- Asked 4/20
- 2080 Chaitra · 4 marks
- 2077 Chaitra · 4 marks
- 2070 Bhadra · 8 marks
- 2068 Magh (old course) · 4 marks
Types of lighting scheme in industry
Short answer
Industrial schemes include general lighting for uniform area illumination, local lighting for high illuminance at specific tasks, and general plus local lighting. By distribution: direct (90-100% downward) is common in workshops, semi-direct in offices, and indirect in areas where glare must be avoided. Emergency lighting ensures safety during supply failure.
Explain different types of lighting scheme used in an industry.
A lighting scheme is the way luminaires are arranged to provide light for the work in an area. Industries use the following schemes:
1. General lighting
Luminaires are spread in a regular pattern over the whole area to give uniform illumination (e.g. 200–300 lux) on the working plane, independent of where machines are placed. Spacing–height ratio is kept within limits for uniformity. Used in assembly halls, warehouses and general workshops.
2. Localised (local) lighting
Extra lamps are fixed close to particular work points (on a lathe, inspection bench, drawing board) to give high illumination (500–1000+ lux) only where fine work is done. Saves energy but gives strong contrast if used alone.
3. General plus local (supplementary) lighting
Moderate general lighting for movement and safety, plus local lamps at critical tasks. This is the usual scheme in machine shops: it is economical and avoids dark surroundings and eye strain.
4. Localised general lighting
General-type luminaires are concentrated in the zones where work is done (above machine rows), with lower lighting over gangways.
5. Emergency lighting
Battery-backed or generator-fed lights that come on when the normal supply fails, lighting escape routes, exits, stairs and critical machines (minimum about 1 lux on escape routes).
Classification by light distribution
| Scheme | Downward light | Use in industry |
|---|---|---|
| Direct | 90–100 % | High-bay halls, workshops (most common) |
| Semi-direct | 60–90 % | Offices, control rooms |
| General diffusing | 40–60 % | Canteens |
| Semi-indirect / indirect | 0–40 % | Drawing offices, VDU rooms (no glare) |
In factories, direct general lighting with high-bay LED or metal-halide luminaires plus local lighting at machines is the normal choice, with phases distributed to avoid stroboscopic effect.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Industry room 30 × 20 m LED lighting and DB · Industrial Power Distribution and Illumination, chapter 7 · asked 2×
- Street lighting scheme design procedure · Industrial Power Distribution and Illumination, chapter 8
- Lighting schemes: local, general, emergency · Industrial Power Distribution and Illumination, chapter 7 · asked 2×
- Energy and cost saving from lighting retrofit · Industrial Power Distribution and Illumination, chapter 10
- Factors in power and lighting system design · Industrial Power Distribution and Illumination, chapter 5
- Emergency lighting purposes and trickle charging · Industrial Power Distribution and Illumination, chapter 9
- Tariff types used in industry billing by NEA · Utilization of Electrical Energy, chapter 6
- Why bricks are widely used · Civil Engineering Materials, chapter 3 · asked 3×
- Regenerative scheme with open feed water heater · Power Plant Equipment, chapter 7
All Industrial Power Distribution and Illumination chapter 7 questions →