Design strength of ISA 100x75x6, 6 bolts

Short answer

Design tensile strength is 229.5 kN (yielding of gross section). For full capacity, 8 M16 (grade 4.6) bolts are needed in the connection.

A single unequal angle 100x75x6 is connected to a 10mm thick gusseted plate at the ends with six 16mm diameter bolts to transfer tension as shown in figure below. Determine the design tensile strength of the angle assuming that the yield and the ultimate stress of steel used are 250 MPa and 410 MPa if the gusset plate is connected to the longer leg. Also design connection for its full capacity. [Figure: ISA 100x75x6 (A = 1010 mm²) connected through its 100 mm leg to a 10 mm gusset plate with 16 mm bolts]

Data: ISA 100×75×6 (Ag=1010A_g=1010 mm²), gusset 10 mm connected to the 100 mm leg by six 16 mm bolts (d0=18d_0=18 mm); fy=250f_y=250, fu=410f_u=410 N/mm². Assumed layout: single line of bolts, pitch p=50p=50 mm, end distance 30 mm, bolt line 55 mm from the heel (edge distance 45 mm to the toe). Bolts assumed grade 4.6.

1. Yielding of gross section (cl. 6.2)

Tdg=Agfyγm0=1010×2501.10×10−3=229.5 kNT_{dg}=\frac{A_gf_y}{\gamma_{m0}}=\frac{1010\times250}{1.10}\times10^{-3}=229.5\ \text{kN}

2. Rupture of net section with shear lag (cl. 6.3.3)

  • Connected leg: Anc=(100−62−18)×6=474A_{nc}=(100-\tfrac{6}{2}-18)\times6=474 mm²
  • Outstanding leg: Ago=(75−62)×6=432A_{go}=(75-\tfrac{6}{2})\times6=432 mm²
  • w=75w=75 mm, bs=w+w1−t=75+55−6=124b_s=w+w_1-t=75+55-6=124 mm (w1w_1 = distance of the bolt line from the heel), Lc=5×50=250L_c=5\times50=250 mm
β=1.4−0.076wtfyfubsLc=1.4−0.076×756×250410×124250=1.113(0.7≤β≤1.443)\beta=1.4-0.076\frac{w}{t}\frac{f_y}{f_u}\frac{b_s}{L_c}=1.4-0.076\times\frac{75}{6}\times\frac{250}{410}\times\frac{124}{250}=1.113\quad(0.7\le\beta\le1.443) Tdn=0.9Ancfuγm1+βAgofyγm0=139.9+109.3=249.2 kNT_{dn}=\frac{0.9A_{nc}f_u}{\gamma_{m1}}+\frac{\beta A_{go}f_y}{\gamma_{m0}}=139.9+109.3=249.2\ \text{kN}

3. Block shear (cl. 6.4)

Avg=1680A_{vg}=1680, Avn=1086A_{vn}=1086, Atg=270A_{tg}=270, Atn=216A_{tn}=216 mm²

  • Tdb1=Avgfy3γm0+0.9Atnfuγm1=284.2T_{db1}=\dfrac{A_{vg}f_y}{\sqrt3\gamma_{m0}}+\dfrac{0.9A_{tn}f_u}{\gamma_{m1}}=284.2 kN
  • Tdb2=0.9Avnfu3γm1+Atgfyγm0=246.5T_{db2}=\dfrac{0.9A_{vn}f_u}{\sqrt3\gamma_{m1}}+\dfrac{A_{tg}f_y}{\gamma_{m0}}=246.5 kN

Design tensile strength Td=min⁡(229.5, 249.2, 246.5)=229.5T_d=\min(229.5,\ 249.2,\ 246.5)=229.5 kN (yielding of gross section governs).

Design of connection for full capacity (16 mm, 4.6 bolts)

  • Vdsb=4003×1571.25×10−3=29.01V_{dsb}=\dfrac{400}{\sqrt3}\times\dfrac{157}{1.25}\times10^{-3}=29.01 kN
  • Bearing on the 6 mm angle (e=30, p=50e=30,\ p=50): kb=0.556k_b=0.556, Vdpb=43.7V_{dpb}=43.7 kN
  • Number of bolts =229.529.01=7.91=\dfrac{229.5}{29.01}=7.91 → 8 bolts (the six bolts are not enough for the full capacity).

Answer: design tensile strength ≈229.5\approx229.5 kN; connect with 8 M16 bolts (4.6) at 50 mm pitch (a longer joint) or use higher-grade bolts. With six bolts the connection strength would be only 6×29.0=174.06\times29.0=174.0 kN.