- 2082 Kartik · 8 marks
Pulse TF with digital PID, plant 1/(s(s+2))
Short answer
Digital PID with Kp=1, Ki=0.2, Kd=0.2 gives G_D(z)=(1.4z²-1.4z+0.2)/(z(z-1)). ZOH plus plant 1/s(s+2) with T=1 yields G(z)=(0.2838z+0.1485)/((z-1)(z-0.1353)). Closed-loop: C/R = (0.3974z³-0.1895z²-0.1511z+0.0297)/(z⁴-1.7380z³+1.0812z²-0.2865z+0.0297).
For the control system with digital PID controller as shown in the figure, obtain the pulse transfer function. Assume that the sampling period T is 1 second. Consider Kₚ=1, KI=0.2 and Kd=0.2 of PID controller. [Figure: unity-feedback loop: r(t) → summing junction → e(t) → sampler (T = 1) → e(kT) → digital controller → ZOH → 1/s(s+2) → C(t)]
The digital controller is a PID controller. It is followed by a ZOH and the plant, with one sampler on the error signal, so:
Step 1: Digital PID controller
Digital PID controller. Using the positional PID form (Ogata), with , , :
Step 2: ZOH + plant
With and :
Step 3: Open-loop pulse transfer function
Step 4: Closed-loop pulse transfer function
or
Answer: The closed-loop pulse transfer function is as above, with characteristic equation .
Check: At the numerator is and the denominator is , so the DC gain is about 1, as expected with integral action.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Pulse TF with PID controller, plant 1/(s+1) · Digital Control System, chapter 3 · asked 2×
- Closed-loop TF with digital PID, plant 1/(s(s+1)) · Digital Control System, chapter 3 · asked 2×
- Pulse transfer function of digital PID controller · Digital Control System, chapter 3 · asked 2×
- Response sequence with digital PI controller · Digital Control System, chapter 3
- Digital PD controller design for plant 1/s² · Digital Control System, chapter 4 · asked 2×
- Closed-loop pulse TF with two samplers and H(s) · Digital Control System, chapter 3 · asked 2×
- Transfer function with G3 feedforward, H1 and unity loop · Control Systems, chapter 3
- PID controller block diagram, transfer function, characteristics · Control Systems, chapter 7
- Range of PI gains Kp, KI for stability · Control Systems, chapter 4