Charging lead acid battery from AC source

Short answer

Common methods include constant-current, constant-voltage, trickle, float, and boost charging using a step-down transformer and rectifier. Principal components are a fuse/switch, isolating transformer, diode/SCR bridge, smoothing choke/capacitor, current controller, meters, reverse-current protection, automatic cut-off, and cooling.

What are the methods commonly adopted for charging a lead acid battery from an A.C. single phase source. What are the principle components of charger of the above type?

Methods of charging a lead-acid battery from a single-phase AC source

Since the battery needs DC, the AC is first stepped down and rectified. The common methods are:

  1. Constant-current charging using a transformer, rectifier and variable series resistance (or SCR control) to hold current at about C/10. Two-rate charging lowers the current when gassing starts.
  2. Constant-voltage charging – rectifier output regulated at about 2.3–2.4 V/cell; current falls as the battery charges. A small series resistance limits the initial current (modified constant-voltage).
  3. Trickle charging – small rectifier with high series resistance gives a tiny continuous current to standby batteries.
  4. Float charging – a regulated rectifier connected in parallel with battery and load at ≈ 2.2 V/cell.
  5. Boost charging – high-current rectifier for short periods.

Rectifiers used: half-wave (small trickle chargers), centre-tap full-wave, or bridge full-wave (most common), with diodes or SCRs.

 230 V ─[F]─┬─────────┐
 1φ AC      │ Step-   │ ┌─D1─┬─D2─┐
            │ down    ├─┤    │    ├─[L]─[R]─(A)─┐
            │ transf. │ └─D3─┴─D4─┘             +│
 N ─────────┴─────────┘        │            [Battery]
                               └───────────────−─┘
                 (V) across battery

Principal components of such a charger

  1. Fuse/MCB and ON-OFF switch – protection on AC side.
  2. Step-down (isolating) transformer – lowers 230 V to the needed level and isolates the battery from mains; tappings allow coarse voltage adjustment.
  3. Rectifier – diode bridge (or SCR bridge for control) converting AC to DC.
  4. Filter / smoothing choke and capacitor – reduces ripple in the charging current.
  5. Current-control device – variable resistor, rheostat, SCR firing circuit or switch-mode regulator.
  6. Ammeter and voltmeter – to monitor charging current and battery voltage.
  7. Reverse-current/polarity protection – blocking diode so the battery cannot discharge back into the charger; reverse polarity alarm.
  8. Automatic cut-off or float controller – switches to float/trickle mode at full charge to prevent overcharging.
  9. Cooling and enclosure – heat sinks for rectifier, ventilated cabinet.