Short answer

An impedance relay measures V/I = Z and operates when Z drops below the set value. Its torque equation is T = K₁I² − K₂V² − K₄; at balance K₁I² = K₂V² so Z = √(K₁/K₂) = Zₛ. It trips when Z < Zₛ. The characteristic is a circle centred at the origin on the R-X diagram, making it non-directional.

What is an impedance relay? Starting from the universal torque equation, explain its operating principle, torque equation and operating characteristics (as used for the protection of feeder).

An impedance relay is a distance relay that measures the ratio of voltage to current (V/I = Z) at the relay point and operates when this impedance falls below a set value. Since line impedance is proportional to length, it measures the distance to the fault.

Universal torque equation

For a general electromagnetic relay with current, voltage and directional elements:

T = K₁ I² + K₂ V² + K₃ V I cos(θ − τ) + K₄

where K₁, K₂, K₃ are constants, θ is the angle between V and I, τ is the maximum torque angle, and K₄ is the mechanical restraining (spring) torque.

Torque equation of impedance relay

In the impedance relay the current element produces operating torque and the voltage element produces restraining torque; there is no directional element (K₃ = 0):

Put K₂ = −K₂ (restraint), K₃ = 0:
T = K₁ I² − K₂ V² − K₄

At the balance point (T = 0), neglecting spring torque K₄:

K₁ I² = K₂ V²
V² / I² = K₁ / K₂
Z = V / I = √(K₁ / K₂) = constant (setting Zs)

The relay operates when operating torque > restraining torque:

K₁ I² > K₂ V²   ⟹   Z = V/I < √(K₁/K₂) = Zs

Operating principle

  • Construction: a balanced beam; the current coil (fed by CT) pulls one end down, the voltage coil (fed by PT) pulls the other end.
  • Normal condition: voltage is high and current is normal, so Z_seen (load impedance) is large; voltage pull wins and contacts stay open.
  • Fault within the zone: voltage at the relay falls and current rises, so Z_seen = impedance up to the fault point < Zs; current pull wins and the relay trips.
  • Fault beyond the zone: Z_seen > Zs, so the relay does not operate.
        Voltage coil       Current coil
          (PT) ▼              ▼ (CT)
     ──────────────△───────────────
               pivot     ▲ trip contacts

Operating characteristic (R-X diagram)

Since operation depends only on |Z|, the characteristic is a circle centred at the origin with radius Zs.

          X
          │   .-~~~-.
          │ /  Trip  \
        ──┼─(  zone   )── R
          │ \  Z<Zs  /
          │   '-...-'
          │ outside: no trip

Properties for feeder protection

  • Non-directional: it operates for faults in all four quadrants (behind the relay too), so it is used with a directional unit (mho or directional relay) in series.
  • Affected by arc resistance moderately and by power swings, since the circle covers a large area.
  • Used in three zones with time steps: Zone 1 ≈ 80–90% of the line (instantaneous), Zone 2 ≈ 120–150% (about 0.3–0.5 s), Zone 3 covers the next line (about 1 s).
  • Its reach does not depend on fault current level, so it gives faster and more selective protection than overcurrent relays on long lines.