# Tower cost factors and bending moment at angle

Transmission and Distribution System Design · Chapter 4: Conductor and Support Selection

- Asked in: 2073 Magh, 6 marks
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_8/transmission_and_distribution_system_design/tower-cost-factors-bending-moment
- Whole chapter: https://www.bctengineer.com/md/semester_8/transmission_and_distribution_system_design/chapter-4

## Question

Explain the factors affecting the tower cost for transmission line. Derive the expression for computing the bending moment acting on tower due to turning of line by an angle of α.

## Short answer

Tower cost depends on height, bending moment, voltage, span, conductor size, line deviation, climate, and safety factor. Bending moment due to line deviation α: resultant force along internal bisector is 2T sin(α/2) per conductor; adding wind load p d L gives M = Σ(2T sin(α/2) + p d L) h_i summed over all wires.

## Answer

Tower cost is roughly proportional to tower weight. By Ryle's formula, $W_t = K H_t\sqrt{M\times FS}$, so the weight depends on the tower height $H_t$ and on the bending (overturning) moment $M$ at its base.

#### Factors affecting tower cost
1. **Voltage level:** a higher voltage needs longer insulator strings and air clearances. This makes the cross arms longer, the conductor spacing larger, the ground clearance higher, and so the tower taller.
2. **Span length:** a longer span gives a larger sag and a taller tower. It also gives a larger wind span, so the bending moment rises. On the other hand, fewer towers are needed per km.
3. **Conductor size and tension:** a larger diameter means more wind load. A heavier conductor means a larger vertical load. Higher tension means larger loads at angle points and under broken-wire conditions.
4. **Number of circuits and earth wires:** a double circuit adds cross-arm levels and doubles the loads on the tower.
5. **Line deviation angle:** angle towers (type B, C, D) must resist $2T\sin(\alpha/2)$ from every wire, so they are heavier.
6. **Climate:** wind pressure, ice loading and temperature range.
7. **Terrain and soil:** foundation type, hill slopes, river crossings needing extra-tall towers, and transport access.
8. **Factor of safety** and broken-wire conditions in the design code.

#### Bending moment due to a line deviation of α
The line turns through an angle α at the tower. Each wire pulls with tension $T$ along the two line directions.

```text
  T (to span 1)                          T (to span 2)
       `-._                          _.-`
           `-._         F        _.-`
               `-._     ^    _.-`
                   `-._ | _.-`
                        O   tower
  each pull makes alpha/2 with the original line direction
  and (90 deg - alpha/2) with the bisector OF
```

1. Without the turn the two pulls are exactly opposite. After turning by α, each pull makes an angle of $(90^\circ-\alpha/2)$ with the bisector of the angle between the two spans.
2. Resolve each pull. The components perpendicular to the bisector are $T\cos(\alpha/2)$ in opposite directions, so they cancel.
3. The components along the bisector are each $T\cos(90^\circ-\alpha/2) = T\sin(\alpha/2)$, in the same direction, so they add:
$$
F = T\sin\frac{\alpha}{2} + T\sin\frac{\alpha}{2} = 2T\sin\frac{\alpha}{2}
$$
   This resultant acts along the bisector, towards the inside of the angle.
4. This force acts at the height $h_i$ of each wire. Wind on each wire, over its wind span $L$, adds $p\,d\,L$. So the bending moment at ground level is:

$$
M = \sum_{i}\left(2T_i\sin\frac{\alpha}{2} + p\,d_i\,L\right)h_i
$$

The sum covers every power conductor and the earth wire(s). For a double circuit there are two conductors at each of the three levels, and the earth wire acts at the top height $H_t$.

For a straight-line tower, α ≈ 0, so only the wind term remains. For angle towers the deviation term usually dominates. For example, with $T=6000$ kg and $\alpha = 30^\circ$, the deviation force is $2\times6000\sin15^\circ = 3106$ kg per conductor. That is much larger than the wind load on a 300 m span of a 4 cm conductor, which is $100\times0.04\times300 = 1200$ kg.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. Why does tower cost depend on height and moment?
   A. Weight by Ryle's formula W = K Ht sqrt(M x FS), and cost is about proportional to weight
   B. Cost depends only on voltage
   C. Cost depends on span only
   D. Cost is independent of loads
   Answer: A. Cost follows tower weight, which grows with height and base bending moment. (Key point: Tower weight relation)

2. How does increasing span affect tower cost?
   A. Fewer towers per km but taller towers with larger wind span, raising moment
   B. Always lowers cost
   C. No effect
   D. Only reduces tower height
   Answer: A. Span trades fewer towers against larger sag, height and wind load per tower. (Key point: Effect of span length)

3. What is the resultant force per wire at a line turn of α?
   A. T sin α
   B. 2T sin(α/2) along the bisector
   C. 2T cos(α/2)
   D. T cos α
   Answer: B. Components perpendicular to the bisector cancel and the two T sin(α/2) components add. (Key point: Resultant deviation force)

4. Which is the bending moment at ground level for an angle tower?
   A. M = sum of (2T sin(α/2) + p d L) h_i over all wires
   B. M = T sin α only
   C. M = sum of p d L only
   D. M = 2T sin(α/2) x span
   Answer: A. Each wire contributes deviation plus wind force acting at its height h_i. (Key point: Bending moment expression)

## Related in Transmission and Distribution System Design

- [Force on angle tower: 2T sin(α/2)](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Aangle-tower-force-2t-sin) — Transmission and Distribution System Design, chapter 4
- [Bending moment ratio, 132 kV vs 220 kV towers](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Abending-moment-ratio-132-220kv) — Transmission and Distribution System Design, chapter 4
- [Factors affecting choice of BIL](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Abil-choice-factors) — Transmission and Distribution System Design, chapter 3
- [Factors affecting air clearance](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Aair-clearance-factors) — Transmission and Distribution System Design, chapter 3
- [Tower dimensions for 220 kV single circuit line](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atower-dimensions-220kv) — Transmission and Distribution System Design, chapter 4, asked 2×
- [Tower dimensions for 220 kV double circuit line](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atower-dimensions-220kv-double-circuit) — Transmission and Distribution System Design, chapter 4, asked 2×

## Related in other subjects

- [Cost vs value; factors affecting valuation](https://www.bctengineer.com/question.md?key=semester_8%2Fconstruction_management%3Acost-vs-value-factors) — Construction Management, chapter 13
- [Strain energy due to bending, rectangular beam](https://www.bctengineer.com/question.md?key=semester_4%2Ftheory_of_structures_i%3Astrain-energy-bending-derivation) — Theory of Structures I, chapter 2, asked 2×
- [Derive input impedance of transmission line](https://www.bctengineer.com/question.md?key=semester_3%2Felectromagnetism%3Aderive-input-impedance-line) — Electromagnetism, chapter 5
- [Inertia force and turning moment in an engine](https://www.bctengineer.com/question.md?key=semester_6%2Ftheory_of_mechanism_and_machine_i%3Areciprocating-engine-inertia-force-torque) — Theory of Mechanism and Machine I, chapter 8