# Need for excitation and improving dynamic response

Power Plant Equipment · Chapter 3: Var/Voltage Control in Hydrogenerating Systems

- Asked in: 2073 Chaitra, 8 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_7/power_plant_equipment/excitation-dynamic-improvement
- Whole chapter: https://www.bctengineer.com/md/semester_7/power_plant_equipment/chapter-3

## Question

Why do we need excitation system in power plants? How the dynamic response of excitation system can be improved? Explain with appropriate diagram and mathematical deduction.

## Short answer

Excitation maintains terminal voltage and enhances transient stability. Dynamic response is improved by rate-feedback from field voltage to damp oscillations, feedback around the exciter to reduce its time constant, fast static exciters, and a power system stabilizer.

## Answer

#### Need of excitation system

A synchronous generator needs DC field current to build up its flux. The excitation system supplies this current and controls it so that:

- terminal voltage stays constant from no load to full load;
- reactive power is shared properly among parallel machines;
- the field is "forced" quickly during faults to keep the machine in step (better transient stability);
- field current stays inside the machine's capability limits.

#### Basic loop and its limitation

```text
Vref    +--------+  +--------+ Efd +--------+  Vt
 -->(Σ)->|  K_A   |->|  K_E   |---->|  K_G   |--+-->
    ^-   |1+sT_A  |  |1+sT_E  |     |1+sT_G  |  |
    |    +--------+  +--------+     +--------+  |
    +-------------------------------------------+
```

With loop gain $K = K_AK_EK_G$, the steady-state error for a step in $V_{ref}$ is

$$
e_{ss} = \frac{1}{1+K}
$$

Raising $K$ lowers the error but, with three lags in the loop, the response becomes oscillatory and finally unstable. The exciter time constant $T_E$ (about 0.5 to 1 s for a DC exciter) is the main cause of slow response.

#### Methods to improve the dynamic response

**1. Rate (derivative) feedback via a stabilizing transformer.** Feed back $H_F = \dfrac{sK_F}{1+sT_F}$ from $E_{fd}$ to the amplifier input. The closed loop becomes

$$
\frac{V_t}{V_{ref}} = \frac{G_AG_EG_G}{1+G_AG_EH_F+G_AG_EG_G}
$$

The extra term $G_AG_EH_F$ contains $s$, so it adds damping only during transients; at steady state ($s\to0$) it vanishes and the low error is kept. Hence high gain and good damping are obtained together.

**2. Reducing the effective exciter time constant by feedback.** Put a proportional feedback $K_f$ around the exciter:

$$
\begin{aligned}
\frac{E_{fd}}{V_R} &= \frac{\dfrac{K_E}{1+sT_E}}{1+\dfrac{K_EK_f}{1+sT_E}} = \frac{K_E}{1+K_EK_f+sT_E} \\
&= \frac{K_E/(1+K_EK_f)}{1+s\,\dfrac{T_E}{1+K_EK_f}}
\end{aligned}
$$

The time constant falls from $T_E$ to $T_E/(1+K_EK_f)$: the exciter responds $(1+K_EK_f)$ times faster. The lost gain is made up in the amplifier.

**3. Fast exciters.** Replace rotating DC exciters by static (thyristor) or brushless high-initial-response exciters with small time constants and high **ceiling voltage** (2 to 3 times rated), so field current rises quickly.

**4. Power system stabilizer (PSS).** Adds a signal from rotor speed or electrical power through lead–lag blocks, giving positive damping to low-frequency rotor oscillations that a fast AVR may otherwise make worse.

**5. Lead compensation** in the regulator to cancel the largest lag.

Together these give a fast rise, small overshoot and small steady-state error.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Why is an excitation system needed in a power plant?
   A. To supply field current and keep terminal voltage constant and share reactive power
   B. To increase turbine speed
   C. To generate steam
   D. To control frequency
   Answer: A. The generator needs DC field current, which is controlled to regulate voltage and VAr. (Key point: Why needed)

2. What is the main cause of slow response in a DC excitation loop?
   A. The sensor time constant
   B. The exciter time constant T_E
   C. The amplifier gain
   D. The PSS
   Answer: B. T_E (about 0.5-1 s) is the largest lag. (Key point: Slow response cause)

3. With proportional feedback Kf around the exciter, the effective time constant becomes:
   A. T_E (1 + K_E K_f)
   B. T_E/(1 + K_E K_f)
   C. T_E K_E K_f
   D. T_E - K_f
   Answer: B. Efd/VR = KE/(1+KEKf+sTE), so the time constant is TE/(1+KEKf), making it faster. (Key point: Feedback around exciter)

4. What gives a quicker field current rise in modern exciters?
   A. Small time constant and high ceiling voltage (static or brushless)
   B. Large exciter inductance
   C. Lower ceiling voltage
   D. Slip rings
   Answer: A. Static or brushless exciters with small time constants and high ceiling (2-3 times rated) force field current quickly. (Key point: Fast exciters)

## Related in Power Plant Equipment

- [Dynamic response of excitation system](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Aexcitation-dynamic-response) — Power Plant Equipment, chapter 3, asked 3×
- [Excitation system with stabilizing transformer: transfer function](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Aexcitation-stabilizing-transformer-model) — Power Plant Equipment, chapter 3, asked 13×
- [Functional block diagram of excitation control](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Aexcitation-control-block-diagram) — Power Plant Equipment, chapter 3
- [Brush excitation system](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Abrush-excitation-system) — Power Plant Equipment, chapter 3
- [Function of excitation system and its transfer function](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Aexcitation-function-tf) — Power Plant Equipment, chapter 3, asked 2×
- [Static excitation system](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Astatic-excitation-system) — Power Plant Equipment, chapter 3

## Related in other subjects

- [Why do we need DFT](https://www.bctengineer.com/question.md?key=semester_7%2Fdigital_signal_analysis_and_processing%3Awhy-need-dft) — Digital Signal Analysis and Processing, chapter 7, asked 6×
- [Why do we need FFT](https://www.bctengineer.com/question.md?key=semester_7%2Fdigital_signal_analysis_and_processing%3Awhy-need-fft) — Digital Signal Analysis and Processing, chapter 7, asked 2×
- [Static vs dynamic mathematical model](https://www.bctengineer.com/question.md?key=semester_8%2Fsimulation_and_modeling%3Astatic-vs-dynamic-math-model) — Simulation and Modeling, chapter 2, asked 3×
- [Dynamic mathematical model with example](https://www.bctengineer.com/question.md?key=semester_8%2Fsimulation_and_modeling%3Adynamic-mathematical-model) — Simulation and Modeling, chapter 2, asked 2×