title: "Generator choice and SCR versus stability"
subject: "Power Plant Design"
chapter: 4
key: "semester_8/power_plant_design:generator-choice-scr-stability"
source: https://www.bctengineer.com/q/semester_8/power_plant_design/generator-choice-scr-stability
site: BCT Engineering
---

# Generator choice and SCR versus stability

Power Plant Design · Chapter 4: Electric System Design of a Power Plant

- Asked in: 2071 Bhadra, 5+5 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_8/power_plant_design/generator-choice-scr-stability
- Whole chapter: https://www.bctengineer.com/md/semester_8/power_plant_design/chapter-4

## Question

Discuss the various factors which should be considered for the choice of generator during the design of a power plant. Also clarify analytically that lower the short circuit ratio (SCR), lower be the stability of the system.

## Short answer

Factors: MVA/pf, voltage, speed/poles, shaft type, reactances/SCR, inertia, efficiency, insulation, cooling, excitation, NGT grounding, grid spec, transport limits. Lower SCR means higher Xd, so maximum power Pmax = EV·SCR decreases, load angle increases for same power, and synchronizing power coefficient reduces, lowering steady-state and transient stability margins.

## Answer

#### Factors for the choice of generator
1. **Rating (MVA) and power factor:** $S = P_{turbine}\,\eta_g / \cos\phi$; power factor usually 0.85–0.9 lagging so the unit can supply reactive power. Some overload margin (e.g. 10%) is often specified.
2. **Rated voltage:** usually 6.6 kV or 11 kV for hydro units (higher, e.g. 13.8–15.75 kV, for very large units); chosen with GSU and bus/cable cost.
3. **Speed and number of poles:** fixed by the turbine: $N = 120f/p$. Hydro units are slow, salient-pole machines with many poles.
4. **Shaft arrangement:** vertical (large Francis/Kaplan) or horizontal (small Pelton/Francis).
5. **Reactances and SCR:** $X''_d$ sets fault level and breaker rating; SCR and $X_d$ set stability and voltage regulation.
6. **Inertia constant (GD²):** larger inertia limits speed rise on load rejection and improves stability, but costs more.
7. **Efficiency and losses:** high efficiency (above 97–98%) saves energy over the plant life.
8. **Insulation and temperature rise:** class F insulation with class B temperature rise is common; altitude derating above 1000 m.
9. **Cooling:** air-cooled (open or closed with air–water coolers) for hydro.
10. **Excitation system:** brushless for small/medium units, static for large units.
11. **Neutral grounding:** high-resistance grounding via NGT.
12. **Grid requirements:** capability curve, reactive power range, fault ride-through, harmonics.
13. **Transport and erection limits:** weight and size on hill roads; split stator if needed.
14. **Standards and cost:** IEC 60034; capital cost versus loss capitalisation.

#### Lower SCR gives lower stability (analytical proof)
**Short circuit ratio (SCR)** is the ratio of field current needed to produce rated open-circuit voltage to the field current needed to circulate rated armature current on a sustained three-phase short circuit:
$$
SCR = \frac{I_f\ (\text{rated OC voltage})}{I_f\ (\text{rated SC current})} \approx \frac{1}{X_d\,(\text{p.u., saturated})}
$$
Typical values: salient-pole hydro generators 1.0–1.5; cylindrical-rotor turbo generators 0.5–0.7.

#### Analytical relation with stability
Power delivered by a generator (neglecting resistance and saliency) to an infinite bus:
$$
P = \frac{E V}{X_d}\sin\delta = E\,V\,(SCR)\sin\delta
$$
- **Maximum (steady-state limit) power:** $P_{max} = \dfrac{EV}{X_d} = E\,V\,(SCR)$. Lower SCR → lower $P_{max}$.
- **Load angle for given load:** $\sin\delta = \dfrac{P}{E\,V\,(SCR)}$. Lower SCR → larger $\delta$, closer to the 90° limit.
- **Synchronizing power coefficient:** $P_s = \dfrac{dP}{d\delta} = E\,V\,(SCR)\cos\delta$. Lower SCR → smaller restoring torque after a disturbance.

