title: "Factors in choosing a generator"
subject: "Power Plant Design"
chapter: 4
key: "semester_8/power_plant_design:generator-selection-factors"
source: https://www.bctengineer.com/q/semester_8/power_plant_design/generator-selection-factors
site: BCT Engineering
---

# Factors in choosing a generator

Power Plant Design · Chapter 4: Electric System Design of a Power Plant

- Asked in: 2082 Shrawan, 6 marks; 2074 Bhadra, 6 marks; 2073 Magh, 5 marks (asked 3 times)
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_8/power_plant_design/generator-selection-factors
- Whole chapter: https://www.bctengineer.com/md/semester_8/power_plant_design/chapter-4

## Question

Discuss the various factors which should be considered for the choice of generator during the design of a power plant.

## Short answer

Generator selection factors: MVA rating from turbine output and power factor (0.85–0.9), voltage (6.6–11 kV), speed/poles (N=120f/p), shaft arrangement, reactances and SCR, inertia constant, efficiency above 97%, insulation class F/B, air cooling, excitation (brushless or static), high-resistance neutral grounding, grid requirements, transport limits, and cost.

## Answer

The generator must match the turbine, the grid and the site. The main factors are:

1. **Rating (MVA) and power factor:** $S = P_{turbine}\,\eta_g / \cos\phi$; power factor usually 0.85–0.9 lagging so the unit can supply reactive power. Some overload margin (e.g. 10%) is often specified.
2. **Rated voltage:** usually 6.6 kV or 11 kV for hydro units (higher, e.g. 13.8–15.75 kV, for very large units); chosen with GSU and bus/cable cost.
3. **Speed and number of poles:** fixed by the turbine: $N = 120f/p$. Hydro units are slow, salient-pole machines with many poles.
4. **Shaft arrangement:** vertical (large Francis/Kaplan) or horizontal (small Pelton/Francis).
5. **Reactances and SCR:** $X''_d$ sets fault level and breaker rating; SCR and $X_d$ set stability and voltage regulation.
6. **Inertia constant (GD²):** larger inertia limits speed rise on load rejection and improves stability, but costs more.
7. **Efficiency and losses:** high efficiency (above 97–98%) saves energy over the plant life.
8. **Insulation and temperature rise:** class F insulation with class B temperature rise is common; altitude derating above 1000 m.
9. **Cooling:** air-cooled (open or closed with air–water coolers) for hydro.
10. **Excitation system:** brushless for small/medium units, static for large units.
11. **Neutral grounding:** high-resistance grounding via NGT.
12. **Grid requirements:** capability curve, reactive power range, fault ride-through, harmonics.
13. **Transport and erection limits:** weight and size on hill roads; split stator if needed.
14. **Standards and cost:** IEC 60034; capital cost versus loss capitalisation.

#### Example
For a 10 MW turbine output, $\eta_g = 0.97$, pf 0.85: generator rating $= 10 \times 0.97/0.85 \approx 11.4$ MVA, 11 kV, 50 Hz; if the turbine speed is 600 rpm, poles $= 120 \times 50/600 = 10$.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. The generator speed and number of poles are:
   A. Chosen freely irrespective of turbine
   B. Set by the transformer
   C. Set by the cable size
   D. Fixed by the turbine speed using N = 120f/p
   Answer: D. The generator is coupled to the turbine, so poles p = 120f/N. (Key point: Speed and poles)

2. Generator MVA rating is found from:
   A. S = P_turbine x efficiency / power factor
   B. S = P_turbine x power factor
   C. S = P_turbine / efficiency x pf
   D. S = V x f
   Answer: A. S = P_turbine * eta_g / cos(phi); e.g. 10 MW, 0.97, 0.85 gives about 11.4 MVA. (Key point: Rating)

3. What do X''d and inertia (GD^2) influence?
   A. Only the paint colour
   B. X''d sets fault level and breaker rating; larger inertia limits speed rise on load rejection and improves stability
   C. X''d sets cooling; inertia sets voltage
   D. Nothing important
   Answer: B. Sub-transient reactance determines fault current; inertia helps stability but costs more. (Key point: Reactance and inertia)

4. Which excitation is usually chosen?
   A. Static for small units, brushless for large
   B. Static for all
   C. Brushless for small/medium units, static for large units
   D. Brushless for all
   Answer: C. Brushless is suited to small/medium units; static to large units needing fast response. (Key point: Excitation choice)

## Related in Power Plant Design

- [Generator choice and SCR versus stability](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Agenerator-choice-scr-stability) — Power Plant Design, chapter 4
- [Generator choice and significance of SCR](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Agenerator-choice-scr-significance) — Power Plant Design, chapter 4
- [Design: 260 m head plant, generator lead](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Adesign-2078-260m-generator-lead) — Power Plant Design, chapter 4, asked 5×
- [Design: 245 m head plant, standby generator](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Adesign-2073-245m-standby) — Power Plant Design, chapter 4, asked 14×
- [Choice of generator circuit breaker](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Agenerator-circuit-breaker-choice) — Power Plant Design, chapter 4, asked 2×
- [Design: 360 m head plant, 132 kV](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Adesign-2078-360m-132kv) — Power Plant Design, chapter 4, asked 5×

## Related in other subjects

- [Factors for choosing stations; offset types](https://www.bctengineer.com/question.md?key=semester_3%2Fsurveying_i%3Afactors-stations-and-offset-types) — Surveying I, chapter 3
- [Factors in power and lighting system design](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Apower-lighting-design-factors) — Industrial Power Distribution and Illumination, chapter 5
- [Firm power and plant load factors](https://www.bctengineer.com/question.md?key=semester_6%2Fhydro_power%3Afirm-power-load-factors) — Hydro Power, chapter 3
- [Factors affecting choice of BIL](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Abil-choice-factors) — Transmission and Distribution System Design, chapter 3