title: "Microprocessor-based transmission line protection"
subject: "Switchgear and Protection"
chapter: 8
key: "semester_6/switchgear_and_protection:microprocessor-line-protection"
source: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/microprocessor-line-protection
site: BCT Engineering
---

# Microprocessor-based transmission line protection

Switchgear and Protection · Chapter 8: Static and Digital Relays

- Asked in: 2071 Magh, 8 marks; 2075 Baisakh, 8 marks (asked 2 times)
- Video: [SGP Lec 41: Microprocessor Based Distance Relay](https://www.youtube.com/watch?v=qsyGT6hPxrg) — Polytech Plus
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/microprocessor-line-protection
- Whole chapter: https://www.bctengineer.com/md/semester_6/switchgear_and_protection/chapter-8

## Question

Draw the block diagram of microprocessor based protective scheme for protection of transmission line.

## Short answer

A microprocessor-based line protection scheme samples line voltages and currents via CTs/PTs, scales and filters them, then converts to digital via multiplexed ADC. The microprocessor computes phasors using DFT, calculates apparent impedance for each zone, and compares with mho/quadrilateral characteristics. Zone 1 trips instantly; zones 2 and 3 trip after set delays. Output drivers operate auxiliary relays to trip the breaker, with event recording and SCADA communication.

## Answer

In a **microprocessor-based line protection scheme**, the voltages and currents of the transmission line are sampled, converted to digital form and processed by a microprocessor that computes the apparent impedance (or other quantities) and issues a trip when a fault lies inside a protected zone. Usually it works as a **distance (impedance/mho/quadrilateral) relay** with three zones.

#### Block diagram

```text
 Transmission line ══CB══════════════════
        │ CT (Ia,Ib,Ic)     │ PT (Va,Vb,Vc)
        ▼                   ▼
 ┌──────────────────────────────────┐
 │ Aux CTs/PTs, surge suppressors   │
 │ (isolation, scaling to ±10 V)    │
 └───────────────┬──────────────────┘
          [I→V converters]
                 │
       [Anti-aliasing LP filters]
                 │
       [Sample & hold circuits]
                 │
       [Analog multiplexer] ◄─ control
                 │
          [A/D converter]
                 │
 ┌───────────────▼──────────────────┐
 │  MICROPROCESSOR / DSP            │
 │  ROM: program  RAM: samples      │
 │  EEPROM: zone settings           │
 └──┬────────┬────────┬────────┬────┘
    │        │        │        │
 [Timer] [Output   [Display/ [Comm.
         interface]  keypad]  port]
             │
     [Driver + aux relay]──► CB trip coil
 [Digital inputs: CB status, carrier]
 [DC-DC power supply from battery]
```

#### Working

1. **Input stage:** CT and PT outputs pass through auxiliary transformers which isolate and scale them; current signals are converted to voltages across precision resistors.
2. **Anti-aliasing filter:** removes components above half the sampling frequency.
3. **Sample-and-hold + multiplexer:** all six signals are sampled at the same instant (e.g. 12–20 samples per cycle) and passed one by one to the ADC.
4. **ADC:** gives 12–16 bit binary numbers to the microprocessor.
5. **Microprocessor program:**
   - Computes phasors of V and I by Fourier (DFT) or least-squares algorithms.
   - Computes apparent impedance Z = V/I (R and X) for each phase and phase pair, with residual compensation for earth faults.
   - Compares Z with zone 1, zone 2 and zone 3 characteristics (mho or quadrilateral).
   - Zone 1: instantaneous trip; zone 2 and zone 3: trip after timer delays (e.g. 0.3 s and 1 s).
   - Checks power swing, VT fuse failure, and carrier signals.
6. **Output interface:** opto-isolated drivers operate auxiliary relays to trip the breaker and give alarms.
7. Records events and disturbance data; communicates with SCADA.

**Advantages:** one hardware for many characteristics, self-checking, fault location, low burden and easy setting changes.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. What does the microprocessor compute to protect a transmission line?
   A. Apparent impedance Z = V/I, compared with zone characteristics
   B. Only the frequency
   C. The line temperature
   D. Only the CT ratio
   Answer: A. It works as a distance relay with zone 1, 2 and 3 comparisons. (Key point: Scheme function)

2. What is the correct order of the front-end?
   A. Aux CT/PT, anti-aliasing filter, sample-and-hold, multiplexer, ADC
   B. ADC, filter, aux CT/PT, multiplexer
   C. Multiplexer, sample-and-hold, ADC, filter
   D. Sample-and-hold, aux CT, ADC, filter
   Answer: A. Signals are scaled, band-limited, sampled simultaneously, multiplexed and digitised. (Key point: Signal chain order)

3. Which algorithms estimate the phasors of V and I?
   A. Fourier (DFT) or least-squares
   B. Binary search
   C. Bubble sort
   D. Huffman coding
   Answer: A. Fourier or least-squares algorithms extract the fundamental phasors used to compute R and X. (Key point: Phasor algorithms)

4. How are the zones treated?
   A. Zone 1 instantaneous; zones 2 and 3 after timer delays such as 0.3 s and 1 s
   B. All zones instantaneous
   C. Zone 1 delayed 1 s
   D. Only zone 3 is used
   Answer: A. Delayed outer zones coordinate with adjacent line protection. (Key point: Zone timing)

## Related in Switchgear and Protection

- [Protection requirements; protective system vs scheme](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aprotective-system-vs-scheme) — Switchgear and Protection, chapter 1
- [Unit protection scheme](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aunit-protection-scheme) — Switchgear and Protection, chapter 7
- [Microprocessor relaying via generator field current](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Amicroprocessor-generator-field) — Switchgear and Protection, chapter 8
- [Basic requirements of a protection scheme](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Abasic-requirements-protection-scheme) — Switchgear and Protection, chapter 1, asked 3×
- [Converting IDMT scheme to differential protection](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aidmt-to-differential-transformer) — Switchgear and Protection, chapter 7
- [Knee point voltage; measuring vs protective CT](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aknee-point-measuring-protective-ct) — Switchgear and Protection, chapter 2

## Related in other subjects

- [Microprocessor based system and bus organization](https://www.bctengineer.com/question.md?key=semester_4%2Fmicroprocessor%3Amp-based-system-bus-organization) — Microprocessor, chapter 1, asked 5×
- [Features of microprocessor based instrumentation](https://www.bctengineer.com/question.md?key=semester_5%2Finstrumentation_ii%3Ambi-features) — Instrumentation II, chapter 1, asked 4×
- [Types of microprocessor based instrumentation systems](https://www.bctengineer.com/question.md?key=semester_5%2Finstrumentation_ii%3Ambi-types) — Instrumentation II, chapter 1
- [MBI block diagram and basic features](https://www.bctengineer.com/question.md?key=semester_5%2Finstrumentation_ii%3Ambi-block-features) — Instrumentation II, chapter 1, asked 4×