phase, 11/132 kV, delta-star connected power transformer is protected by differential protection. The CTs on the LV side have a current ratio of 200/1. What must be the current ratio of the CTs on the HV side? How the CTs on both the sides of the transformer are connected?

## Short answer

For delta-star transformer, LV delta-side CTs 200/1 are star connected, giving 1 A pilot. HV line current is 200 x 11/132 = 16.67 A; HV star-side CTs are delta connected, requiring secondary 1/√3 A. HV CT ratio is 16.67 : 1/√3 ≈ 28.87 : 1.

## Answer

For differential protection, CTs on the **delta** winding side are connected in **star**, and CTs on the **star** winding side are connected in **delta**. This compensates the 30° phase shift of the transformer and prevents zero-sequence currents (from earth faults on the earthed star side) from causing false trips.

**Data:** 11/132 kV, delta (LV) / star (HV); LV CTs 200/1.

#### CT ratio on HV side
```text
LV line current = 200 A → LV CT secondary (pilot) = 1 A
                (LV CTs in star)

HV line current = 200 × 11/132 = 16.67 A

HV CTs in delta: pilot current = √3 × CT secondary
CT secondary = 1/√3 = 0.5774 A

HV CT ratio = 16.67 : 0.5774 = 28.87 : 1
```

#### Connection of CTs
- **LV (11 kV, delta winding):** CTs of 200/1 connected in **star**.
- **HV (132 kV, star winding):** CTs of 16.67 : 1/√3 (≈ 28.87/1) connected in **delta**.
- Pilot wires join corresponding phases of the two CT groups; the operating (and restraining) coils of the differential relays are connected between the pilots and the star point.

```text
 11 kV delta ──[CTs 200/1, star]──┐
                                   ├─ pilots ─ 87 relays
 132 kV star ──[CTs 28.87/1, delta]┘
```

**Answer:** HV CT ratio = **16.67 : 1/√3 ≈ 28.87 : 1**; LV CTs in star, HV CTs in delta.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. For a delta (LV) / star (HV) transformer, how are the CTs connected?
   A. LV CTs star, HV CTs delta
   B. LV CTs delta, HV CTs star
   C. Both star
   D. Both delta
   Answer: A. CTs on the delta winding go in star and CTs on the star winding go in delta. (Key point: CT connections)

2. Besides phase-shift correction, what does the delta CT connection on the earthed star side prevent?
   A. Overvoltage on pilots
   B. False trip from zero-sequence current during external earth faults
   C. CT saturation from inrush
   D. Pilot capacitance effects
   Answer: B. Delta circulates zero-sequence current, keeping it out of the relay for external earth faults. (Key point: Why delta CTs on star side)

3. LV CTs 200/1 on 11 kV side carry 200 A. The HV (132 kV) line current is:
   A. 2400 A
   B. 16.67 A
   C. 200 A
   D. 28.87 A
   Answer: B. I_HV = 200 × 11/132 = 16.67 A. (Key point: HV line current)

4. With HV CTs in delta and 1 A pilot current, the HV CT ratio is:
   A. 16.67 : 1
   B. 16.67 : sqrt(3), about 9.6 : 1
   C. 16.67 : 1/sqrt(3), about 28.87 : 1
   D. 200 : 1
   Answer: C. CT secondary is 1/sqrt(3) = 0.5774 A, so the ratio is 16.67 : 0.5774 = 28.87 : 1. (Key point: HV CT ratio)

## Related in Switchgear and Protection

- [CT ratio for 33/6.6 kV star/delta (300:5)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Adifferential-ct-33-6-6kv-300) — Switchgear and Protection, chapter 7
- [CT ratio for 33/6.6 kV star/delta (400/5)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Adifferential-ct-33-6-6kv-400) — Switchgear and Protection, chapter 7
- [Differential protection: 11 kV, 100 MVA generator](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Agenerator-differential-11kv-6-ohm) — Switchgear and Protection, chapter 7
- [IDMT relays across 132/11 kV transformer (3500 A)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aidmt-132-11kv-3500a) — Switchgear and Protection, chapter 7
- [Percentage differential relay: 125 MVA transformer](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Apercentage-differential-125mva) — Switchgear and Protection, chapter 7
- [Percentage differential relay: 150 MVA transformer](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Apercentage-differential-150mva) — Switchgear and Protection, chapter 7

## Related in other subjects

- [Currents and efficiency of 132/11 kV transformer at 5 MW](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Astar-delta-132-11kv-5mw-currents) — Electrical Machines I, chapter 2, asked 3×
- [Design: 500 kVA 66/11 kV power transformer](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-500kva-66-11kv) — Electric Machine Design, chapter 3, asked 6×
- [Currents and efficiency of 132/11 kV transformer at 4 MW](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Astar-delta-132-11kv-4mw-currents) — Electrical Machines I, chapter 2, asked 3×
- [Design: 4000 kVA 66/11 kV power transformer](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-4000kva-66-11kv) — Electric Machine Design, chapter 3, asked 5×