# Pilot current with tap change (10 MVA)

Switchgear and Protection · Chapter 7: Protective Relays

- Asked in: 2071 Magh, 8 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/pilot-current-10mva-tap
- Whole chapter: https://www.bctengineer.com/md/semester_6/switchgear_and_protection/chapter-7

## Question

A 10 MVA, 132/33 kV, star-delta, three-phase, 50 Hz transformer is connected in delta on the low voltage side and in star with star point earthed on the high voltage side. If the CTs on the high voltage have a ratio of 75/1 A, determine the CT ratio on the low voltage side. What would be the current circulating through pilots for a through fault due to which a current of 5 times the full load occurs if the voltage tapping is set to 128 kV at the time of occurrence of fault?

## Short answer

LV CT ratio is N = 75 x (132/33)/√3 = 173.2 : 1, star connected. At 128 kV tap and 5 times full load, LV pilot current is 874.77/173.2 = 5.05 A, HV pilot current is √3 x 225.53/75 = 5.21 A, giving 0.158 A relay unbalance.

## Answer

HV is star connected, so the HV CTs are connected in **delta**; LV is delta connected, so the LV CTs are connected in **star**. The LV CT ratio is chosen so that pilot currents balance at the nominal ratio 132/33 kV. A tap change upsets this balance and a spill current flows.

**Data:** 10 MVA, 132/33 kV; HV CTs 75/1 (in delta); through fault = 5 × full load; tap set at 128 kV.

#### Step 1: LV CT ratio
For HV current I_H, the delta of HV CTs gives a pilot current √3 I_H / 75. The LV CTs (ratio N:1, star) give I_L / N, with I_L = 4 I_H (132/33).

```text
I_L / N = √3 I_H / 75
N = 75 × (I_L/I_H) / √3 = 75 × 4 / √3 = 173.2
LV CT ratio = 173.2 : 1
```

#### Step 2: Fault currents with 128 kV tap
Full-load current on the LV (33 kV) side:
```text
I_FL(LV) = 10 × 10⁶ / (√3 × 33 × 10³) = 174.95 A
Through-fault LV current = 5 × 174.95 = 874.77 A
HV current with tap at 128 kV = 874.77 × 33/128 = 225.53 A
```

#### Step 3: Pilot currents
```text
From LV CTs: 874.77 / 173.2 = 5.051 A
From HV CTs: √3 × 225.53 / 75 = 5.208 A
Out-of-balance (relay) current = 5.208 − 5.051 = 0.158 A
```

**Answer:** LV CT ratio = **173.2 : 1** (star connected). For the through fault with the tap at 128 kV, the pilot currents are about **5.05 A** (LV side) and **5.21 A** (HV side), so an unbalanced current of **0.158 A** circulates through the relay. A percentage-biased relay is needed so that this does not cause tripping. (If "5 times full load" is taken on the HV side, the corresponding values are 5.05 A, 4.90 A and 0.153 A.)

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. How is the LV CT ratio N found?
   A. Equating LV pilot current I_L/N with the HV delta pilot current sqrt(3) I_H/75 at nominal ratio
   B. Making N equal to the HV CT ratio
   C. Making N = 33/132 × 75
   D. Dividing 75 by sqrt(3)
   Answer: A. Pilot currents must balance at nominal ratio, giving N = 75 × 4/sqrt(3) = 173.2. (Key point: Condition for LV CT ratio)

2. The LV CT ratio is:
   A. 300 : 1
   B. 75 : 1
   C. 43.3 : 1
   D. 173.2 : 1
   Answer: D. I_L = 4 I_H, so N = 75 × 4 / sqrt(3) = 173.2. (Key point: LV CT ratio value)

3. Why does a through fault with the tap at 128 kV cause current in the relay?
   A. The CTs are connected wrongly
   B. The tap changes the HV current for a given LV current, upsetting the CT balance set for 132/33
   C. The fault is internal
   D. The pilot wires are open
   Answer: B. CT ratios were matched for 132/33 kV; with 128 kV tap the HV current rises, leaving a spill current. (Key point: Effect of tap change)

4. The out-of-balance pilot current is about 0.158 A. What remedy keeps the relay from tripping?
   A. Open-circuit the CTs
   B. Use a percentage-biased differential relay
   C. Remove the LV CTs
   D. Increase fault current
   Answer: B. A biased relay raises its operating level with through current, so the small spill does not trip it. (Key point: Result and remedy)

## Related in Switchgear and Protection

- [CT ratio for 33/6.6 kV star/delta (400/5)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Adifferential-ct-33-6-6kv-400) — Switchgear and Protection, chapter 7
- [CT ratio for 33/6.6 kV star/delta (300:5)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Adifferential-ct-33-6-6kv-300) — Switchgear and Protection, chapter 7
- [IDMT relays across 132/33 kV transformer (2000 A)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aidmt-132-33kv-2000a) — Switchgear and Protection, chapter 7
- [IDMT relays across 132/33 kV transformer (2700 A)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aidmt-132-33kv-2700a-graph) — Switchgear and Protection, chapter 7
- [IDMT relays across 132/11 kV transformer (3500 A)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aidmt-132-11kv-3500a) — Switchgear and Protection, chapter 7
- [Percentage differential relay: 125 MVA transformer](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Apercentage-differential-125mva) — Switchgear and Protection, chapter 7

## Related in other subjects

- [500 kVA delta/star transformer efficiency](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Athree-phase-500kva-33-11-efficiency) — Electrical Machine, chapter 2
- [Nominal-T 100 km line, 50 MVA at 132 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Anominal-t-100km-50mva) — Power System Analysis I, chapter 6
- [Currents and efficiency of 132/11 kV transformer at 5 MW](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Astar-delta-132-11kv-5mw-currents) — Electrical Machines I, chapter 2, asked 3×
- [Charging current of 60 Hz horizontal 132 kV line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Ahorizontal-60hz-132kv-charging) — Power System Analysis I, chapter 4