# Protection of a medium size generator

Power Plant Design · Chapter 4: Electric System Design of a Power Plant

- Asked in: 2082 Shrawan, 6 marks; 2079 Chaitra, 4 marks; 2077 Chaitra, 4 marks (asked 3 times)
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_8/power_plant_design/medium-generator-protection
- Whole chapter: https://www.bctengineer.com/md/semester_8/power_plant_design/chapter-4

## Question

List out the necessary protection schemes to be employed for a medium size generator in a power plant.

## Short answer

Core electrical protections: differential (87G), stator earth fault (64G), rotor earth fault (64R), loss of excitation (40), negative sequence (46), reverse power (32), voltage-restrained overcurrent (51V) or impedance (21), thermal overload (49), over/under voltage/frequency, overfluxing (24), out-of-step (78). Mechanical: overspeed, bearing/vibration.

## Answer

A medium size generator (roughly 5–100 MVA) is protected against internal faults, abnormal operating conditions and system disturbances. Typical schemes, with ANSI device numbers:

| ANSI | Protection | Purpose |
|---|---|---|
| 87G | Generator differential | Fast clearing of stator phase-to-phase faults |
| 87GT / 87T | Overall gen-transformer / transformer differential | Faults in GSU and connections |
| 64G (59N + 27TN) | Stator earth fault (95% neutral overvoltage + 100% third harmonic) | Earth faults in stator winding (high-resistance grounded via NGT) |
| 64R | Rotor (field) earth fault | First earth fault in field winding |
| 40 | Loss of excitation (field failure) | Prevents running as induction generator and drawing VArs |
| 46 | Negative phase sequence | Unbalanced loads/open phase; rotor heating |
| 32 | Reverse power | Motoring when turbine power is lost |
| 51V / 21 | Voltage-restrained overcurrent / impedance | Backup for external faults |
| 49 | Stator thermal overload (RTDs) | Overheating |
| 59 / 27 | Over/under voltage | Load rejection, AVR failure |
| 81O / 81U | Over/under frequency | Speed and grid frequency deviations |
| 24 | Overfluxing (V/Hz) | Protects generator and GSU core |
| 78 | Pole slipping (out of step) | Loss of synchronism |
| 50/27 | Inadvertent energisation | Breaker closed at standstill |
| 50BF | Breaker failure | Backup tripping of adjacent breakers |

#### Mechanical/hydraulic protections
Overspeed, bearing and oil temperature, vibration, cooling water failure, low oil pressure, shear pin failure.

#### Tripping logic
Faults like 87G, 64G, 64R (second stage) trip the GCB, field breaker and turbine (emergency shutdown); abnormal conditions like 46, 49 or 81 first alarm, then trip after a time delay.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Which protection clears stator phase-to-phase faults quickly?
   A. 32 Reverse power
   B. 87G Generator differential
   C. 46 Negative sequence
   D. 81 Frequency
   Answer: B. 87G compares currents at both ends of the stator winding. (Key point: Stator phase faults)

2. Device 40 (loss of excitation) protects against:
   A. Motoring by lost turbine power
   B. Unbalanced loads
   C. Running as an induction generator and drawing VArs
   D. Stator overheating
   Answer: C. Without field the machine absorbs reactive power from the grid. (Key point: Loss of excitation)

3. Negative phase sequence protection (46) guards against:
   A. Rotor heating from unbalanced loads or open phase
   B. Overfluxing
   C. Breaker failure
   D. Reverse power
   Answer: A. Negative sequence current induces double-frequency currents that heat the rotor. (Key point: Negative sequence)

4. How are faults and abnormal conditions treated?
   A. All only alarm
   B. Faults like 87G/64G trip the GCB, field breaker and turbine; abnormal conditions alarm then trip after delay
   C. All trip instantly
   D. Abnormal conditions trip, faults alarm
   Answer: B. Internal faults need immediate tripping; abnormal conditions are alarmed first, then tripped with a time delay. (Key point: Tripping logic)

## Related in Power Plant Design

- [Sketch of a medium head PROR plant](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Apror-medium-head-sketch) — Power Plant Design, chapter 3, asked 2×
- [Components of a medium head high discharge plant](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Amedium-head-high-discharge-components) — Power Plant Design, chapter 3, asked 2×
- [Protection for alternator and step-up transformer](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Amega-project-protection) — Power Plant Design, chapter 4
- [Unit generator-transformer schemes](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Aunit-generator-transformer-schemes) — Power Plant Design, chapter 4, asked 3×
- [Design: 245 m head plant, standby generator](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Adesign-2073-245m-standby) — Power Plant Design, chapter 4, asked 14×
- [Design: 260 m head plant, generator lead](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Adesign-2078-260m-generator-lead) — Power Plant Design, chapter 4, asked 5×

## Related in other subjects

- [Differential protection: 11 kV, 100 MVA generator](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Agenerator-differential-11kv-6-ohm) — Switchgear and Protection, chapter 7
- [Lightning protection schemes](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Alightning-protection-schemes) — Switchgear and Protection, chapter 5
- [Skin depth and power in dissipative medium](https://www.bctengineer.com/question.md?key=semester_3%2Felectromagnetism%3Askin-depth-time-average-power-density) — Electromagnetism, chapter 4
- [Combined phase and earth fault protection of generator](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Acombined-phase-earth-fault-generator) — Switchgear and Protection, chapter 7