**Numerical illustration** ($E = 1.8$ p.u. kept the same, $V = 1$ p.u., $P = 0.85$ p.u.):

| SCR | $X_d$ (p.u.) | $P_{max}$ (p.u.) | $\delta$ | $P_s$ (p.u./rad) | Margin $(P_{max}-P)/P_{max}$ |
|---|---|---|---|---|---|
| 1.2 | 0.833 | 2.16 | 23.17° | 1.986 | 60.6% |
| 1.0 | 1.000 | 1.80 | 28.18° | 1.587 | 52.8% |
| 0.6 | 1.667 | 1.08 | 51.91° | 0.666 | 21.3% |

So the **lower the SCR, the lower the stability margin** (higher $\delta$, smaller $P_{max}$ and $P_s$).

Physically, a low SCR means a high synchronous reactance, i.e. weak magnetic coupling between rotor and stator through a small air gap; the generator must swing to a larger angle to transmit the same power, leaving less margin before it slips a pole.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. How is the short circuit ratio related to the synchronous reactance?
   A. SCR is approximately Xd (p.u.)
   B. SCR is approximately 1/Xd (p.u., saturated)
   C. SCR is independent of Xd
   D. SCR is approximately Xd^2
   Answer: B. SCR is the field current for rated open-circuit voltage divided by that for rated short-circuit current, which is about 1/Xd in p.u. (Key point: SCR and Xd)

2. Why does a lower SCR reduce the steady-state stability limit?
   A. Pmax = E V / SCR, so it rises
   B. Pmax = E V (SCR), so Pmax falls in proportion to SCR
   C. Pmax is unaffected, only the voltage changes
   D. Pmax depends only on the turbine
   Answer: B. Since P = (EV/Xd) sin(delta) = E V (SCR) sin(delta), the maximum power is directly proportional to SCR. (Key point: Maximum power)

3. For the same load P, what happens to the load angle when SCR is reduced?
   A. Delta becomes negative
   B. Delta increases, nearer the 90° limit
   C. Delta stays the same
   D. Delta decreases
   Answer: B. sin(delta) = P/(E V SCR), so a lower SCR needs a larger delta for the same power, leaving less margin. (Key point: Load angle)

4. What does the synchronizing power coefficient Ps = E V (SCR) cos(delta) show at lower SCR?
   A. Higher speed of the rotor
   B. No change in restoring torque
   C. Smaller restoring torque after a disturbance
   D. Larger restoring torque after a disturbance
   Answer: C. Lower SCR and larger delta both reduce Ps, so the machine is less able to return to synchronism after a disturbance. (Key point: Synchronizing power)

## Related in Power Plant Design

- [Generator choice and significance of SCR](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Agenerator-choice-scr-significance) — Power Plant Design, chapter 4
- [Short circuit ratio and system stability](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Ascr-significance-stability) — Power Plant Design, chapter 4, asked 3×
- [Consequences of higher or lower SCR](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Ascr-higher-lower-consequences) — Power Plant Design, chapter 4, asked 3×
- [Factors in choosing a generator](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Agenerator-selection-factors) — Power Plant Design, chapter 4, asked 3×
- [Choice of generator circuit breaker](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Agenerator-circuit-breaker-choice) — Power Plant Design, chapter 4, asked 2×
- [Design: 260 m head plant, generator lead](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Adesign-2078-260m-generator-lead) — Power Plant Design, chapter 4, asked 5×

## Related in other subjects

- [Factors in power and lighting system design](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Apower-lighting-design-factors) — Industrial Power Distribution and Illumination, chapter 5
- [Per unit circuit of three-generator system, 30 MVA base](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Apu-circuit-30mva-g1-g2-g3) — Power System Analysis I, chapter 3
- [Power vs lighting system and cable sizing factors](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Apower-vs-lighting-cable-factors) — Industrial Power Distribution and Illumination, chapter 5
- [T/F: earth wire choice depends on circuit and voltage](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atf-earth-wire-choice-circuit-voltage) — Transmission and Distribution System Design, chapter 3