Process to determine wire size

Short answer

Add all load powers, compute load current using I=P/(V cosφ) for single phase or I=P/(1.732 VL cosφ) for three phase, apply a 20–25% safety margin, then select a standard conductor size whose ampacity meets this current. Finally check voltage drop (≤3–5%) and coordinate with the protective device; e.g. 2 kW heater at 230 V needs 2.5 mm² copper with 16 A MCB.

Explain the process to determine the size of the wire.

The size (cross-sectional area) of a conductor must allow it to carry the load current safely, without overheating and without an excessive voltage drop. The steps are:

1. Find the total load. Add the power ratings of all appliances on the circuit:

Ptotal=∑PP_{total}=\sum P

2. Calculate the load current.

Single phase:

I=PVcos⁡ϕI=\frac{P}{V\cos\phi}

Three phase:

I=P3 VLcos⁡ϕI=\frac{P}{\sqrt3\,V_L\cos\phi}

3. Apply a safety margin and diversity factor. Increase the current by 20-25% for future expansion (or use a diversity factor if not all loads operate at once).

4. Select the wire size for current-carrying capacity. From the manufacturer's or a standard table (such as IS/IEC), choose a conductor whose rated ampacity is at least the design current, considering the ambient temperature, the method of installation (conduit, open) and the number of cables grouped together. Typical copper sizes: 1.5 mm² (lighting, up to 10 A), 2.5 mm² (power sockets, 16 A), 4 mm² (geysers, ACs, 25 A), 6 mm² (32 A).

5. Check the voltage drop. The drop in the cable should not exceed about 3-5% of the supply voltage:

ΔV=I⋅R=I⋅ρLA\Delta V=I\cdot R=I\cdot\frac{\rho L}{A}

Here LL is the total conductor length (go and return for a single-phase circuit). If the drop exceeds the limit, choose a larger size.

6. Check the short-circuit withstand and coordinate with the protective device (MCB rating at or above the load current and not above the cable rating).

Example: a 2 kW heater at 230 V, pf 1, draws I=8.7I=8.7 A; with a 25% margin this is 10.9 A, so a 2.5 mm² copper wire with a 16 A MCB is selected.