# Fault current: two 50 MW generators, reactor inductance

Power Plant Equipment · Chapter 4: Substation Equipments

- Asked in: 2069 Chaitra, 8 marks
- Video: [L10 switchgear and protection,  Current Limiting Reactor](https://www.youtube.com/watch?v=Y6pcGSmGlec) — Base Technical Academy
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_7/power_plant_equipment/fault-two-50mw-inductance
- Whole chapter: https://www.bctengineer.com/md/semester_7/power_plant_equipment/chapter-4

## Question

Figure below shows the single line diagram of parallel operated generators. Their ratings are: G1: capacity = 50 MW, 11kV, X1 = 0.16 pu based on its rating; G2: capacity = 50MW, 11kV, X2 = 0.16 pu based on its rating; Xl = 2 ohms. [Figure: G1 (through X1) and G2 (through X2), both star-grounded, connected to a common busbar; the feeder leaves the busbar through Xl] Calculate the fault current in the feeder during 3 phases to ground fault on the feeder. Calculate the value of inductance (in mH) of the reactor to be connected in series with Xl so that the fault current decreases by 40%.

## Short answer

On a 50 MVA, 11 kV base, the feeder fault current is 2895 A. To reduce fault current by 40%, add a series reactor of 1.462 ohm, which is 4.65 mH at 50 Hz.

## Answer

Ratings in MW are taken as MVA (unity power factor). Fault current $I_f = I_{base}/X_{eq}$; ohms to pu: $X_{pu} = X_\Omega\,\text{MVA}_b/\text{kV}^2$.

**Base:** 50 MVA, 11 kV; $Z_{base} = 11^2/50 = 2.42\ \Omega$; $I_{base} = \dfrac{50\times10^6}{\sqrt3\times11\times10^3} = 2624.3\ \text{A}$.

```text
  G1 50MW,0.16   G2 50MW,0.16
      |              |
  ====+======+=======+==== 11 kV
             |
           Xl=2 ohm + new L
             |
             F
```

#### Fault current

$$
\begin{aligned}
X_1\parallel X_2 &= \frac{0.16}{2} = 0.08\ \text{pu} \\
X_l &= \frac{2}{2.42} = 0.82645\ \text{pu} \\
X_{eq} &= 0.08 + 0.82645 = 0.90645\ \text{pu} \\
I_f &= \frac{2624.3}{0.90645} = 2895.2\ \text{A}
\end{aligned}
$$

(Fault MVA $= 50/0.90645 = 55.16$ MVA.)

#### Reactor for 40 % reduction in fault current

New $I_f = 0.6\times2895.2 = 1737.1$ A, so the total reactance must become $X_{eq}/0.6$:

$$
\begin{aligned}
X_{eq,new} &= \frac{0.90645}{0.6} = 1.51074\ \text{pu} \\
X_{add} &= 1.51074 - 0.90645 = 0.60430\ \text{pu} \\
X_{add}(\Omega) &= 0.60430\times2.42 = 1.4624\ \Omega \\
L &= \frac{1.4624}{2\pi\times50} = 4.655\times10^{-3}\ \text{H}
\end{aligned}
$$

**Answer:** $I_f$ ≈ **2895 A**; series reactor ≈ **1.462 Ω, i.e. L ≈ 4.65 mH** (fault current falls to about 1737 A).

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. On a 50 MVA, 11 kV base, what is the feeder Xl = 2 ohm in pu?
   A. 2 x 2.42 = 4.84 pu
   B. 2/2.42 = 0.826 pu
   C. 2/50 = 0.04 pu
   D. 2/11 = 0.18 pu
   Answer: B. Z_base = 11^2/50 = 2.42 ohm, so X_pu = 2/2.42 = 0.826 pu. (Key point: Per-unit conversion)

2. What are X_eq and the fault current in the feeder?
   A. 0.16 pu, 16.4 kA
   B. 0.906 pu, about 2895 A
   C. 0.90 pu, 55 A
   D. 1.65 pu, 1590 A
   Answer: B. X_eq = 0.16/2 + 0.826 = 0.906 pu and I_f = I_base/X_eq = 2624.3/0.906 = 2895 A. (Key point: Equivalent reactance and fault current)

3. To cut fault current by 40%, what must the total reactance become?
   A. X_eq x 0.6
   B. X_eq / 0.6
   C. X_eq x 0.4
   D. X_eq + 0.4
   Answer: B. Current is inversely proportional to reactance, so I = 0.6 I_old needs X_new = X_old/0.6 = 1.51 pu. (Key point: Condition for 40% reduction)

4. The added reactance is 1.462 ohm. How is L obtained at 50 Hz?
   A. L = X x 2 pi x 50
   B. L = X/(2 pi x 50) = 4.65 mH
   C. L = X/50 = 29 mH
   D. L = X x 50 = 73 H
   Answer: B. X = 2 pi f L so L = 1.462/(314.16) = 4.65 mH. (Key point: Converting reactor ohms to inductance)

## Related in Power Plant Equipment

- [Fault current: 50 MW and 40 MW generators](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-50mw-40mw-equal-current) — Power Plant Equipment, chapter 4
- [Fault current: two 50 MVA generators, feeder reactor](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-50mva-feeder-reactor) — Power Plant Equipment, chapter 4, asked 3×
- [Fault level: three generators, feeder reactor](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-three-generators-feeder) — Power Plant Equipment, chapter 4
- [Fault current: four 1600 kVA generators](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-four-1600kva-generators) — Power Plant Equipment, chapter 4
- [Bus-bar reactor scheme with four generators](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Abus-bar-reactor-four-generators) — Power Plant Equipment, chapter 4, asked 2×
- [Fault level: two 50 MVA generators, 50% reduction](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-50mva-50-percent) — Power Plant Equipment, chapter 4

## Related in other subjects

- [Reactance diagram: 50 MVA, 13.8 kV base, three generators](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-50mva-13-8kv) — Power System Analysis I, chapter 3
- [Reactance diagram: two generators, two motors, j50 Ω line](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-two-gens-two-motors) — Power System Analysis I, chapter 3
- [L-L fault current in kA at bus 3](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3All-fault-bus3-ka) — Power System Analysis II, chapter 5
- [HV bus fault and limiting reactor](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Ahv-bus-fault-reactor-limit) — Power System Analysis II, chapter 3