# Fuse and contactor ratings for induction motor

Switchgear and Protection · Chapter 3: Fuses

- Asked in: 2071 Magh, 6 marks
- Video: [How To Select Size of Contactor, Fuse and C.B For Motor in Urdu/Hindi](https://www.youtube.com/watch?v=kNEvCnID-rY) — kW Calc
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/motor-fuse-contactor-selection
- Whole chapter: https://www.bctengineer.com/md/semester_6/switchgear_and_protection/chapter-3

## Question

An induction motor is required to protect through a fuse and contactor. Suggest a suitable guide line for selection of ratings of fuse and contactor. State any assumptions you make.

## Short answer

For a 15kW, 415V motor with eta=0..9, pf=0.85: full-load current =27.28A. Select 63A gG HRC fuse (withstands 163.7A starting for 10s), 32A AC-3 contactor, and thermal overload relay set at 28A. Ensure fuse let-through I²t within contactor withstand for type-2 coordination.

## Answer

**Assumptions:** 3-phase squirrel-cage induction motor, 15 kW, 415 V, 50 Hz, efficiency 90 %, power factor 0.85, direct-on-line (DOL) starting, starting current 6 × full-load for up to 10 s, prospective fault current at motor control centre 25 kA. The scheme is fuse (short-circuit protection) + contactor (switching) + thermal overload relay (overload protection).

```text
 415 V ─[HRC fuse]─[Contactor]─[O/L relay]─ M
        short-ckt   switching   overload
```

#### Step 1: Full-load current
```text
 I_FL = P / (√3 · V · η · cosφ)
      = 15 000 / (√3 × 415 × 0.90 × 0.85)
      = 27.28 A
 Starting current = 6 × 27.28 = 163.7 A for ~10 s
```

#### Step 2: Fuse selection guidelines
1. **Type:** motor-rated HRC fuse (aM or gM) or time-delay gG fuse, because it must not melt on starting current.
2. **Rating:** for DOL start, about **2–2.5 × I_FL** for gG fuses → 54.6–68.2 A. Choose **63 A** gG HRC (or a 32 A/40 A aM fuse).
3. **Check starting:** the pre-arcing time of the chosen fuse at 163.7 A must be greater than the starting time (10 s) with margin, also allowing for repeated starts.
4. **Breaking capacity:** must exceed the prospective fault current (25 kA); LV HRC fuses with 80 kA are suitable.
5. **Back-up to contactor:** the fuse must clear all currents above the contactor's breaking capacity, and its cut-off current/I²t must be within the contactor's short-circuit withstand (type-2 coordination as per IEC 60947-4-1).
6. Overload protection is not expected from the fuse.

#### Step 3: Contactor selection guidelines
1. **Utilisation category:** **AC-3** (starting squirrel-cage motors, switching off while running).
2. **Rated operational current Ie (AC-3)** ≥ I_FL at 415 V → choose a **32 A AC-3** contactor (≥ 27.28 A).
3. **Making/breaking capacity:** AC-3 contactor makes 10 × Ie (320 A) and breaks 8 × Ie (256 A), so it can make the 163.7 A starting current and break locked-rotor current.
4. **Coil voltage** suited to control supply (230 V AC or 110 V AC/24 V DC) and number of auxiliary contacts for control/interlocks.
5. Electrical and mechanical life suitable for number of operations per hour.

#### Step 4: Overload relay
Thermal (bimetal) relay with range including I_FL, set at **1.0–1.05 × I_FL ≈ 27.3–28.6 A**, class 10 trip (operates within 10 s at 7.2 × setting), with single-phasing protection.

**Coordination:** overload relay curve protects for currents up to about 8–10 × I_FL; above the crossover point the fuse operates first, protecting the contactor.

**Answer (for assumed motor):** I_FL = 27.28 A; fuse ≈ 63 A gG HRC (or 40 A aM); contactor 32 A AC-3; overload relay set ≈ 28 A.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. In the fuse + contactor + overload relay scheme, who provides overload protection?
   A. The HRC fuse
   B. The contactor
   C. The thermal overload relay
   D. The supply transformer
   Answer: C. The fuse gives short-circuit protection and the contactor switches; the thermal relay handles overload. (Key point: Role of each device)

2. For the assumed 15 kW, 415 V, eta 0.90, pf 0.85 motor, I_FL is:
   A. 27.28 A
   B. 24.6 A
   C. 36.4 A
   D. 163.7 A
   Answer: A. I_FL = 15000/(sqrt(3) x 415 x 0.9 x 0.85) = 27.28 A. (Key point: Full-load current)

3. Why must the fuse be rated about 2-2.5 x I_FL for DOL starting (63 A gG)?
   A. So it blows during every start
   B. So it does not melt on the 6 x I_FL starting current lasting about 10 s
   C. To provide overload protection
   D. To equal the contactor rating
   Answer: B. Its pre-arcing time at the starting current must exceed the starting time, avoiding nuisance blowing. (Key point: Fuse rating)

4. Which utilisation category and rating suits this motor's contactor?
   A. AC-1, 16 A
   B. AC-4, 20 A
   C. AC-3, 32 A
   D. AC-3, 16 A
   Answer: C. AC-3 covers squirrel-cage motor starting and running, with Ie of at least 27.28 A, so 32 A. (Key point: Contactor selection)

## Related in Switchgear and Protection

- [Fuse selection for 250 kVA transformer](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Atransformer-fuse-selection-250kva) — Switchgear and Protection, chapter 3
- [Contactor for motor control and protection](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Acontactor-motor-control-protection) — Switchgear and Protection, chapter 4, asked 3×
- [Selecting HRC fuse rating for motor](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Ahrc-fuse-motor-rating) — Switchgear and Protection, chapter 3
- [Fuse selection for transformer, capacitor, lighting](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Afuse-selection-transformer-capacitor-lighting) — Switchgear and Protection, chapter 3
- [Feeder switching guideline; contactor in place of CB](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Afeeder-isolator-cb-guideline) — Switchgear and Protection, chapter 4
- [HRC fuse I²t and fuses in series](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Ahrc-fuse-i2t-series) — Switchgear and Protection, chapter 3

## Related in other subjects

- [Line pf of 35 kW induction motor with capacitors](https://www.bctengineer.com/question.md?key=semester_7%2Futilization_of_electrical_energy%3Ainduction-motor-35kw-capacitor-line-pf) — Utilization of Electrical Energy, chapter 6, asked 3×
- [Damper winding to make motor self starting](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machines_ii%3Adamper-winding-self-starting) — Electric Machines II, chapter 2
- [Induction motor equivalent circuit from no-load and blocked rotor tests](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aim-noload-blocked-400v-equivalent) — Electrical Machines I, chapter 5
- [Reactor to protect circuit breaker of small station](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Areactor-protect-circuit-breaker) — Power Plant Equipment, chapter 4