T-beam with effective flange width 2242 mm, web 300×500 mm, effective depth 450 mm. Neutral axis lies in flange; design as rectangular section of width bf. Provide 5-20 mm bars (1571 mm²) for factored moment 217 kNm. Deflection check satisfied with L/d actual 13.9 < allowable 32.

A beam is simply supported on two walls of width 250 mm with a clear span of 6 m. If the beam has to support 150 mm deep slab and live load of intensity 3 kN/m2^2, design a T-beam. The beam is spaced at 4 m c/c. Take M20 concrete and Fe415 steel. Design for shear is not required.

Assumptions: beam web bw=300b_w=300 mm, D=500D=500 mm (about L/12L/12), effective cover 50 mm, d=450d=450 mm; floor finish ignored (not given). M20, Fe415.

Step 1: Effective span (IS 456 cl. 22.2): the lesser of c/c=6+0.25=6.25c/c=6+0.25=6.25 m and clear span +d=6+0.45=6.45+d=6+0.45=6.45 m, so Leff=6.25L_{eff}=6.25 m.

Step 2: Loads per metre length of beam (each beam carries slab load from a 4 m width)

Slab dead load=0.15×25=3.75 kN/m2;live load=3 kN/m2Slab load on beam=(3.75+3)×4=27.00 kN/mRib self weight=0.30×(0.50−0.15)×25=2.625 kN/mw=29.62 kN/m,wu=1.5w=44.44 kN/m\begin{aligned} \text{Slab dead load}&=0.15\times25=3.75\ \text{kN/m}^2;\quad\text{live load}=3\ \text{kN/m}^2\\ \text{Slab load on beam}&=(3.75+3)\times4=27.00\ \text{kN/m}\\ \text{Rib self weight}&=0.30\times(0.50-0.15)\times25=2.625\ \text{kN/m}\\ w&=29.62\ \text{kN/m},\qquad w_u=1.5w=44.44\ \text{kN/m} \end{aligned} Mu=wuL28=44.44×6.2528=216.98 kN⋅mM_u=\frac{w_uL^2}{8}=\frac{44.44\times6.25^2}{8}=216.98\ \text{kN·m}

Step 3: Effective flange width (T-beam)

bf=l06+bw+6Df=62506+300+6×150=2242 mm (<4000 mm)b_f=\frac{l_0}{6}+b_w+6D_f=\frac{6250}{6}+300+6\times150=2242\ \text{mm}\ (<4000\ \text{mm})

Step 4: Neutral axis position. Moment capacity when xu=Dfx_u=D_f:

Mu,f=0.36fckbfDf(d−0.42Df)=936.93 kN⋅m>MuM_{u,f}=0.36f_{ck}b_fD_f(d-0.42D_f)=936.93\ \text{kN·m}>M_u

The neutral axis lies within the flange; design as a rectangular beam of width bfb_f.

Step 5: Tension steel

Mu=0.87fyAstd(1−Astfybfdfck) ⇒ Ast=1374 mm2M_u=0.87f_yA_{st}d\left(1-\frac{A_{st}f_y}{b_fdf_{ck}}\right)\ \Rightarrow\ A_{st}=1374\ \text{mm}^2

xu=0.87fyAst0.36fckbf=30.7x_u=\dfrac{0.87f_yA_{st}}{0.36f_{ck}b_f}=30.7 mm <Df<D_f (OK). Minimum steel 0.85bwd/fy=2770.85b_wd/f_y=277 mm2^2 (OK).

Provide 5-20 mm dia bars, Ast,prov=1571A_{st,prov}=1571 mm2^2 (bw=300b_w=300 mm can hold them in one or two layers).

Step 6: Deflection check. bw/bf=0.13<0.3b_w/b_f=0.13<0.3, so the flange factor is 0.8. For flanged beams, ptp_t for Fig. 4 is based on bfdb_fd: pt=100×15712242×450=0.16%p_t=\dfrac{100\times1571}{2242\times450}=0.16\%, fs=0.58fyAst,reqAst,prov=210.5f_s=0.58f_y\dfrac{A_{st,req}}{A_{st,prov}}=210.5 N/mm2^2, so kt=2.0k_t=2.0 (maximum).

(Ld)allow=20×2.0×0.8=32.0,(Ld)actual=6250450=13.89\left(\frac{L}{d}\right)_{allow}=20\times2.0\times0.8=32.0,\qquad\left(\frac{L}{d}\right)_{actual}=\frac{6250}{450}=13.89

Safe in deflection.

Answer: T-beam bf=2242b_f=2242 mm, Df=150D_f=150 mm, bw=300b_w=300 mm, D=500D=500 mm, with 5-20 mm bars (Ast,req=1374A_{st,req}=1374 mm2^2).