title: "Reactor to protect circuit breaker of small station"
subject: "Power Plant Equipment"
chapter: 4
key: "semester_7/power_plant_equipment:reactor-protect-circuit-breaker"
source: https://www.bctengineer.com/q/semester_7/power_plant_equipment/reactor-protect-circuit-breaker
site: BCT Engineering
---

# Reactor to protect circuit breaker of small station

Power Plant Equipment · Chapter 4: Substation Equipments

- Asked in: 2076 Chaitra, 5 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_7/power_plant_equipment/reactor-protect-circuit-breaker
- Whole chapter: https://www.bctengineer.com/md/semester_7/power_plant_equipment/chapter-4

## Question

A small generating station has two alternators of 2500KVA and 500KVA with percentage reactance of 8 & 6 percentage respectively. The circuit breakers are rated at 150,000kVA. Due to increase in system load it is intended to add a third generator of 10,000kVA rating and 7.5% reactance. If the system voltage is 3300volts, find the reactance X necessary to protect the C.B. [Figure: alternators A and B connected directly to the busbar, which feeds an outgoing circuit through the CB rated 150,000 kVA; the third generator C (10,000 kVA, 7.5%) is connected to the busbar through the reactor X]

## Short answer

On 10,000 kVA base, A and B parallel give 25.26%, and C is 7.5%. To keep fault level ≤150,000 kVA, total reactance must be 6.667%, so add a reactor of 1.56% (≈0.017 Ω) in series with the new generator.

## Answer

The C.B. must not see a fault level above its rating (150,000 kVA). G3 is connected to the bus through reactor $X$. For a fault on the outgoing circuit just beyond the C.B., all three machines feed the fault.

**Base:** 10,000 kVA, 3.3 kV; $Z_{base} = \dfrac{3.3^2}{10} = 1.089\ \Omega$. Percentage reactance on new base: $\%X_{new} = \%X\times\dfrac{\text{kVA}_b}{\text{kVA}}$.

```text
   A 2500kVA   B 500kVA    C 10000kVA,7.5%
     8%          6%          |
     |           |          [X]
 ====+===========+===========+==== 3.3 kV
           |
          CB 150,000 kVA
           |--- F
```

#### Reactances on 10,000 kVA base

| Machine | Calculation | %X |
|---|---|---|
| A | $8\times10000/2500$ | 32 % |
| B | $6\times10000/500$ | 120 % |
| C | given | 7.5 % |

$A\parallel B$: $\dfrac{32\times120}{152} = 25.263\ \%$, giving fault kVA $= 10000\times100/25.263 = 39{,}583$ kVA (safe).

If C were connected directly: $25.263\parallel7.5 = 5.783\ \%$, fault kVA $= 172{,}917$ kVA > 150,000 kVA. So a reactor is needed.

#### Required reactor

Allowed total reactance:

$$
\%X_{eq} = \frac{10000\times100}{150000} = 6.667\ \%
$$

$$
\begin{aligned}
\frac{1}{6.667} &= \frac{1}{25.263} + \frac{1}{7.5+X} \\
0.15 - 0.039583 &= 0.110417 = \frac{1}{7.5+X} \\
7.5 + X &= 9.0566 \\
X &= 1.5566\ \%
\end{aligned}
$$

In ohms:

$$
X_\Omega = \frac{1.5566}{100}\times1.089 = 0.01695\ \Omega
$$

**Answer:** Reactor $X$ ≈ **1.557 % on 10,000 kVA base ≈ 0.017 Ω** in series with the new generator keeps the fault level at 150,000 kVA.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. On 10,000 kVA base, what are the reactances of A (2500 kVA, 8%) and B (500 kVA, 6%)?
   A. 32% and 120%
   B. 8% and 6%
   C. 2% and 0.3%
   D. 320% and 1200%
   Answer: A. %X x 10000/kVA gives 32% and 120%. (Key point: Common base)

2. Why is a reactor required?
   A. The fault level is already below the breaker rating
   B. With C directly connected, the fault level is about 172,917 kVA, above the 150,000 kVA breaker rating
   C. A and B alone exceed the rating
   D. The breaker has no rating
   Answer: B. A parallel B is 25.26%, parallel C gives 5.78%, so 172,917 kVA exceeds the breaker. (Key point: Why a reactor is needed)

3. What total % reactance equals 150,000 kVA on a 10,000 kVA base?
   A. 15%
   B. 0.667%
   C. 6.667%
   D. 66.7%
   Answer: C. %X = 10000 x 100/150000 = 6.667%. (Key point: Target reactance)

4. Where is the reactor and what is its value?
   A. In series with A: X about 5%
   B. In parallel with C: X about 1.557%
   C. In series with the CB: X about 7.5%
   D. In series with C: X about 1.557% (0.017 ohm)
   Answer: D. 7.5 + X = 9.057%, so X = 1.557%, times 1.089 ohm = 0.017 ohm. (Key point: Reactor placement and value)

## Related in Power Plant Equipment

- [Fault current: two 500 kVA alternators](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-500kva-alternators) — Power Plant Equipment, chapter 4
- [Fault current: two 50 MVA generators, feeder reactor](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-two-50mva-feeder-reactor) — Power Plant Equipment, chapter 4, asked 3×
- [Feeder reactor: 40 and 30 MVA, 50% reduction](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-40-30mva-50-percent) — Power Plant Equipment, chapter 4, asked 4×
- [Feeder reactor: 40 and 30 MVA, 40% reduction](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Afault-40-30mva-40-percent) — Power Plant Equipment, chapter 4, asked 4×
- [Function of reactor in power system](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Areactor-function) — Power Plant Equipment, chapter 4, asked 3×
- [Bus-bar reactor scheme: 30 MVA and 50 MVA](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Abus-bar-reactor-30-50-mva) — Power Plant Equipment, chapter 4, asked 2×

## Related in other subjects

- [DC supply system in a generating station](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Adc-supply-system) — Power Plant Design, chapter 4
- [Percentage increase with parallel pipe at midpoint](https://www.bctengineer.com/question.md?key=semester_4%2Fhydraulics%3Aparallel-pipe-added-midpoint-increase) — Hydraulics, chapter 2
- [Short circuit MVA of feeder circuit breaker](https://www.bctengineer.com/question.md?key=semester_5%2Fpower_system_analysis_ii%3Afeeder-cb-short-circuit-mva) — Power System Analysis II, chapter 3, asked 2×
- [Reactance diagram: 300 MVA, 20 kV generator, two motors](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Areactance-diagram-300mva-20kv) — Power System Analysis I, chapter 3