title: "Microprocessor relaying via generator field current"
subject: "Switchgear and Protection"
chapter: 8
key: "semester_6/switchgear_and_protection:microprocessor-generator-field"
source: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/microprocessor-generator-field
site: BCT Engineering
---

# Microprocessor relaying via generator field current

Switchgear and Protection · Chapter 8: Static and Digital Relays

- Asked in: 2072 Magh, 8 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/microprocessor-generator-field
- Whole chapter: https://www.bctengineer.com/md/semester_6/switchgear_and_protection/chapter-8

## Question

Describe with neat block diagram, the microprocessor based relaying scheme for the protection of generator by monitoring the field current of the alternator.

## Short answer

A microprocessor-based loss-of-field protection monitors the generator field current via a shunt or Hall sensor. The signal is isolated, filtered, scaled, sampled, and digitized. The microprocessor compares the field current with a set minimum (20–40% of no-load value); if below for a set delay (0.5–2 s), it issues an alarm and trips the generator and field circuit breakers. The scheme includes self-checking, data logging, and can add undervoltage or reactive power confirmation.

## Answer

**Loss-of-field (field failure) protection** of an alternator can be done by a microprocessor that continuously monitors the field (excitation) current. If the field current falls below a set minimum (field open, short-circuited, or AVR/exciter failure), the generator loses synchronism and draws large reactive power from the system; the scheme gives an alarm and trips the generator after a short delay.

#### Block diagram

```text
 Exciter ──► Field winding of alternator
              │
        [Shunt / Hall-effect current
         sensor in field circuit]
              │ V ∝ I_f
      [Isolation amplifier / filter]
              │
     [Signal conditioner (0–5 V)]
              │
       [Sample & hold] ─► [A/D converter]
                               │
 ┌─────────────────────────────▼─────┐
 │        MICROPROCESSOR             │
 │ ROM: program   RAM: data          │
 │ Set value I_f(min), time delay    │
 └──────┬──────────┬───────────┬─────┘
        │          │           │
  [Output port] [Display]  [Clock/timer]
        │
  [Driver + aux relay]──► Alarm
        └──────────────► Trip gen. CB
                         & field CB
```

#### Working

1. **Sensing:** the DC field current I_f is measured by a shunt (or Hall sensor) giving a small voltage proportional to I_f. An isolation amplifier separates the field circuit from the electronics and filters ripple.
2. **Conversion:** the signal is scaled to the ADC range (e.g. 0–5 V), sampled and converted to a digital number.
3. **Program logic:**
   - Read the ADC value at regular intervals and convert to field current.
   - Compare with the stored minimum value I_f(min) (e.g. 20–40% of no-load field current; set from the generator's capability curve).
   - If I_f ≥ I_f(min): healthy, repeat.
   - If I_f < I_f(min): start a timer (about 0.5–2 s) to avoid tripping on transient dips or swings.
   - If the low value persists for the set time: give alarm, then send trip signal to the generator CB and field CB.
4. **Output:** the output port drives a transistor/auxiliary relay that trips the breakers; the display shows field current and status.

```text
 Start → Read I_f → I_f < I_min ? ─No─► loop
                         │Yes
                   Start/continue timer
                         │
                 t > t_set ? ─No─► loop
                         │Yes
                  Alarm + Trip CBs
```

**Advantages:** simple, accurate settings, self-checking, and the same microprocessor can also log data and add an under-voltage or reactive-power check to confirm loss of field.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. In the microprocessor scheme for loss-of-field protection, which quantity is continuously monitored?
   A. Stator terminal voltage
   B. Field (excitation) current of the alternator
   C. Rotor speed
   D. Stator neutral current
   Answer: B. The scheme senses the DC field current I_f with a shunt or Hall sensor and trips if it falls below a set minimum. (Key point: What is monitored)

2. Why must the generator be tripped if its field current falls below the minimum value?
   A. It over-speeds and produces excess active power
   B. It loses synchronism and draws large reactive power from the system
   C. Its stator voltage rises dangerously
   D. Its field winding overheats from excess current
   Answer: B. Loss of field makes the machine lose synchronism and absorb large reactive power from the system, so it is alarmed and tripped. (Key point: Effect of field loss)

3. What is the correct order of the signal path from the field circuit to the microprocessor?
   A. Sensor, A/D converter, isolation amplifier, sample and hold
   B. Isolation amplifier, sensor, A/D converter, signal conditioner
   C. Sensor, isolation amplifier and filter, signal conditioner, sample and hold, A/D converter
   D. Signal conditioner, sensor, A/D converter, sample and hold
   Answer: C. The shunt/Hall sensor voltage is isolated and filtered, scaled to 0-5 V, sampled and held, then digitised before the microprocessor reads it. (Key point: Signal chain)

4. Why does the program start a timer (about 0.5-2 s) when I_f < I_f(min) instead of tripping immediately?
   A. To let the ADC finish converting
   B. To avoid tripping on transient dips or swings; trip only if the low value persists
   C. To allow the field breaker to close
   D. To charge the output relay
   Answer: B. A short delay prevents false trips from momentary dips; the generator and field CBs are tripped only if the low value persists for the set time. (Key point: Time delay in logic)

## Related in Switchgear and Protection

- [Microprocessor-based transmission line protection](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Amicroprocessor-line-protection) — Switchgear and Protection, chapter 8, asked 2×
- [Earth fault protection: 20 MVA alternator](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aearth-fault-20mva-5-ohm) — Switchgear and Protection, chapter 7
- [Unit protection scheme](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aunit-protection-scheme) — Switchgear and Protection, chapter 7
- [Differential protection: 11 kV, 100 MVA generator](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Agenerator-differential-11kv-6-ohm) — Switchgear and Protection, chapter 7
- [Combined phase and earth fault protection of generator](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Acombined-phase-earth-fault-generator) — Switchgear and Protection, chapter 7
- [Percentage differential protection of alternator](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aalternator-percentage-differential) — Switchgear and Protection, chapter 7, asked 2×

## Related in other subjects

- [DC motor θm/Va via block diagram](https://www.bctengineer.com/question.md?key=semester_3%2Fcontrol_systems%3Atf-dc-motor-bd-thetam-va) — Control Systems, chapter 2
- [Microprocessor based system and bus organization](https://www.bctengineer.com/question.md?key=semester_4%2Fmicroprocessor%3Amp-based-system-bus-organization) — Microprocessor, chapter 1, asked 5×
- [Protection for alternator and step-up transformer](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Amega-project-protection) — Power Plant Design, chapter 4
- [Features of microprocessor based instrumentation](https://www.bctengineer.com/question.md?key=semester_5%2Finstrumentation_ii%3Ambi-features) — Instrumentation II, chapter 1, asked 4×