# Water turbine transfer function and characteristics

Power Plant Equipment · Chapter 2: Power/Frequency Control in Hydro Generator System

- Asked in: 2081 Bhadra, 6 marks; 2072 Kartik, 8 marks (asked 2 times)
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_7/power_plant_equipment/water-turbine-tf-characteristics
- Whole chapter: https://www.bctengineer.com/md/semester_7/power_plant_equipment/chapter-2

## Question

Derive the transfer function of water turbine relating gate position and mechanical power output. Explain the special characteristic of hydraulic turbine.

## Short answer

The transfer function is (1 - Tw s)/(1 + 0.5 Tw s), with water starting time Tw = L U0/(g H0). It is non-minimum phase: a step gate opening initially reduces power to -2 pu before rising to +1 pu, due to water column inertia. This requires a special governor with transient droop for stability.

## Answer

The water turbine transfer function relates a small change in gate position to the change in mechanical power. Because the water column in the penstock has inertia, the turbine is a **non-minimum phase** system.

#### Derivation
**Assumptions:** lossless turbine, incompressible water, rigid penstock, and small changes about an operating point.

Velocity of water in the penstock: $U = K_u\,G\sqrt{H}$, where $G$ = gate opening and $H$ = head at the gate.

Turbine power: $P_m = K_p\,H\,U$.

Linearising and normalising by initial values ($U_0, G_0, H_0, P_{m0}$), with bar for per-unit change:
$$
\begin{aligned}
\Delta\bar U &= \tfrac{1}{2}\Delta\bar H + \Delta\bar G \\
\Delta\bar P_m &= \Delta\bar H + \Delta\bar U
\end{aligned}
$$
Eliminating $\Delta\bar H = 2(\Delta\bar U - \Delta\bar G)$:
$$
\Delta\bar P_m = 3\Delta\bar U - 2\Delta\bar G
$$

**Acceleration of the water column** (length $L$, area $A$): the net force from the head change accelerates the water mass,
$$
\rho L A\,\frac{d\Delta U}{dt} = -A\rho g\,\Delta H
\;\Rightarrow\; T_w\,\frac{d\Delta\bar U}{dt} = -\Delta\bar H
$$
where the **water starting time** is
$$
T_w = \frac{L\,U_0}{g\,H_0}
$$
In Laplace form: $T_w s\,\Delta\bar U = -2(\Delta\bar U - \Delta\bar G)$, so
$$
\frac{\Delta\bar U}{\Delta\bar G} = \frac{1}{1 + \tfrac{1}{2}T_w s}
$$
Substituting in $\Delta\bar P_m = 3\Delta\bar U - 2\Delta\bar G$:
$$
\frac{\Delta\bar P_m(s)}{\Delta\bar G(s)} = \frac{3}{1 + 0.5T_w s} - 2 = \frac{1 - T_w s}{1 + 0.5T_w s}
$$

#### Special characteristics of a hydraulic turbine
1. **Non-minimum phase response:** the transfer function has a zero in the right-half plane at $s = 1/T_w$. Power initially changes **opposite** to the gate movement. For a unit step in gate opening, power first falls to $-2$ pu and then rises to $+1$ pu with time constant $T_w/2$:
$$
\Delta\bar P_m(t) = 1 - 3e^{-2t/T_w}
$$
2. **Water inertia** decides the response. $T_w$ is typically 0.5–4 s and changes with load, because $U_0$ and $H_0$ change.
3. **Governor needs transient droop:** a fast governor with normal droop would be unstable. So hydro governors have a large temporary droop with a reset time (or slow integral action), making hydro units slower to respond than steam units.
4. **Water hammer:** quick gate closing causes pressure rise; gate speed must be limited.
5. Hydro turbines can start and pick up load quickly from standstill, so they are good for peaking and frequency control once the above is allowed for.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. After linearising, which relation between per-unit power, flow velocity and gate is obtained?
   A. dPm = 3dU - 2dG
   B. dPm = 2dU - 3dG
   C. dPm = dU + dG
   D. dPm = 3dG - 2dU
   Answer: A. With dH = 2(dU - dG), dPm = dH + dU = 3dU - 2dG. (Key point: Linearised relations)

2. What is the water starting time Tw?
   A. Tw = g H0/(L U0)
   B. Tw = L U0/(g H0)
   C. Tw = L H0/(g U0)
   D. Tw = U0/(g L H0)
   Answer: B. Tw = L U0/(g H0), the time for head H0 to accelerate the water column to U0. (Key point: Water starting time)

3. What is the final turbine transfer function dPm/dG?
   A. (1 + Tw s)/(1 - 0.5 Tw s)
   B. 1/(1 + 0.5 Tw s)
   C. (1 - Tw s)/(1 + 0.5 Tw s)
   D. (1 - 0.5 Tw s)/(1 + Tw s)
   Answer: C. 3/(1+0.5Tw s) - 2 = (1 - Tw s)/(1 + 0.5 Tw s). (Key point: Transfer function)

4. Why is a hydro turbine called non-minimum phase?
   A. It has a pole at the origin
   B. It has no inertia
   C. Its output follows the gate immediately
   D. Its transfer function has a right-half-plane zero, so power first moves opposite to the gate
   Answer: D. The zero at s = 1/Tw makes the initial response reverse, caused by water inertia. (Key point: Non-minimum phase)

## Related in Power Plant Equipment

- [Special characteristics of hydraulic turbine](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Ahydraulic-turbine-characteristics) — Power Plant Equipment, chapter 2
- [Hydraulic turbine characteristics and water starting time](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Ahydraulic-turbine-water-starting) — Power Plant Equipment, chapter 2
- [Water turbine response to step gate change](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Awater-turbine-step-gate) — Power Plant Equipment, chapter 2, asked 2×
- [Gas turbine 6:1: power output and efficiency](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Agt-6-1-power-efficiency) — Power Plant Equipment, chapter 6, asked 2×
- [Gas turbine 6:1: generator power output](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Agt-6-1-power-output) — Power Plant Equipment, chapter 6, asked 2×
- [Gas turbine 5:1: power, efficiency, work ratio](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_plant_equipment%3Agt-5-1-work-ratio) — Power Plant Equipment, chapter 6

## Related in other subjects

- [Transfer function from state equations, output x1](https://www.bctengineer.com/question.md?key=semester_3%2Fcontrol_systems%3Atf-from-de-3x1-x2) — Control Systems, chapter 8, asked 2×
- [Transfer function from state equations, output x2](https://www.bctengineer.com/question.md?key=semester_3%2Fcontrol_systems%3Atf-from-de-3x1-x2-y) — Control Systems, chapter 8, asked 2×
- [PID controller block diagram, transfer function, characteristics](https://www.bctengineer.com/question.md?key=semester_3%2Fcontrol_systems%3Apid-bd-tf-characteristics) — Control Systems, chapter 7
- [Mass inside a mass: transfer function and F-I analogy](https://www.bctengineer.com/question.md?key=semester_3%2Fcontrol_systems%3Atf-fi-m1-m2-nested) — Control Systems, chapter 2