# T/F: peak demand as sum of class peaks

Transmission and Distribution System Design · Chapter 6: Electrical Load Characteristics and Load Forecast

- Asked in: 2075 Bhadra, 1+3 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_8/transmission_and_distribution_system_design/tf-peak-demand-sum-classes
- Whole chapter: https://www.bctengineer.com/md/semester_8/transmission_and_distribution_system_design/chapter-6

## Question

State whether the following statement is TRUE or FALSE. Justify your answer with a brief explanation: The peak demand of a load centre is the sum of the peak demand of different consumer classes.

## Short answer

FALSE. Different classes peak at different times; the coincident peak is the sum of class peaks multiplied by their contribution factors (≤1), which is less than the arithmetic sum.

## Answer

**FALSE.**

The peak demand of a load centre is the **coincident** (simultaneous) maximum of the combined load, not the arithmetic sum of the class peaks.

**Justification:**

- Different consumer classes reach their maximum demand at different hours. Domestic load peaks in the evening (lighting, cooking), commercial load around midday/afternoon, and offices, schools and institutions during working hours.
- At the hour of the load centre peak, each class draws only a fraction of its own peak. This fraction is the **contribution (responsibility) factor** $c_i$.
- Therefore

$$
P_{LC} = \sum c_i \, P_{class,i} \le \sum P_{class,i}
$$

**Example:** domestic peak 20 kW (evening, $c = 1$), commercial peak 6 kW ($c = 0.5$ in the evening), institutional peak 4 kW ($c = 0.1$):

$$
P_{LC} = 20 + 3 + 0.4 = 23.4 \text{ kW, not } 30 \text{ kW}
$$

Adding the class peaks directly would oversize the distribution transformer and feeders, raising capital cost and no-load losses. The plain sum is correct only if all classes peak at the same time (all contribution factors equal to 1), which rarely happens.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. 'Peak demand of a load centre is the sum of peak demands of the classes' is:
   A. True, always
   B. False, because the classes peak at different times
   C. True, if power factor is 1
   D. False, because the sum is smaller than the true peak
   Answer: B. The load-centre peak is the coincident maximum, not the plain sum of class peaks. (Key point: Verdict)

2. The correct expression for load-centre peak is:
   A. Sum of P_class
   B. Sum of c_i x P_class,i, with c_i the contribution factor
   C. Max of P_class divided by c_i
   D. Average of P_class
   Answer: B. Each class draws only a fraction c_i of its peak at the system peak. (Key point: Formula)

3. Domestic 20 kW (c = 1), commercial 6 kW (c = 0.5), institutional 4 kW (c = 0.1). The load-centre peak is:
   A. 30 kW
   B. 23.4 kW
   C. 26.5 kW
   D. 20 kW
   Answer: B. 20 + 3 + 0.4 = 23.4 kW. (Key point: Example)

## Related in Transmission and Distribution System Design

- [5th year peak load from consumer survey](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Afifth-year-peak-load-survey) — Transmission and Distribution System Design, chapter 6, asked 7×
- [Peak demand of load center from load pattern](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Apeak-demand-load-center-load-pattern) — Transmission and Distribution System Design, chapter 6, asked 2×
- [T/F: feeder average consumption near peak](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atf-average-consumption-near-peak) — Transmission and Distribution System Design, chapter 6
- [5th year peak load with population growth](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Afifth-year-peak-load-population-growth) — Transmission and Distribution System Design, chapter 6, asked 7×
- [5th year peak load, incremental growth rate](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Afifth-year-peak-load-incremental-growth) — Transmission and Distribution System Design, chapter 6, asked 7×
- [5th year peak load (commercial 30 days)](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Afifth-year-peak-load-30-days) — Transmission and Distribution System Design, chapter 6, asked 7×

## Related in other subjects

- [True/false: series motor started at no load](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machine%3Atf-dc-series-motor-start-noload) — Electrical Machine, chapter 4
- [DC series motor started at no load: true/false](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Adc-series-no-load-true-false) — Electrical Machines, chapter 4
- [True/false: load rejection raises terminal voltage](https://www.bctengineer.com/question.md?key=semester_8%2Fhigh_voltage_engineering%3Atf-load-rejection-voltage-rise) — High Voltage Engineering, chapter 3
- [True/false: derivative controllers always used with others](https://www.bctengineer.com/question.md?key=semester_3%2Fcontrol_systems%3Aderivative-always-with-others) — Control Systems, chapter 7, asked 3×