title: "Fault level: adding a third generator"
subject: "Power Plant Equipment"
chapter: 4
key: "semester_7/power_plant_equipment:fault-third-generator-added"
source: https://www.bctengineer.com/q/semester_7/power_plant_equipment/fault-third-generator-added
site: BCT Engineering
---

# Fault level: adding a third generator

Power Plant Equipment · Chapter 4: Substation Equipments

- Asked in: 2080 Baisakh, 6 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_7/power_plant_equipment/fault-third-generator-added
- Whole chapter: https://www.bctengineer.com/md/semester_7/power_plant_equipment/chapter-4

## Question

Following figure shows two generators operating parallel. i) If a 3-phase to ground fault occurs on the outgoing feeder, calculate the fault current and fault level on the feeder. ii) If a 3rd generator (G3: 10MVA, 11kV, X3=0.2 pu) is added at point 'C', calculate the value of reactor to be added on the outgoing feeder so that the fault level remains same as before. [Figure: G1 20 MVA, 11 kV, X1 = 0.1 pu (path-1) and G2 20 MVA, 11 kV, X2 = 0.1 pu (path-2) connected to a common busbar at points A and B; busbar extends to point C; outgoing feeder from the busbar through a C.B., fault point 'F' on the outgoing feeder]

## Short answer

Fault level is 400 MVA, fault current ≈ 20.99 kA. After adding G3, equivalent reactance drops to 0.04444 pu; to restore 0.05 pu total, add a feeder reactor of 0.00556 pu (0.0336 Ω).

## Answer

Fault MVA $=\text{MVA}_b/X_{eq}$. The feeder has no reactance at first (none given).

**Base:** 20 MVA, 11 kV; $Z_{base} = 11^2/20 = 6.05\ \Omega$; $I_{base} = \dfrac{20\times10^6}{\sqrt3\times11\times10^3} = 1049.7\ \text{A}$.

```text
 G1 20MVA   G2 20MVA   G3 10MVA (added)
  0.1pu      0.1pu      0.2pu
   |A         |B         |C
 ==+==========+==========+=== 11 kV
         |
        C.B.--[X]-- F
```

#### (i) Fault current and fault level (two generators)

$$
\begin{aligned}
X_{eq} &= \frac{0.1}{2} = 0.05\ \text{pu} \\
\text{Fault MVA} &= \frac{20}{0.05} = 400\ \text{MVA} \\
I_f &= \frac{1}{0.05}\times1049.7 = 20{,}995\ \text{A} \approx 20.99\ \text{kA}
\end{aligned}
$$

#### (ii) Reactor after adding G3

G3 on 20 MVA base: $X_3 = 0.2\times\dfrac{20}{10} = 0.4\ \text{pu}$.

$$
\begin{aligned}
\frac{1}{X_{eq}'} &= \frac{1}{0.1}+\frac{1}{0.1}+\frac{1}{0.4} = 22.5 \\
X_{eq}' &= 0.04444\ \text{pu} \;\Rightarrow\; \text{Fault MVA} = 450\ \text{MVA (too high)}
\end{aligned}
$$

To keep 400 MVA the total must stay at 0.05 pu:

$$
\begin{aligned}
X_{reactor} &= 0.05 - 0.04444 = 0.005556\ \text{pu} \\
X_{reactor}(\Omega) &= 0.005556\times6.05 = 0.0336\ \Omega
\end{aligned}
$$

**Answer:** (i) Fault level = **400 MVA**, $I_f \approx$ **20.99 kA**. (ii) Feeder reactor ≈ **0.00556 pu = 0.0336 Ω** keeps the fault level at 400 MVA after G3 is added.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. What is the fault level with G1 and G2 (20 MVA, 0.1 pu each)?
   A. 400 MVA
   B. 200 MVA
   C. 100 MVA
   D. 800 MVA
   Answer: A. X_eq = 0.05 pu; 20/0.05 = 400 MVA. (Key point: Two-generator fault level)

2. On the 20 MVA base, what is G3 (10 MVA, 0.2 pu)?
   A. 0.1 pu
   B. 0.4 pu
   C. 0.2 pu
   D. 0.8 pu
   Answer: B. 0.2 x 20/10 = 0.4 pu. (Key point: G3 conversion)

3. What does adding G3 do to the fault level without a reactor?
   A. Lowers it because more reactance is added
   B. Leaves it unchanged
   C. Raises it to 450 MVA because X_eq falls to 0.0444 pu
   D. Raises it to 800 MVA
   Answer: C. Another parallel source reduces X_eq, increasing the fault MVA. (Key point: Effect of G3)

4. What reactor restores the fault level to 400 MVA?
   A. 0.05 pu
   B. 0.0444 pu
   C. 0.4 pu
   D. 0.00556 pu (about 0.0336 ohm)
   Answer: D. Total must be 0.05 pu; 0.05 - 0.04444 = 0.00556 pu; times 6.05 = 0.0336 ohm. (Key point: Reactor value)

## Related in Power Plant Equipment

- [Fault level: three generators, feeder reactor](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-three-generators-feeder) — Power Plant Equipment, chapter 4
- [Fault current: two 50 MVA generators, feeder reactor](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-50mva-feeder-reactor) — Power Plant Equipment, chapter 4, asked 3×
- [Fault level: two 40 MVA generators, 2 Ω feeder](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-40mva-2-ohm-feeder) — Power Plant Equipment, chapter 4, asked 5×
- [Fault current: four 1600 kVA generators](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-four-1600kva-generators) — Power Plant Equipment, chapter 4
- [Fault current: 50 MW and 40 MW generators](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-50mw-40mw-equal-current) — Power Plant Equipment, chapter 4
- [Fault current: two 50 MW generators, reactor inductance](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-50mw-inductance) — Power Plant Equipment, chapter 4

## Related in other subjects

- [Fault level at end of two 200 km lines](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afault-two-stations-132kv-200km) — Power System Analysis II, chapter 3, asked 2×
- [L-G fault and 3-phase fault, 30 MVA generator](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Alg-fault-30mva-voltages-3phase) — Power System Analysis II, chapter 5
- [Power by two generators, 1.05∠5° and 1.05∠20° pu](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Atwo-generators-1-05-pu) — Power System Analysis I, chapter 3, asked 2×
- [Power by two generators, 1.1∠15° and 1.1∠0° pu](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Atwo-generators-1-1-pu) — Power System Analysis I, chapter 3, asked 2×