title: "Electrical characteristics of a unit transformer"
subject: "Power Plant Design"
chapter: 4
key: "semester_8/power_plant_design:unit-transformer-characteristics"
source: https://www.bctengineer.com/q/semester_8/power_plant_design/unit-transformer-characteristics
site: BCT Engineering
---

# Electrical characteristics of a unit transformer

Power Plant Design · Chapter 4: Electric System Design of a Power Plant

- Asked in: 2074 Magh, 5 marks; 2071 Magh, 6 marks (asked 2 times)
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_8/power_plant_design/unit-transformer-characteristics
- Whole chapter: https://www.bctengineer.com/md/semester_8/power_plant_design/chapter-4

## Question

Discuss electrical characteristics of unit transformer that to be considered during its selection.

## Short answer

Rated MVA ≥ generator rating; LV voltage = generator voltage, HV = grid voltage; vector group YNd11 to block zero-sequence; impedance 8–14% for fault/stability; HV taps for voltage control; low losses capitalised; insulation and temperature rise per IEC 60076; cooling ONAN/ONAF or OFWF; overfluxing capability; short-circuit withstand for 2 s.

## Answer

The **unit transformer** (generator step-up transformer of a unit) connects a generator to the HV system. Its electrical characteristics must suit both the generator and the grid.

#### Electrical characteristics considered
1. **Rated MVA:** at least the generator rated MVA (e.g. 15 MVA for a 12.75 MW, 0.85 pf unit); some margin for overload and the unit auxiliary load.
2. **Voltage ratio:** LV equal to generator voltage (e.g. 11 kV); HV equal to grid voltage plus margin for line drop (e.g. 132 kV).
3. **Vector group:** **YNd11** is common: delta on generator side blocks zero-sequence and third harmonics; star-earthed HV gives an earthed system.
4. **Percentage impedance:** about 8–14%. Higher impedance reduces fault level and breaker rating; lower impedance improves voltage regulation and stability. Fixed by fault-level and stability studies.
5. **Tappings:** off-circuit taps (e.g. ±2 × 2.5%) or OLTC on HV, to match grid voltage and control VAr flow.
6. **Losses and efficiency:** no-load (iron) and load (copper) losses are capitalised; low losses save energy for 30+ years.
7. **Insulation level (BIL) and temperature rise:** HV BIL as per insulation coordination; temperature rise per IEC 60076 (oil 60 K, winding 65 K); altitude correction above 1000 m.
8. **Cooling:** ONAN/ONAF for outdoor; OFWF in underground powerhouses.
9. **Overfluxing capability:** must withstand V/Hz rise on load rejection (e.g. 1.1 p.u. continuous, 1.4 p.u. for a few seconds).
10. **Short-circuit withstand:** thermal and dynamic for 2 s per IEC 60076-5.
11. **Magnetising inrush and noise level.**
12. **Standards:** IEC 60076.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Why is YNd11 common for a unit transformer?
   A. Delta on generator side blocks zero-sequence and third harmonics; earthed star HV gives an earthed system
   B. It reduces MVA
   C. It removes the need for tap changer
   D. It increases fault level
   Answer: A. The delta LV and earthed star HV combination suits generator step-up duty. (Key point: Vector group)

2. A higher percentage impedance of the transformer:
   A. Raises fault level
   B. Improves voltage regulation
   C. Reduces fault level and breaker rating but worsens voltage regulation and stability
   D. Has no effect
   Answer: C. Impedance trades fault level against regulation and stability, set by studies. (Key point: Percentage impedance)

3. The transformer rated MVA should be:
   A. Half the generator MVA
   B. Equal to the grid fault level
   C. Independent of generator
   D. At least the generator rated MVA with margin for overload and auxiliary load
   Answer: D. The transformer must carry the full generator output. (Key point: Rated MVA)

## Related in Power Plant Design

- [Transformer protection, selection and vector group](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Atransformer-protection-vector-group) — Power Plant Design, chapter 4
- [Unit generator-transformer schemes](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Aunit-generator-transformer-schemes) — Power Plant Design, chapter 4, asked 3×
- [Hydropower site selection factors](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Asite-selection-discharge-factors) — Power Plant Design, chapter 3
- [Criteria for turbine selection](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Aturbine-selection-criteria) — Power Plant Design, chapter 3, asked 3×
- [Turbine selection method and governing factors](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Aturbine-selection-method-factors) — Power Plant Design, chapter 3, asked 3×
- [Design: 550 m head plant, transformer quotation](https://www.bctengineer.com/question.md?key=semester_8%2Fpower_plant_design%3Adesign-2077-550m-quotation) — Power Plant Design, chapter 4, asked 3×

## Related in other subjects

- [Motor selection characteristics; rheostatic and regenerative braking](https://www.bctengineer.com/question.md?key=semester_7%2Futilization_of_electrical_energy%3Amotor-selection-characteristics-braking) — Utilization of Electrical Energy, chapter 2
- [Pump characteristics, losses and selection](https://www.bctengineer.com/question.md?key=semester_5%2Ffluid_machines%3Apump-characteristics-losses-selection) — Fluid Machines, chapter 4
- [Fuse selection for 250 kVA transformer](https://www.bctengineer.com/question.md?key=semester_6%2Fswitchgear_and_protection%3Atransformer-fuse-selection-250kva) — Switchgear and Protection, chapter 3
- [Transformer selection for apartment, residence, industry](https://www.bctengineer.com/question.md?key=semester_6%2Findustrial_power_distribution_and_illumination%3Atransformer-selection-apartment-industry) — Industrial Power Distribution and Illumination, chapter 4