# Percentage energy loss of 25 kVA transformer

Transmission and Distribution System Design · Chapter 7: Distribution System Design

- Asked in: 2080 Chaitra, 8 marks
- Video: [How to Calculate Transformer Losses at a Percent Full Load (PE Power Exam)](https://www.youtube.com/watch?v=5pUQFrbX3hI) — Raiya Academy
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_8/transmission_and_distribution_system_design/transformer-energy-loss-25kva
- Whole chapter: https://www.bctengineer.com/md/semester_8/transmission_and_distribution_system_design/chapter-7

## Question

A distribution transformer of 25 kVA with no-load loss of 72 W and rated copper loss is 300 W. Consider the demand for the transformer is 20 kW and the monthly energy sell equals 4800 units @ 0.85 power factors. Use Loss of Load Factor (LLF) = 0.3LF + 0.7LF². Find the percentage energy loss.

## Short answer

Load factor = 4800/(20×720) = 0.333, LLF = 0.1778. Peak copper loss = 300×(23.53/25)² = 265.7 W. Monthly core loss 51.84 kWh, copper loss 34.02 kWh. Total loss 85.86 kWh gives percentage loss = 85.86/4800×100 ≈ 1.79%.

## Answer

Percentage energy loss = (core energy loss + copper energy loss) / energy sold × 100. Copper energy loss uses the loss of load factor.

**Assumption:** month = 30 days = 720 h.

#### Step 1: Load factor

$$
LF = \frac{\text{Energy}}{P_{max} \times T} = \frac{4800}{20 \times 720} = 0.3333
$$

#### Step 2: Loss of load factor

$$
\begin{aligned}
LLF &= 0.3\,LF + 0.7\,LF^2 \\
&= 0.3(0.3333) + 0.7(0.3333)^2 \\
&= 0.1000 + 0.0778 = 0.17778
\end{aligned}
$$

#### Step 3: Copper loss at peak load

$$
\begin{aligned}
S_{peak} &= \frac{20}{0.85} = 23.529 \text{ kVA} \\
P_{cu,peak} &= 300 \times \left(\frac{23.529}{25}\right)^2 = 300 \times 0.8858 = 265.74 \text{ W}
\end{aligned}
$$

#### Step 4: Monthly energy losses

$$
\begin{aligned}
E_{cu} &= 0.26574 \times 0.17778 \times 720 = 34.02 \text{ kWh} \\
E_{core} &= 0.072 \times 720 = 51.84 \text{ kWh} \\
E_{loss} &= 34.02 + 51.84 = 85.86 \text{ kWh}
\end{aligned}
$$

#### Step 5: Percentage energy loss

$$
\%E_{loss} = \frac{85.86}{4800} \times 100 = 1.79\%
$$

(Based on energy input $4800 + 85.86 = 4885.86$ kWh, it is $85.86/4885.86 = 1.76\%$.)

**Answer: Percentage energy loss ≈ 1.79% of energy sold** (monthly loss ≈ 85.9 kWh: 51.84 kWh core loss + 34.02 kWh copper loss).

Note that core loss is the larger part, because the load factor is low (0.33): the transformer is energised all month but carries peak load only briefly.

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. With 4800 kWh, 20 kW peak and 720 h, the load factor is:
   A. 0.50
   B. 0.3333
   C. 0.8
   D. 0.2
   Answer: B. LF = 4800/(20 x 720) = 0.3333. (Key point: Load factor)

2. LLF = 0.3LF + 0.7LF^2 for LF = 0.3333 equals:
   A. 0.1778
   B. 0.3333
   C. 0.1111
   D. 0.2333
   Answer: A. 0.1 + 0.0778 = 0.1778. (Key point: LLF)

3. Peak copper loss is found by:
   A. Using 300 W directly
   B. 300 x (23.53/25)^2 = 265.7 W, with S = 20/0.85
   C. 300 x (20/25)^2
   D. 300 x 0.85
   Answer: B. Copper loss scales with the square of kVA load; peak is 20/0.85 = 23.53 kVA. (Key point: Copper loss at peak)

4. Total monthly loss and its percentage of energy sold:
   A. 85.86 kWh, 1.79%
   B. 51.84 kWh, 1.08%
   C. 34.02 kWh, 0.7%
   D. 85.86 kWh, 17.9%
   Answer: A. Core 51.84 plus copper 34.02 = 85.86 kWh; 85.86/4800 = 1.79%. (Key point: Result)

## Related in Transmission and Distribution System Design

- [Monthly energy loss of 50 kVA transformer](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atransformer-monthly-loss-50kva) — Transmission and Distribution System Design, chapter 7
- [Energy loss of 100 kVA transformer in third year](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atransformer-energy-loss-third-year) — Transmission and Distribution System Design, chapter 7
- [Monthly energy loss in four secondary lines](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Amonthly-loss-four-secondary-lines) — Transmission and Distribution System Design, chapter 7
- [T/F: % power loss equals % energy loss](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Atf-power-loss-energy-loss-same) — Transmission and Distribution System Design, chapter 6
- [LT feeder options: loss and voltage drop, 50 kW](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Alt-feeder-two-options-50kw) — Transmission and Distribution System Design, chapter 7, asked 3×
- [Peak demand of load center from load pattern](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Apeak-demand-load-center-load-pattern) — Transmission and Distribution System Design, chapter 6, asked 2×

## Related in other subjects

- [Design: 25 kVA 11000/433 V distribution transformer](https://www.bctengineer.com/question.md?key=semester_5%2Felectric_machine_design%3Adesign-25kva-11000-433) — Electric Machine Design, chapter 3
- [Equivalent impedance and copper loss of 50 kVA transformer](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3A50kva-4400-220-equivalent-copper-loss) — Electrical Machines I, chapter 2
- [50 kVA transformer: equivalent parameters, copper loss](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines%3Atf-50kva-4400-220-equivalent-resistance) — Electrical Machines, chapter 2
- [Efficiency of 5 kVA transformer at 2 kW load](https://www.bctengineer.com/question.md?key=semester_4%2Felectrical_machines_i%3A5kva-1100-110-max-efficiency-40a) — Electrical Machines I, chapter 2