Conditions for induction generator, T-S curve
Short answer
The machine must be driven above synchronous speed so slip is negative, and it must receive reactive power from the grid or capacitors. In the T-s curve, s<0 gives negative torque and power flow to the supply. Prime mover torque must stay below the generating pull-out torque.
What are the conditions to be fulfilled for the operation of induction machine as induction generator? Explain with the help of T-S curve.
An induction machine works as an induction generator when its rotor is driven by a prime mover above synchronous speed, so the slip becomes negative and the torque reverses. It then delivers active power to the supply.
Conditions for generator operation
- Speed above synchronous speed: , so slip .
- Source of reactive power: the machine has no separate field winding. It must take its magnetising current from the grid (grid-connected), or from a capacitor bank across the stator terminals (self-excited, stand-alone).
- Frequency and voltage fixed by the grid: when grid-connected, the grid keeps the frequency and terminal voltage. For stand-alone use, residual magnetism and sufficient capacitance are needed for voltage build-up.
- Prime mover with enough power: a turbine or engine must drive the rotor so that the mechanical input exceeds losses. The speed is only 2 to 5 % above at rated load.
- Capacitor value must exceed a critical value so that the magnetising line is crossed (self-excited case).
Explanation with T-S curve
The torque-slip curve extends on both sides of .
- : motoring region (torque positive, power flows from the supply to the shaft).
- : generating region. The curve is an inverted image of the motoring part, with torque negative. The maximum (pull-out) generating torque occurs at .
- : braking (plugging) region, rotor runs opposite to the field.
T
| motoring
| _.-*-._
| _-' `-._
+-----+-------+-----------> s
s=1 s=0 (N=Ns)
... _.-' generating (s<0)
| *-'
|
Beyond the slip is negative, the rotor emf and current reverse, and the electromagnetic torque opposes the prime mover. The air-gap power becomes negative, meaning power is fed to the stator and then to the grid. If the driving torque exceeds the maximum generating torque, the machine runs away (loses stability), so the prime mover torque must stay below the pull-out value.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Need and conditions for parallel operation of transformers · Electrical Machines I, chapter 2
- Induction generator in isolated and grid-connected modes · Electrical Machines I, chapter 5 · asked 5×
- Isolated induction generator and renewable energy role · Electrical Machines I, chapter 5
- Excitation capacitors in isolated and grid-connected induction generator · Electrical Machines I, chapter 5
- Conditions for parallel operation of transformers · Electrical Machines I, chapter 2
- Conditions for parallel operation of transformers · Electrical Machines, chapter 2
- Choice of specific electric loading in induction machine · Electric Machine Design, chapter 4 · asked 3×
- Effect of too wide air gap in induction machine · Electric Machine Design, chapter 4
- Choice of magnetic loading in induction machine · Electric Machine Design, chapter 4
- 3-phase induction machine at slip 0.05 · Basic Electrical and Electronics Engineering, chapter 2