# Protection for alternator and step-up transformer

Power Plant Design · Chapter 4: Electric System Design of a Power Plant

- Asked in: 2080 Chaitra, 6 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_8/power_plant_design/mega-project-protection
- Whole chapter: https://www.bctengineer.com/md/semester_8/power_plant_design/chapter-4

## Question

List out the most essential protection schemes required for Alternator and Generator Step Up transformer in a mega size power project.

## Short answer

Essential alternator protections: differential (87G), stator earth fault 95% and 100% (59N/64G, 27TN/64S), rotor earth fault (64R), loss of excitation (40), negative sequence (46). Essential GSU protections: transformer differential (87T), restricted earth fault (64REF), Buchholz (63), overfluxing (24). Overall unit differential (87GT) and master trip (86) cover both.

## Answer

In a mega (large) hydro or thermal project, the alternator and its **generator step-up (GSU) transformer** are protected by a set of main and backup relays, usually grouped as a **unit protection** scheme with an overall differential zone.

#### Generator protections (ANSI number)

| Protection | ANSI | Purpose |
|---|---|---|
| Generator differential | 87G | Stator phase-to-phase faults |
| Stator earth fault 95 % | 59N / 64G | Earth faults on 95 % of winding |
| 100 % stator earth fault | 27TN / 64S | Faults near neutral (3rd harmonic or injection) |
| Rotor earth fault | 64R / 64F | Field winding earth fault |
| Loss of excitation | 40 | Field failure, under-excitation |
| Negative sequence | 46 | Unbalanced load, rotor heating |
| Reverse power | 32 | Motoring of the unit |
| Over/under frequency | 81 | Abnormal speed |
| Over/under voltage | 59 / 27 | Load rejection, AVR failure |
| Overfluxing (V/Hz) | 24 | Core over-excitation |
| Voltage-restrained overcurrent / impedance | 51V / 21 | Backup for external faults |
| Pole slipping | 78 | Loss of synchronism |
| Stator thermal / RTD | 49 | Overload, cooling failure |
| Inadvertent energisation | 50/27 | Breaker closed on a stopped unit |

#### GSU transformer protections

| Protection | ANSI | Purpose |
|---|---|---|
| Transformer differential | 87T | Internal phase faults |
| Restricted earth fault (HV) | 64REF / 87N | Earth faults near HV neutral |
| Buchholz relay | 63 | Incipient internal faults, gas |
| Oil and winding temperature | 26 / 49 | Overheating |
| Pressure relief device | 63PR | Sudden internal pressure |
| HV overcurrent and earth fault | 50/51, 50N/51N | Backup |
| Overfluxing | 24 | Over-excitation of core |
| Oil level, cooling failure | 71 | Alarm |

#### Overall scheme

An **overall (unit) differential 87GT** covers the generator, GSU and unit auxiliary transformer together. Relays are duplicated as **Main-1 and Main-2** groups with separate CTs and DC supplies for very large units. Trips go through a **master trip relay (86)** to the GCB, HV breaker, field breaker and turbine shutdown.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Which protection detects stator phase-to-phase faults of the alternator?
   A. Reverse power (32)
   B. Generator differential (87G)
   C. Loss of excitation (40)
   D. Negative sequence (46)
   Answer: B. 87G compares currents at both ends of the stator winding and trips for internal phase faults. (Key point: Generator differential)

2. Why is a 100% stator earth fault scheme (27TN/64S) added to the 95% scheme?
   A. To detect faults near the neutral end that the 95% scheme misses
   B. To detect rotor earth faults
   C. To detect overfluxing
   D. To protect against motoring
   Answer: A. The 95% scheme leaves the last part of the winding near the neutral uncovered, so 3rd harmonic or injection schemes cover it. (Key point: 100% stator earth fault)

3. What does negative sequence protection (46) guard against?
   A. Motoring of the unit
   B. Unbalanced load causing rotor heating
   C. Core over-excitation
   D. Field winding earth fault
   Answer: B. Unbalanced currents produce negative sequence currents that induce double-frequency currents and overheat the rotor. (Key point: Negative sequence protection)

4. What does the overall differential 87GT cover, and how are trips issued?
   A. Only the GSU; trip directly from each relay
   B. Generator, GSU and unit auxiliary transformer together; trips via master trip relay 86
   C. Only the busbar; trip via Buchholz
   D. Only the generator; trip via 51V
   Answer: B. 87GT forms one zone over the unit, and tripping goes through the master trip relay (86) to the GCB, HV breaker, field breaker and turbine shutdown. (Key point: Overall unit differential)

## Related in Power Plant Design

- [Protection of a medium size generator](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Amedium-generator-protection) — Power Plant Design, chapter 4, asked 3×
- [Unit generator-transformer schemes](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Aunit-generator-transformer-schemes) — Power Plant Design, chapter 4, asked 3×
- [Transformer protection, selection and vector group](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Atransformer-protection-vector-group) — Power Plant Design, chapter 4
- [Quotation for a power transformer](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Apower-transformer-quotation) — Power Plant Design, chapter 4
- [Limits of the alternator capability curve](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Acapability-curve-limits) — Power Plant Design, chapter 4
- [Specification for procuring a power transformer](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Apower-transformer-specification) — Power Plant Design, chapter 4, asked 4×

## Related in other subjects

- [Step-up chopper and controllable power transfer](https://www.bctengineer.com/question.md?key=semester_7%2Fpower_electronics%3Astep-up-chopper-power-transfer) — Power Electronics, chapter 4
- [Differential protection of power transformer](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Atransformer-differential-protection) — Switchgear and Protection, chapter 7
- [Earth fault protection: 20 MVA alternator](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aearth-fault-20mva-5-ohm) — Switchgear and Protection, chapter 7
- [Percentage differential protection of alternator](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Aalternator-percentage-differential) — Switchgear and Protection, chapter 7, asked 2×