# T/F: HVDC converter reactive power need

Transmission and Distribution System Design · Chapter 1: Introduction

- Asked in: 2072 Magh, 3 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_8/transmission_and_distribution_system_design/tf-hvdc-reactive-power
- Whole chapter: https://www.bctengineer.com/md/semester_8/transmission_and_distribution_system_design/chapter-1

## Question

State whether the following statement is TRUE or FALSE. Justify your answer with a brief explanation: HVDC converter station requires huge amount of reactive power support.

## Short answer

True. Line-commutated converters draw lagging current due to firing and commutation angles, consuming reactive power up to 50–60% of real power. Converter stations need large shunt capacitor banks, filters, or SVCs to supply this support.

## Answer

**TRUE.**

- Line-commutated (thyristor) converters always draw current that lags the voltage, both as rectifier (firing angle $\alpha$) and as inverter (extinction angle $\gamma$), plus extra lag due to commutation overlap $\mu$.
- The reactive power consumed is roughly $Q \approx P\tan\phi$ with $\cos\phi \approx \frac{1}{2}[\cos\alpha + \cos(\alpha+\mu)]$; in practice $Q$ is **50–60% of the transmitted real power** at each end.
- This reactive power is supplied by AC filters (which also remove harmonics), shunt capacitor banks, synchronous condensers or SVC/STATCOM at the converter station.

So a 1000 MW HVDC terminal needs about 500–600 MVAr of local reactive support. (Voltage-source converter HVDC does not have this need, but the statement refers to conventional HVDC.)

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. For conventional HVDC the statement 'converter station requires huge reactive power' is:
   A. False
   B. True
   C. True only for inverter
   D. True only for VSC
   Answer: B. Line-commutated converters always draw lagging current and consume large reactive power. (Key point: Verdict)

2. Reactive demand of a conventional converter is about what fraction of transmitted real power?
   A. 5-10%
   B. 50-60%
   C. 150%
   D. Zero
   Answer: B. Q is roughly 50-60% of P at each end, e.g. 500-600 MVAr for 1000 MW. (Key point: Magnitude)

3. How is the converter's reactive demand supplied?
   A. By the DC line
   B. AC filters, shunt capacitors, synchronous condensers or SVC/STATCOM
   C. By series reactors
   D. By the thyristors themselves
   Answer: B. Local reactive support is provided at the converter station; filters also remove harmonics. (Key point: Sources of Q)

## Related in Transmission and Distribution System Design

- [T/F: HVDC better for longer lines](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atf-hvdc-longer-length) — Transmission and Distribution System Design, chapter 1
- [T/F: % power loss equals % energy loss](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atf-power-loss-energy-loss-same) — Transmission and Distribution System Design, chapter 6
- [T/F: LLF unity for constant power loss](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atf-llf-unity-constant-loss) — Transmission and Distribution System Design, chapter 6
- [T/F: sag absent with supports at different heights](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atf-sag-absent-different-heights) — Transmission and Distribution System Design, chapter 4
- [T/F: higher voltage more economical](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atf-higher-voltage-more-economical) — Transmission and Distribution System Design, chapter 2
- [T/F: capability curve inversely proportional to length](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atf-capability-curve-inverse-length) — Transmission and Distribution System Design, chapter 2

## Related in other subjects

- [True/false: derivative controllers always used with others](https://www.bctengineer.com/question.md?key=semester_3%2Fcontrol_systems%3Aderivative-always-with-others) — Control Systems, chapter 7, asked 3×
- [True/false: CT secondary kept open](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atf-false-ct-secondary-open) — Electrical Machine, chapter 2
- [True/false: series motor started at no load](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atf-dc-series-motor-start-noload) — Electrical Machine, chapter 4
- [True/false: rotor core loss neglected](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atf-rotor-core-loss-neglected) — Electrical Machine, chapter 5