title: "T/F: conductor configuration for 400 kV lines"
subject: "Transmission and Distribution System Design"
chapter: 4
key: "semester_8/transmission_and_distribution_system_design:tf-vertical-configuration-400kv"
source: https://www.bctengineer.com/q/semester_8/transmission_and_distribution_system_design/tf-vertical-configuration-400kv
site: BCT Engineering
---

# T/F: conductor configuration for 400 kV lines

Transmission and Distribution System Design · Chapter 4: Conductor and Support Selection

- Asked in: 2078 Chaitra, 1+3 marks; 2073 Bhadra, 4 marks (asked 2 times)
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_8/transmission_and_distribution_system_design/tf-vertical-configuration-400kv
- Whole chapter: https://www.bctengineer.com/md/semester_8/transmission_and_distribution_system_design/chapter-4

## Question

State and justify whether the following statement is TRUE or FALSE: Vertical configuration is generally adopted for transmission line of above 400 kV.

## Short answer

FALSE. For single-circuit lines above 400 kV, horizontal configuration is generally adopted because it gives lower tower height, better shielding with two earth wires, reduced overturning moment, and avoids phase-to-phase contact during ice shedding. Vertical configuration is typical for double-circuit lines up to 220 kV.

## Answer

**FALSE.**

For lines of 400 kV and above, the **horizontal configuration** is generally adopted for single-circuit lines. The vertical configuration is used for double-circuit lines up to 220 kV, and occasionally for 400 kV double circuits.

Reasons for the horizontal configuration at EHV:
1. **Lower tower height:** all phases are on one level. A vertical arrangement would stack three large phase spacings (8–12 m each) plus long strings, making the tower very tall and heavy.
2. **Smaller overturning moment:** the conductors are lower, so the moment from wind is less and the foundations are cheaper.
3. **Lightning performance:** low conductors and two earth wires give better shielding and fewer strikes.
4. **Galloping and ice shedding:** with no conductor directly above another, a conductor jumping after ice shedding cannot clash with the phase above.
5. **Maintenance:** the lower height makes stringing and live-line work easier.

The disadvantage is a wider right-of-way. Where land is costly, a vertical or delta double-circuit tower is chosen instead.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Vertical configuration is generally adopted for lines above 400 kV. This is:
   A. True, to save right-of-way
   B. True, because it gives better lightning shielding
   C. False, horizontal configuration is generally used for single circuit EHV lines
   D. False, delta is always used
   Answer: C. Horizontal configuration is generally used at 400 kV and above. (Key point: Verdict)

2. Why does a vertical arrangement suit EHV badly?
   A. It makes the phase spacing smaller
   B. Three large phase spacings (8-12 m each) are stacked, making the tower very tall and heavy
   C. It increases the corona
   D. It requires no earth wire
   Answer: B. Large EHV spacings stacked vertically give a very tall, heavy tower. (Key point: Tower height)

3. What is the main disadvantage of the horizontal configuration?
   A. Higher overturning moment
   B. More lightning strikes
   C. Wider right-of-way
   D. Conductor clashing after ice shedding
   Answer: C. A horizontal layout needs more width, hence a wider right-of-way. (Key point: Disadvantage of horizontal)

## Related in Transmission and Distribution System Design

- [400 kV lines: configuration, V-string, earth wires](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Ajustify-400kv-config-vstring-earthwire) — Transmission and Distribution System Design, chapter 4
- [T/F: V-type string for 400 kV lines](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atf-v-string-400kv-mechanical) — Transmission and Distribution System Design, chapter 3
- [T/F: double earth wire for 400 kV single circuit](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atf-400kv-single-circuit-double-earth) — Transmission and Distribution System Design, chapter 3
- [Conductor selection, 220 kV line for 200 MW](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Aconductor-selection-220kv-200mw-120km) — Transmission and Distribution System Design, chapter 4
- [T/F: X/R ratio, transmission vs distribution](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atf-xr-ratio-transmission-distribution) — Transmission and Distribution System Design, chapter 1
- [Conductor selection, 100 MW 70 km 132 kV](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Aconductor-selection-100mw-70km-132kv) — Transmission and Distribution System Design, chapter 4

## Related in other subjects

- [400 kV line with 3-conductor bundles: reactances and VAR](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Atriple-bundle-400kv-reactances) — Power System Analysis I, chapter 4, asked 3×
- [True/False: ampere conductors and temperature rise](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Atf-ampere-conductor-temperature) — Electric Machine Design, chapter 5
- [True/False: armature reaction and ampere conductors](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Atf-armature-reaction-ampere-conductor) — Electric Machine Design, chapter 5
- [Significance of transmission voltage level, 132 vs 400 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Avoltage-level-132kv-vs-400kv) — Power System Analysis I, chapter 1