title: "Selecting HRC fuse rating for motor"
subject: "Switchgear and Protection"
chapter: 3
key: "semester_6/switchgear_and_protection:hrc-fuse-motor-rating"
source: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/hrc-fuse-motor-rating
site: BCT Engineering
---

# Selecting HRC fuse rating for motor

Switchgear and Protection · Chapter 3: Fuses

- Asked in: 2079 Chaitra, 5 marks
- Video: [How to Select Fuse Rating | What is HRC Fuse | Hindi](https://www.youtube.com/watch?v=maWfYt0MHsQ) — Electrical With Abhishek Joshi
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/hrc-fuse-motor-rating
- Whole chapter: https://www.bctengineer.com/md/semester_6/switchgear_and_protection/chapter-3

## Question

Discuss the method of selecting the rating of HRC fuse in motor stator.

## Short answer

SelectHRCfuse by calculating motor full-load and starting current. Choose aM or time-delay gG fuse whose pre-arcing time at start current exceeds starting time, typically 2-3 times full-load for gG (e.g., for 27.28A motor, 63A gG). Verify breaking capacity and type-2 coordination with contactor, ensuring fuse cuts off before contactor damage.

## Answer

An HRC fuse in a motor (stator) circuit provides **short-circuit protection** only; overload protection is given by a thermal overload relay. The fuse must not blow during starting, but must clear faults and protect the contactor.

#### Method of selection
1. **Find full-load current:**
```text
 I_FL = P_out / (√3 · V_L · η · cosφ)
```
2. **Find starting current and starting time:** DOL starting current I_st ≈ 5–7 × I_FL for 5–10 s (longer for high-inertia loads); star–delta ≈ 2–2.5 × I_FL; soft starter ≈ 3 × I_FL.
3. **Choose fuse type:** motor-circuit HRC fuse (**aM**, partial-range) or time-delay **gG** fuse. aM fuses withstand starting current and can be rated close to I_FL.
4. **Choose rating:** the smallest standard rating whose **pre-arcing time at I_st is greater than the starting time** (with margin for frequent starts and hot condition). As rough guides for gG fuses:
   - DOL start: fuse ≈ 2–3 × I_FL
   - Star–delta start: fuse ≈ 1.5–2 × I_FL
5. **Check breaking capacity** ≥ prospective fault current at the motor terminals.
6. **Coordinate with contactor and overload relay:** the fuse must interrupt all currents above the contactor's breaking capacity (≈ 8 × Ie for AC-3) and limit the let-through I²t to the contactor and cable withstand (type-2 coordination).
7. **Check cable protection:** fuse I²t below the cable's k²S².

#### Example
15 kW, 415 V motor, η = 0.9, pf = 0.85, DOL:
```text
 I_FL = 15 000 / (√3 × 415 × 0.9 × 0.85) = 27.28 A
 I_st = 6 × 27.28 = 163.7 A for 10 s
 Fuse (gG) ≈ 2.5 × 27.28 = 68.2 A → 63 A standard,
 check its T–I curve: melting time at 163.7 A > 10 s ✓
```
An aM fuse of about 32–40 A could also be used.

#### Points to remember
- Too small a fuse blows during starting (nuisance tripping); too large a fuse may not protect the contactor and cables.
- Never rely on the fuse for overload; use the overload relay set at ≈ 1.0–1.05 × I_FL.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. What protection does an HRC fuse in a motor circuit give?
   A. Overload only
   B. Short-circuit protection only
   C. Under-voltage protection
   D. Single phasing protection
   Answer: B. Overload is left to the thermal relay; the fuse is for short circuits. (Key point: Purpose of fuse)

2. The fuse rating chosen is the smallest standard rating whose:
   A. Current rating equals I_FL
   B. Breaking capacity equals starting current
   C. Pre-arcing time at starting current exceeds the starting time
   D. Voltage rating equals the motor power
   Answer: C. This prevents blowing during starting while keeping protection as tight as possible. (Key point: Rating criterion)

3. How does the gG fuse multiple of I_FL change with star-delta instead of DOL starting?
   A. It is higher, because starting current is higher
   B. It is lower (1.5-2 x I_FL), because starting current is lower
   C. It does not change
   D. It must be zero
   Answer: B. Star-delta starting current is about 2-2.5 x I_FL, so a smaller fuse suffices. (Key point: Starter type effect)

4. What is the consequence of choosing too large a fuse?
   A. It blows during starting
   B. It has lower breaking capacity
   C. It may not protect the contactor and cables
   D. The motor cannot start
   Answer: C. Too small causes nuisance blowing; too large leaves contactor and cable unprotected. (Key point: Too small or large)

## Related in Switchgear and Protection

- [Fuse vs MCB; HRC fuse time terms](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Afuse-vs-mcb-hrc-terms) — Switchgear and Protection, chapter 3
- [HRC fuse construction; fuse vs MCB](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Ahrc-fuse-construction-vs-mcb) — Switchgear and Protection, chapter 3
- [HRC fuse construction and advantages](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Ahrc-fuse-construction-advantages) — Switchgear and Protection, chapter 3
- [HRC fuse operating characteristics and applications](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Ahrc-fuse-operating-characteristics) — Switchgear and Protection, chapter 3
- [HRC fuse I²t and fuses in series](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Ahrc-fuse-i2t-series) — Switchgear and Protection, chapter 3
- [Short note: Low voltage HRC fuse](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Ashort-note-lv-hrc-fuse) — Switchgear and Protection, chapter 3

## Related in other subjects

- [Fuse vs MCB and HRC rupturing capacity](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Afuse-mcb-hrc-rupturing) — Industrial Power Distribution and Illumination, chapter 3, asked 3×
- [MCB, MCCB and HRC fuse comparison](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Amcb-mccb-hrc-comparison) — Industrial Power Distribution and Illumination, chapter 3, asked 3×
- [Cut-off current characteristics of HRC fuse](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Ahrc-cutoff-characteristics) — Industrial Power Distribution and Illumination, chapter 3
- [HRC fuse quartz sand, cut-off, vs Kit-Kat](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Ahrc-quartz-sand-kitkat) — Industrial Power Distribution and Illumination, chapter 3