title: "Power loss, 10 km 11 kV UDL feeder"
subject: "Transmission and Distribution System Design"
chapter: 7
key: "semester_8/transmission_and_distribution_system_design:udl-feeder-10km-11kv"
source: https://www.bctengineer.com/q/semester_8/transmission_and_distribution_system_design/udl-feeder-10km-11kv
site: BCT Engineering
---

# Power loss, 10 km 11 kV UDL feeder

Transmission and Distribution System Design · Chapter 7: Distribution System Design

- Asked in: 2068 Bhadra (old course), 4+4 marks
- Video: [Lecture video 18EE43 Module 5  Uniformely distributed loads  Malini k v](https://www.youtube.com/watch?v=S1Xfhg3sef0) — Sairam EE Video
- Answer checked by Claude Opus 5.5 (high effort) on 2026-10-14
- Page: https://www.bctengineer.com/q/semester_8/transmission_and_distribution_system_design/udl-feeder-10km-11kv
- Whole chapter: https://www.bctengineer.com/md/semester_8/transmission_and_distribution_system_design/chapter-7

## Question

Compute the power loss for a 10 km long 11 kV, 3-phase distribution feeder having sending end current of 100 A with uniformly distributed load (Use R = 0.4 Ω/km, X = 0.3 Ω/km). Derive any expression used.

## Short answer

For a uniformly distributed feeder, three-phase power loss equals I_s^2 r l. With sending-end current 100 A, r = 0.4 Ω/km, l = 10 km, loss = 40 kW.

## Answer

#### Derivation for uniformly distributed load
Let a feeder of length $l$ carry sending-end current $I_s$, with load tapped uniformly so the current falls linearly to zero at the far end:
$$
I(x) = I_s\left(1-\frac{x}{l}\right)
$$
Per-phase voltage drop, with $z = r + jx$ per km:
$$
V_D = \int_0^l z I_s\left(1-\frac{x}{l}\right)dx = \frac{1}{2}I_s z l
$$
Three-phase power loss:
$$
P_L = 3\int_0^l r I_s^2\left(1-\frac{x}{l}\right)^2dx = 3\cdot\frac{1}{3}I_s^2 r l = I_s^2 r l
$$
So a UDL feeder behaves like the whole load lumped at the **middle** for voltage drop, and at **one-third** of the length for loss.

#### Why $1/3$
Each small element $dx$ at distance $x$ carries current $I(x)$. Integrating $r I(x)^2$ gives
$$
\int_0^l\left(1-\frac{x}{l}\right)^2dx = \frac{l}{3}
$$
so the loss is only one-third of what it would be with the whole load at the far end.

#### Substitution
$I_s = 100$ A, $r = 0.4\ \Omega$/km, $l = 10$ km, so $R = 4\ \Omega$ per phase.
$$
\begin{aligned}
P_L &= 3\times\frac{1}{3}I_s^2 R = I_s^2 R\\
&= 100^2\times0.4\times10 = 40{,}000\ \text{W}
\end{aligned}
$$
(For comparison, with the same current lumped at the end, loss $=3\times100^2\times4 = 120$ kW.)

The reactance $X = 0.3\ \Omega$/km does not affect real power loss; it only enters the voltage drop, $V_D = \frac12 I_s(R\cos\phi + X\sin\phi)$.

**Answer: Power loss = 40 kW.**

## Check yourself

The answer's key points as multiple-choice questions, with the correct option and why.

1. For a 3-phase UDL feeder, the power loss is:
   A. 3 I_s^2 R
   B. I_s^2 R
   C. I_s^2 R / 3
   D. I_s^2 R / 2
   Answer: B. 3 x (1/3) I_s^2 R = I_s^2 R. (Key point: UDL loss expression)

2. Why is the UDL loss one third of the end-lumped loss per phase?
   A. The integral of (1 - x/l)^2 over the length equals l/3
   B. Load is at one third of the feeder voltage
   C. Reactance reduces loss
   D. Only a third of the feeder is energised
   Answer: A. Current decreases linearly, so integrating I^2 gives l/3 of the lumped value. (Key point: Why one third)

3. What is the effect of X = 0.3 Ω/km on the power loss?
   A. Loss increases by X/R
   B. None; X only enters the voltage drop
   C. Loss is halved
   D. Loss is multiplied by sqrt3
   Answer: B. Real power loss is I^2R; reactance affects voltage drop only. (Key point: Role of X)

4. With I_s = 100 A, r = 0.4 Ω/km, 10 km, the loss is:
   A. 120 kW
   B. 40 kW
   C. 16 kW
   D. 4 kW
   Answer: B. 100^2 x 0.4 x 10 = 40 kW (the end-lumped value would be 120 kW). (Key point: Numerical result)

## Close variants set in other exams

- [Loss and drop, 15 km 11 kV feeder](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Audl-feeder-15km-11kv) — Transmission and Distribution System Design, chapter 7, asked 2×

## Related in Transmission and Distribution System Design

- [Loss and voltage drop, 16 km uniformly varying load](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Auniformly-varying-load-16km-feeder) — Transmission and Distribution System Design, chapter 7
- [Voltage drop and loss, uniformly varying load](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Avoltage-drop-loss-uniformly-varying) — Transmission and Distribution System Design, chapter 7, asked 2×
- [Voltage drop and loss with uniformly distributed load](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Avoltage-drop-loss-uniform-load) — Transmission and Distribution System Design, chapter 7, asked 2×
- [LT feeder options: loss and voltage drop, 50 kW](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Alt-feeder-two-options-50kw) — Transmission and Distribution System Design, chapter 7, asked 3×
- [Peak loss and voltage drop for LT feeder options](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Alt-feeder-configuration-options) — Transmission and Distribution System Design, chapter 7, asked 2×
- [Capacitor size, four-node 11 kV feeder](https://www.bctengineer.com/question.md?key=semester_8%2Ftransmission_and_distribution_system_design%3Acapacitor-size-four-node-feeder) — Transmission and Distribution System Design, chapter 7, asked 5×

## Related in other subjects

- [110 km, 110 kV line: sending end, regulation, efficiency](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3A110km-line-performance) — Power System Analysis I, chapter 6, asked 2×
- [Sending end active power from ABCD, 132/130.5 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Asending-power-132kv-130-5kv) — Power System Analysis I, chapter 6
- [400 km long line, 60 MVA at 220 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Along-line-400km-60mva) — Power System Analysis I, chapter 5
- [Sending and receiving power, 140∠10° and 132 kV](https://www.bctengineer.com/question.md?key=semester_4%2Fpower_system_analysis_i%3Apower-140kv-132kv-a099) — Power System Analysis I, chapter 6