# Cut-off and time-current characteristics of fuse

Switchgear and Protection · Chapter 3: Fuses

- Asked in: 2078 Chaitra, 6 marks
- Video: [What is Cut Off Characteristics Of Fuse.](https://www.youtube.com/watch?v=fXrXmJ_oQ3A) — IB TECHNICAL CLASSES
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/fuse-cutoff-time-current
- Whole chapter: https://www.bctengineer.com/md/semester_6/switchgear_and_protection/chapter-3

## Question

Explain the cut-off characteristics and the time-current characteristics of a fuse.

## Short answer

Time-current characteristic is inverse: time decreases as current increases, with pre-arcing and total clearing curves; below minimum fusing current no operation. Cut-off characteristic shows maximum instantaneous current versus prospective rms current; for large faults the fuse melts before first peak, limiting peak current and let-through energy.

## Answer

#### Time–current characteristic of a fuse
The time–current (T–I) characteristic shows the time taken by a fuse to operate for different values of current. It is plotted on log–log scales.
```text
 t (s, log)
 10⁴│╲
    │ ╲
 10²│  ╲   pre-arcing curve
    │   ╲  ╲ total clearing curve
  1 │    ╲  ╲
    │     ╲__╲__
 0.01│         ‾‾‾──____
    └──┬──────────────────► I (log)
      I_min fusing
```
- It is an **inverse** characteristic: small overcurrent → long time; large current → very short time.
- Below the **minimum fusing current** the fuse does not operate at all.
- Two curves are usually given: **pre-arcing (melting) time** and **total operating time** (pre-arcing + arcing). The gap between them is the arcing time; it is important only for short times.
- The characteristic depends on element material, cross-section, shape (notches), the filler and the ambient temperature.
- It is used for coordination: the T–I curves of fuses, relays and breakers in series must not cross.

#### Cut-off characteristic of a fuse
When the prospective fault current is large, an HRC fuse melts before the current reaches its first peak. The maximum instantaneous current actually reached is the **cut-off current**.
```text
 i
 │      ╱‾‾╲  prospective current
 │     ╱    ╲
 │  ●╲╱ cut-off
 │  ╱ ╲
 │ ╱   ╲___ actual (limited)
 └┴──┴───┴──────► t
   t_p  t_a
```
The **cut-off characteristic** is a graph of cut-off current (peak) versus prospective current (r.m.s.):
```text
 I_cut-off (kA peak)
  │             ╱ no cut-off line
  │           ╱   (peak = 2.5 × Irms)
  │         ╱   ___ 200 A fuse
  │       ╱ __─‾ ___ 100 A fuse
  │     ╱_─‾_──‾
  └─────────────────► prospective (kA rms)
```
- Each fuse rating has a curve; above a certain prospective current, cut-off occurs and the curve falls below the "no cut-off" line.
- Smaller fuse ratings give lower cut-off currents.

**Importance:** it gives the maximum peak current (electromagnetic force) and let-through energy that the downstream cables, busbars and switches must withstand, and allows smaller equipment and cheaper switchgear to be used.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. What do the two T-I curves of a fuse represent?
   A. Pre-arcing (melting) time and total operating time; gap between is arcing time
   B. Voltage and current
   C. Cut-off and rated
   D. Min and max ambient
   Answer: A. Total = pre-arcing + arcing. (Key point: T-I curves)

2. What happens below minimum fusing current?
   A. Fuse blows instantly
   B. Fuse does not operate at all
   C. Fuse arcs
   D. Fuse resets
   Answer: B. The characteristic is inverse with a lower limit. (Key point: Minimum fusing)

3. What is plotted in the cut-off characteristic?
   A. Time vs current
   B. I2t vs time
   C. Cut-off (peak) current vs prospective r.m.s. current for each rating
   D. Voltage vs time
   Answer: C. Curves fall below the no-cut-off line (peak = 2.5 x rms) above a certain prospective current. (Key point: Cut-off graph)

4. What is the importance of the cut-off characteristic?
   A. Gives rated current
   B. Gives arc voltage
   C. Gives cost
   D. Gives maximum peak current and let-through energy that downstream equipment must withstand
   Answer: D. It allows smaller, cheaper switchgear. (Key point: Importance)

## Related in Switchgear and Protection

- [Prospective current, cut-off current, time delay fuse](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aprospective-cutoff-time-delay-fuse) — Switchgear and Protection, chapter 3
- [Fuse terms with cut-off characteristic sketch](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Afuse-terms-cutoff-sketch) — Switchgear and Protection, chapter 3
- [Fuse time-current factors and coordination](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Afuse-tcc-factors-coordination) — Switchgear and Protection, chapter 3
- [Fuse vs MCB; HRC fuse time terms](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Afuse-vs-mcb-hrc-terms) — Switchgear and Protection, chapter 3
- [HRC fuse operating characteristics and applications](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Ahrc-fuse-operating-characteristics) — Switchgear and Protection, chapter 3

## Related in other subjects

- [Cut-off current characteristics of HRC fuse](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Ahrc-cutoff-characteristics) — Industrial Power Distribution and Illumination, chapter 3
- [HRC fuse quartz sand, cut-off, vs Kit-Kat](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Ahrc-quartz-sand-kitkat) — Industrial Power Distribution and Illumination, chapter 3
- [MCB principle, MCB/MCCB/RCCB, HRC cut-off](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Amcb-mccb-rccb-hrc-cutoff) — Industrial Power Distribution and Illumination, chapter 3
- [Cut-off and single-mode range, 4×2 cm](https://www.bctengineer.com/question.md?key=semester_3%2Felectromagnetism%3Awaveguide-4x2cm-cutoff-single-mode-range) — Electromagnetism, chapter 6