# Merz-Price CT ratio for 66000/6600 V

Switchgear and Protection · Chapter 7: Protective Relays

- Asked in: 2077 Chaitra, 4 marks
- Video: [CURRENT TRANSFORMER  TURNS RATIO CALCULATION  || MERZ PRICE DIFFERENTIAL PROTECTION](https://www.youtube.com/watch?v=KNFVWeYsUE4) — ELECTRICAL NEST
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/merz-price-66kv-ct-ratio
- Whole chapter: https://www.bctengineer.com/md/semester_6/switchgear_and_protection/chapter-7

## Question

A 3 phase 66000/6600 V star/delta transformer is protected by Merz-Price system. What will be the ratio of current transformer on the high voltage side if the current transformers on the low voltage side have a ratio of 400/5 A?

## Short answer

For the 66/6.6 kV star/delta transformer, LV CTs 400/5 in star give 5 A pilot current. HV line current is 400 x 6.6/66 = 40 A; HV CTs in delta need secondary 5/√3 A. HV CT ratio is 40 : 5/√3 ≈ 69.3 : 5.

## Answer

In the Merz-Price (circulating current) scheme for a star/delta transformer, the HV (star) side CTs are connected in **delta** and the LV (delta) side CTs in **star**, so that the pilot currents from both sides are equal and in phase.

**Data:** 66 000/6600 V, star/delta; LV CTs 400/5.

```text
LV line current = 400 A → LV CT secondary (pilot) = 5 A

HV line current = 400 × 6600/66 000 = 40 A

HV CTs in delta: pilot current = √3 × CT secondary
CT secondary = 5/√3 = 2.887 A

HV CT ratio = 40 : 5/√3 = 40 : 2.887
            = 69.28 : 5   (≈ 13.86 : 1)
```

**Answer:** HV CT ratio = **40 : 5/√3 ≈ 69.3 : 5**, with HV CTs connected in delta and LV CTs in star.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. In the Merz-Price scheme for a 66/6.6 kV star/delta transformer, the LV (delta) side CTs are connected in:
   A. Delta
   B. Star
   C. Open delta
   D. Zigzag
   Answer: B. The delta winding side gets star-connected CTs, and the star side gets delta-connected CTs. (Key point: Merz-Price CT connections)

2. LV CTs are 400/5. For 400 A LV line current, what is the HV line current?
   A. 4000 A
   B. 400 A
   C. 69.3 A
   D. 40 A
   Answer: D. I_HV = 400 × 6600/66000 = 40 A. (Key point: HV line current)

3. What is the HV CT ratio?
   A. 40 : 5
   B. 40 : 5/sqrt(3), about 69.3 : 5
   C. 40 : 5 × sqrt(3)
   D. 13.86 : 5
   Answer: B. Delta-connected CTs give a 2.887 A secondary for 5 A pilot current, so 40 : 2.887 = 69.3 : 5. (Key point: HV CT ratio)

## Related in Switchgear and Protection

- [CT ratio for 33/6.6 kV star/delta (400/5)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Adifferential-ct-33-6-6kv-400) — Switchgear and Protection, chapter 7
- [Merz-Price: protected winding (13.8 kV)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Amerz-price-13-8kv-protected) — Switchgear and Protection, chapter 7, asked 2×
- [CT ratio for 33/6.6 kV star/delta (300:5)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Adifferential-ct-33-6-6kv-300) — Switchgear and Protection, chapter 7
- [Merz-Price: unprotected winding (5000 kVA)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Amerz-price-5000kva-unprotected) — Switchgear and Protection, chapter 7, asked 2×
- [CT ratio and connection for 11/132 kV](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Adifferential-ct-11-132kv) — Switchgear and Protection, chapter 7
- [Pilot current with tap change (10 MVA)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Apilot-current-10mva-tap) — Switchgear and Protection, chapter 7

## Related in other subjects

- [Design: 150 kVA 6600/400 V distribution transformer](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-150kva-6600-400-regulation) — Electric Machine Design, chapter 3, asked 5×
- [Design: 125 kVA 6600/400 V three phase transformer](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-125kva-three-phase-windings) — Electric Machine Design, chapter 3, asked 4×
- [500 kVA delta/star transformer efficiency](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Athree-phase-500kva-33-11-efficiency) — Electrical Machine, chapter 2
- [2.2 kW 400 V cage motor (star-delta) design](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-2-2kw-400v-star-delta) — Electric Machine Design, chapter 4, asked 3×