title: "Fault current: four 1600 kVA generators"
subject: "Power Plant Equipment"
chapter: 4
key: "semester_7/power_plant_equipment:fault-four-1600kva-generators"
source: https://www.bctengineer.com/q/semester_7/power_plant_equipment/fault-four-1600kva-generators
site: BCT Engineering
---

# Fault current: four 1600 kVA generators

Power Plant Equipment · Chapter 4: Substation Equipments

- Asked in: 2074 Asoj, 4+4 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_7/power_plant_equipment/fault-four-1600kva-generators
- Whole chapter: https://www.bctengineer.com/md/semester_7/power_plant_equipment/chapter-4

## Question

Below figure shows 4 Nos of identical generators operating in parallel. Each generator is rated as 1600 kVA, 11kV, Xg = 0.2 pu. [Figure: G1, G2, G3, G4, each through Xg, connected to an 11 kV busbar at points A, B, C, D; an outgoing feeder from the busbar between B and C through a circuit breaker and a reactor X = 10 Ω, with a 3-phase to ground fault at its end] (i) Calculate fault current in outgoing feeder and fault current supplied by each generator. (ii) If reactors of 5 ohm each are connected between point A and B, point C and D respectively. Calculate fault current in outgoing feeder and fault current supplied by each generator.

## Short answer

Using 11 kV phase voltage 6350.85 V and generator reactance 15.125 Ω, four parallel generators plus 10 Ω feeder give 13.781 Ω, so fault current is 460.83 A, 115.21 A per generator. With 5 Ω bus reactors between A-B and C-D, total current is 443.57 A; G1/G4 supply 95.16 A each, G2/G3 supply 126.62 A each.

## Answer

Work in ohms at 11 kV. Phase voltage $V_{ph} = 11000/\sqrt3 = 6350.85$ V. Fault current $I_f = V_{ph}/X_{total}$.

$$
\begin{aligned}
Z_{base} &= \frac{11^2}{1.6} = 75.625\ \Omega \\
X_g &= 0.2\times75.625 = 15.125\ \Omega
\end{aligned}
$$

```text
  G1      G2       G3      G4
  |Xg     |Xg      |Xg     |Xg
  A--[5]--B----+---C--[5]--D   11 kV bus
               |       ([5] only in part ii)
              CB
               |
            X=10 ohm
               |
               F
```

#### (i) Without bus reactors

All four generators are directly in parallel:

$$
\begin{aligned}
X_{par} &= \frac{15.125}{4} = 3.781\ \Omega \\
X_{total} &= 3.781 + 10 = 13.781\ \Omega \\
I_f &= \frac{6350.85}{13.781} = 460.83\ \text{A}
\end{aligned}
$$

Each generator supplies $460.83/4 = 115.21$ A. (Fault MVA $=\sqrt3\times11\times0.46083 = 8.78$ MVA.)

#### (ii) With 5 Ω reactors between A–B and C–D

G1 and G4 now reach the feeder through 5 Ω; G2 and G3 connect directly.

$$
\begin{aligned}
X_{G1} = X_{G4} &= 15.125 + 5 = 20.125\ \Omega \\
\frac{1}{X_{par}} &= \frac{2}{20.125} + \frac{2}{15.125} = 0.23161 \\
X_{par} &= 4.3176\ \Omega \\
X_{total} &= 4.3176 + 10 = 14.3176\ \Omega \\
I_f &= \frac{6350.85}{14.3176} = 443.57\ \text{A}
\end{aligned}
$$

The bus voltage behind the reactors is $I_f X_{par} = 443.57\times4.3176 = 1915.2$ V, so

$$
\begin{aligned}
I_{G1} = I_{G4} &= \frac{1915.2}{20.125} = 95.16\ \text{A} \\
I_{G2} = I_{G3} &= \frac{1915.2}{15.125} = 126.62\ \text{A}
\end{aligned}
$$

Check: $2(95.16) + 2(126.62) = 443.57$ A.

**Answer:** (i) $I_f$ = **460.83 A**, each generator **115.21 A**. (ii) $I_f$ = **443.57 A**; G1 and G4 supply **95.16 A** each, G2 and G3 supply **126.62 A** each.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. What is Xg = 0.2 pu for a 1.6 MVA, 11 kV generator?
   A. 15.125 ohm
   B. 0.2 ohm
   C. 75.6 ohm
   D. 7.56 ohm
   Answer: A. Z_base = 11^2/1.6 = 75.625 ohm; times 0.2 = 15.125 ohm. (Key point: Generator reactance in ohms)

2. With four generators directly in parallel and a 10 ohm feeder, what is the fault current?
   A. 1843 A
   B. 460.8 A
   C. 6350 A
   D. 230 A
   Answer: B. X_total = 15.125/4 + 10 = 13.78 ohm; I = 6350.85/13.78 = 460.8 A. (Key point: Part (i) fault current)

3. How much does each generator supply in part (i)?
   A. 460.8 A each
   B. 230.4 A each
   C. 115.2 A, equal because they are identical
   D. Different for each generator
   Answer: C. Identical generators in parallel share equally: 460.83/4. (Key point: Part (i) sharing)

4. With 5 ohm reactors between A-B and C-D, which generators supply less current and why?
   A. G2 and G3, because they have the extra 5 ohm
   B. All four equal
   C. G1 and G4 supply more because of the reactors
   D. G1 and G4, because they reach the feeder through the extra 5 ohm
   Answer: D. G1 and G4 branches are 20.125 ohm versus 15.125 ohm, so they supply 95.2 A versus 126.6 A. (Key point: Part (ii) sharing)

## Related in Power Plant Equipment

- [Fault current: two 50 MW generators, reactor inductance](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-50mw-inductance) — Power Plant Equipment, chapter 4
- [Fault current: 50 MW and 40 MW generators](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-50mw-40mw-equal-current) — Power Plant Equipment, chapter 4
- [Fault level: adding a third generator](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-third-generator-added) — Power Plant Equipment, chapter 4
- [Bus-bar reactor scheme with four generators](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Abus-bar-reactor-four-generators) — Power Plant Equipment, chapter 4, asked 2×
- [Fault level: three generators, feeder reactor](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-three-generators-feeder) — Power Plant Equipment, chapter 4
- [Fault current: two 500 kVA alternators](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-500kva-alternators) — Power Plant Equipment, chapter 4

## Related in other subjects

- [Fault through impedance at bus 2](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-impedance-bus2-actual-currents) — Power System Analysis II, chapter 3
- [Regulation of delta connected 1600 kVA alternator](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machines_ii%3Aregulation-delta-1600kva) — Electric Machines II, chapter 1
- [L-L fault current in kA at bus 3](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3All-fault-bus3-ka) — Power System Analysis II, chapter 5
- [SLG fault at mid-line through 4.033 Ω](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Aslg-fault-mid-line-motor) — Power System Analysis II, chapter 5