Preventing ground loops; electromagnetic coupling

Short answer

Prevent ground loops by single-point grounding, isolation (transformers, optocouplers), differential signaling, grounding shields at one end, and minimizing loop area. Electromagnetic (radiated) coupling occurs when far-field waves induce voltages in conductors acting as antennas. Mitigate with metal shielding, filtering, and minimizing trace lengths.

How ground loop can be prevented? Explain the Electromagnetic coupling.

Preventing ground loops

A ground loop forms when a circuit is grounded at more than one point, so the ground-potential difference drives noise current. To prevent it:

  • Use single-point (star) grounding at low frequency.
  • Use isolation: isolation transformer, opto-coupler or differential amplifier to break the loop.
  • Ground the cable shield at only one end (low frequency).
  • Use balanced differential signalling and twisted pairs, to cancel the induced voltage.
  • Reduce the loop area and keep all equipment on one power circuit.
  • Use common-mode chokes or a ferrite on cables.

Electromagnetic (radiated) coupling

Electromagnetic coupling occurs when a source emits a radiating wave, and wires, traces or loops of the receiver act as antennas that pick up the energy. It occurs in the far field (distance greater than λ/2π), where electric and magnetic fields travel together with wave impedance of 377 ohm.

  • Sources: radio/TV transmitters, mobile phones, switching power supplies, digital clocks, motors with sparking brushes, and lightning.
  • Receiver: any conductor of length near λ/4 or longer; the induced voltage is proportional to the field strength and effective antenna length.
  • Reduction: enclose the circuit in a grounded metal shield, filter all lines entering the enclosure, reduce lead and trace lengths, use shielded or twisted cables, ferrite beads, increase distance, slow down clock edges.