# Differential protection of power transformer

Switchgear and Protection · Chapter 7: Protective Relays

- Asked in: 2073 Magh, 6 marks
- Video: [Learn the basics of differential protection of Transformers](https://www.youtube.com/watch?v=z7a3KsoJh4M) — electrical engineerr
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_6/switchgear_and_protection/transformer-differential-protection
- Whole chapter: https://www.bctengineer.com/md/semester_6/switchgear_and_protection/chapter-7

## Question

With a neat sketch explain the operation of differential protection scheme for a power transformer.

## Short answer

Differential protection compares CT secondary currents from both sides of the transformer. Under normal or external fault conditions, currents balance and no current flows in relay. For an internal fault, imbalance current operates the relay. CT connections correct phase shift, and percentage bias with harmonic restraint ensures stability against inrush and CT mismatch.

## Answer

**Differential (Merz-Price) protection** of a transformer compares the currents entering and leaving the transformer. For a normal load or an external fault these currents balance, so no current flows in the relay. For an internal fault they do not balance, and the difference current operates the relay.

```text
      HV side                     LV side
 ──CT1──┬──[ POWER TRANSFORMER ]──┬──CT2──
   (Y)  │      (Δ / Y)            │  (Δ)
        i1                        i2
        │      ┌──────────┐      │
        └──────┤ OC  │ RC ├──────┘
     pilot     │  relay   │   pilot
               └──────────┘
   OC = operating coil (carries i1 − i2)
   RC = restraining coil (carries (i1+i2)/2)
```

#### Operation

1. CTs are placed on both sides, and their secondaries are joined by pilot wires so that, under healthy conditions, the secondary currents circulate and the relay operating coil carries almost no current.
2. **External fault / load:** I1 and I2 rise together and the circulating currents stay equal, so the relay does not trip (it is stable).
3. **Internal fault** (winding to earth, phase-to-phase, turn-to-turn): extra current flows from one or both sides into the fault, the secondary currents differ, and (i1 − i2) flows in the operating coil. When it exceeds the setting, the relay trips the HV and LV breakers.

#### Special points for transformers

- **CT ratios:** chosen so that the secondary currents are equal, i.e. in inverse proportion to the voltage ratio.
- **CT connections:** CTs on the star side are connected in delta and CTs on the delta side in star, to correct the 30° phase shift and to block zero-sequence current for external earth faults.
- **Percentage (biased) relay:** the restraining coil makes the trip setting rise with through current, so CT mismatch, tap changing and CT saturation do not cause false tripping.
- **Magnetising inrush:** at switch-on, a large inrush current flows on one side only. It is rich in second harmonic, so harmonic restraint is used to block tripping.

**Use:** standard main protection for transformers above about 5 MVA.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. For an external fault the differential relay:
   A. Trips
   B. Stays stable because the currents balance and no current flows in the operating coil
   C. Trips after delay
   D. Short-circuits the CTs
   Answer: B. Currents entering and leaving are equal, so the difference is zero. (Key point: Principle)

2. On an internal fault, the operating coil carries:
   A. i1 + i2
   B. i1 − i2, which trips both breakers when above setting
   C. Zero
   D. Only magnetising current
   Answer: B. Fault current feeding into the zone unbalances the secondaries. (Key point: Internal fault)

3. Why are star-side CTs connected in delta?
   A. Increase burden
   B. Correct the 30° phase shift and block zero-sequence current
   C. Reduce cost
   D. Increase ratio
   Answer: B. Needed for correct phase comparison and external earth fault stability. (Key point: CT connection)

4. Magnetising inrush is prevented from tripping the relay by:
   A. Higher CT ratio
   B. Second-harmonic restraint
   C. Removing bias
   D. Open-circuiting CTs
   Answer: B. Inrush is rich in second harmonic, which is used to block tripping. (Key point: Inrush)

## Related in Switchgear and Protection

- [Converting IDMT scheme to differential protection](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aidmt-to-differential-transformer) — Switchgear and Protection, chapter 7
- [Differential protection: 11 kV, 100 MVA generator](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Agenerator-differential-11kv-6-ohm) — Switchgear and Protection, chapter 7
- [Unit protection scheme](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aunit-protection-scheme) — Switchgear and Protection, chapter 7
- [Basic requirements of a protection scheme](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Abasic-requirements-protection-scheme) — Switchgear and Protection, chapter 1, asked 3×
- [Percentage differential relay: 125 MVA transformer](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Apercentage-differential-125mva) — Switchgear and Protection, chapter 7
- [Protection requirements; protective system vs scheme](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aprotective-system-vs-scheme) — Switchgear and Protection, chapter 1

## Related in other subjects

- [Transformer protection, selection and vector group](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Atransformer-protection-vector-group) — Power Plant Design, chapter 4
- [Protection for alternator and step-up transformer](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Amega-project-protection) — Power Plant Design, chapter 4
- [Transformer no-load and load operation, constant core flux](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3Aideal-transformer-noload-load-constant-flux) — Electrical Machines I, chapter 2, asked 5×
- [Transformer operation; flux constant at any load](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atransformer-load-noload-flux-constant) — Electrical Machine, chapter 2, asked 3×