# RRRV from short circuit test (220 kV)

Switchgear and Protection · Chapter 6: Circuit Breakers

- Asked in: 2078 Chaitra, 6 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/rrrv-220kv-test
- Whole chapter: https://www.bctengineer.com/md/semester_6/switchgear_and_protection/chapter-6

## Question

In a short circuit test on a 220 kV 3-phase system, the breaker gave the following results: p.f. of the fault 0.45, recovery voltage 0.9 of full line value; the breaking current is symmetrical and the restriking transient had a natural frequency of 18 kHz. Determine the rate of rise of restriking voltage. Assume that the fault is grounded.

## Short answer

For the grounded fault, V_r=144.37 kV and peak restriking voltage is 288.75 kV reached at 27.78 μs, so average RRRV is 10.39 kV/μs; maximum instantaneous RRRV is 16.33 kV/μs.

## Answer

The **RRRV** is the rate at which the voltage across the CB contacts rises after the arc is extinguished at current zero.

#### Method
- Peak phase voltage: *V_m* = √2 × *V_L*/√3.
- At current zero the instantaneous system voltage is *V_m* sin φ (fault current lags by φ, cos φ = fault p.f.).
- Active recovery voltage: *V_r* = *k* × sin φ × *V_m*, where *k* is the recovery voltage factor (0.9 of full line value).
- For an **ungrounded** symmetrical fault the first pole to clear would see 1.5 times this (first-pole-to-clear factor 1.5); here the fault is grounded, so the factor is 1.
- Restriking voltage peak = 2 *V_r*, reached at *t* = 1/(2*f_n*).
- RRRV (average up to the peak, the usual textbook value) = 2*V_r* / *t* = 4 *f_n* *V_r*. The maximum instantaneous rate is *ω_n V_r*.

#### Data
*V_L* = 220 kV, cos φ = 0.45, *k* = 0.9, *f_n* = 18 kHz, fault grounded (factor 1).
```text
sin φ = √(1 − 0.45²)          = 0.8930
V_m   = √2 × 220/√3           = 179.63 kV
V_r   = 0.9 × 0.8930 × 179.63 = 144.37 kV
Peak restriking = 2 V_r       = 288.75 kV
t = 1/(2 f_n) = 1/(2×18000)   = 27.78 μs
RRRV = 288.75 kV / 27.78 μs   = 10.39 kV/μs
```
Maximum instantaneous rate (at *t* = 1/(4*f_n*) = 13.9 μs):
```text
ω_n V_r = 2π × 18000 × 144.37 kV
        = 16.33 kV/μs
```
**Answer: RRRV ≈ 10.39 kV/μs (average up to the first peak of 288.75 kV); maximum instantaneous RRRV ≈ 16.33 kV/μs.**

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. For a 220 kV system the peak phase voltage V_m is
   A. 220 kV
   B. 311 kV
   C. 179.6 kV
   D. 127 kV
   Answer: C. V_m = sqrt(2) x 220/sqrt(3) = 179.63 kV. (Key point: Peak phase voltage)

2. With pf 0.45 and k = 0.9, V_r is
   A. 144.4 kV
   B. 72.7 kV
   C. 161.7 kV
   D. 289 kV
   Answer: A. sin(phi) = 0.893, V_r = 0.9 x 0.893 x 179.63 = 144.37 kV. (Key point: Active recovery voltage)

3. With f_n = 18 kHz, the restriking voltage peak of 2 V_r is reached at
   A. 55.6 us
   B. 13.9 us
   C. 27.8 us
   D. 6.9 us
   Answer: C. t = 1/(2 f_n) = 27.78 us. (Key point: Time to peak)

4. The average RRRV for the grounded fault is
   A. 10.39 kV/us
   B. 16.33 kV/us
   C. 5.2 kV/us
   D. 15.6 kV/us
   Answer: A. 288.75 kV / 27.78 us = 10.39 kV/us; 16.33 kV/us is the maximum instantaneous rate w_n V_r. (Key point: RRRV result)

## Close variants set in other exams

- [RRRV from short circuit test (132 kV)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Arrrv-132kv-test) — Switchgear and Protection, chapter 6, asked 2×

## Related in Switchgear and Protection

- [Recovery, restriking voltage, RRRV and derivation](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Arestriking-voltage-derivation) — Switchgear and Protection, chapter 6
- [Restriking voltage vs recovery voltage](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Arestriking-vs-recovery-voltage) — Switchgear and Protection, chapter 6
- [Restriking voltage numerical (6.6 kV, 8 mH)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Arestriking-6-6kv-8mh) — Switchgear and Protection, chapter 6, asked 2×
- [Restriking voltage numerical (11 kV, 10 mH)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Arestriking-11kv-10mh) — Switchgear and Protection, chapter 6, asked 2×
- [Breaking MVA and making kA (800 A, 33 kV)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Acb-breaking-making-800a) — Switchgear and Protection, chapter 6
- [Resistance switching numerical (220 kV, 600 Ω)](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aresistance-switching-220kv) — Switchgear and Protection, chapter 6, asked 2×

## Related in other subjects

- [Tower dimensions for 220 kV single circuit line](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atower-dimensions-220kv) — Transmission and Distribution System Design, chapter 4, asked 2×
- [Tower dimensions for 220 kV double circuit line](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atower-dimensions-220kv-double-circuit) — Transmission and Distribution System Design, chapter 4, asked 2×
- [220 kV line, 200 MW: sending end from ABCD](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Aabcd-220kv-200mw) — Power System Analysis I, chapter 6
- [Air clearances for 220 kV single circuit line](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Aair-clearances-220kv-single-circuit) — Transmission and Distribution System Design, chapter 4