Emergency supply and Ah vs Wh efficiency
Short answer
Emergency supply independently powers essential loads when normal supply fails, using batteries, UPS, DG with AMF, or a second feeder. Ah efficiency is Ah out divided by Ah in; Wh efficiency is Wh out divided by Wh in, and is lower because charge voltage exceeds discharge voltage; example gives 80% and 72.13%.
What is emergency supply system for industrial plant? Differentiate between Ah efficiency and Wh efficiency of battery.
Emergency supply system for an industrial plant
An emergency supply system is an independent, automatically started power source that supplies the essential loads of a plant when the normal supply fails, to protect life, equipment and critical processes.
Essential loads: escape and exit lighting, fire alarm, fire pumps, lifts, control and protection supplies, process loads needing safe shutdown (cooling, stirring, lubrication), communication and security.
Sources:
- Battery systems – self-contained or central battery; supply is instant.
- UPS – no-break supply for computers, PLCs and instruments.
- Diesel generator with AMF panel – starts automatically in about 10–15 s; feeds large loads for long periods.
- Second utility feeder with automatic transfer switch (ATS).
Utility ─►[ATS]─► Essential bus ─► fire pump, lights
▲
DG set ─────┘
Battery/UPS ─────► PLC, alarm, control (no break)
Essential loads are kept on a separate bus, batteries are on float/trickle charge, and the system is tested regularly.
Ah efficiency vs Wh efficiency
η_Ah = Ah delivered on discharge / Ah supplied on charge
η_Wh = Wh delivered on discharge / Wh supplied on charge
= η_Ah × (V_avg discharge / V_avg charge)
| Point | Ah efficiency | Wh efficiency |
|---|---|---|
| Based on | Quantity of charge only | Energy (charge × voltage) |
| Considers voltage | No | Yes |
| Losses included | Gassing, side reactions | Also I²R and polarisation losses |
| Value (lead-acid) | 80–90% | 70–80% |
| Relation | Always higher | Lower, since V_charge > V_discharge |
| Use | Deciding charging time/Ah needed | Energy cost and economics |
Example: discharge 4 A × 12 h at 2.2 V, charge 3 A × 20 h at 2.44 V → η_Ah = 48/60 = 80%, η_Wh = 105.6/146.4 = 72.13%.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Trickle charging and Ah/Wh efficiency (4 A, 12 h, 1.2 V) · Industrial Power Distribution and Illumination, chapter 9 · asked 3×
- Trickle charging and Ah/Wh efficiency (2.2 V, 2.44 V) · Industrial Power Distribution and Illumination, chapter 9 · asked 3×
- Trickle charging and Ah/Wh efficiency (30 A, 6 h) · Industrial Power Distribution and Illumination, chapter 9 · asked 2×
- Types of power supply system for industrial plant · Industrial Power Distribution and Illumination, chapter 1 · asked 2×
- Importance of emergency supply, online vs offline UPS · Industrial Power Distribution and Illumination, chapter 9
- Emergency power supply system for industry · Industrial Power Distribution and Illumination, chapter 9 · asked 2×
- Fuel supply system of diesel plant · Power Plant Equipment, chapter 5 · asked 3×
- Battery charger bridge 15 V: currents, power, efficiency · Power Electronics, chapter 2 · asked 3×
- Battery charger bridge: average current, efficiency · Power Electronics, chapter 2
- Diesel plant components and fuel supply · Power Plant Equipment, chapter 5 · asked 3×
All Industrial Power Distribution and Illumination chapter 9 questions →