Solid breakdown due to actual working conditions

Short answer

Actual working mechanisms are thermal runaway due to dielectric and conduction losses, chemical attack by oxidation/hydrolysis, void partial discharges, electrical and water treeing, tracking on contaminated surfaces, and erosion. They cause long-term failure below intrinsic strength.

Explain the breakdown mechanisms of solid insulating bodies occurring due to actual working conditions.

In practical equipment the working stress is far below the intrinsic strength of the insulation, yet solids fail over months or years. These failures are caused by slow processes produced by the actual working conditions: heat, chemical attack, moisture, surface contamination and partial discharges.

1. Thermal breakdown

  • Conduction loss (DC, W=σE2W = \sigma E^2) and dielectric loss (AC, W=E2fεrtan⁡δ1.8×1012W = \frac{E^2 f\varepsilon_r\tan\delta}{1.8\times10^{12}} W/cm³) heat the insulation.
  • Conductivity and tan⁡δ\tan\delta rise with temperature, so heating feeds on itself.
  • If heat generated exceeds heat conducted away, temperature rises without limit (thermal runaway) and the material melts or chars.
  • Worse under AC than DC, with high ambient temperature, poor cooling and thick insulation.

2. Electrochemical (chemical) breakdown

  • In the presence of air, moisture and heat, insulating materials slowly undergo chemical change:
    • Oxidation (e.g. rubber and polythene become brittle and crack)
    • Hydrolysis (moisture breaks down paper and some polymers, raising loss)
    • Chemical reaction with ozone and nitric acid produced by discharges
  • Under DC, electrolysis of ionic impurities creates conducting paths.
  • Rate roughly doubles for every 8–10 °C rise in temperature (Montsinger rule), so life depends strongly on operating temperature.

3. Breakdown due to internal (partial) discharges

  • Voids or gas bubbles left in the solid during manufacture have lower permittivity and strength.
  • Stress in a void is εr\varepsilon_r times the stress in the solid, so the void discharges at a voltage well below working voltage.
  • Each discharge (pC level) erodes the void walls by ion bombardment, heat and chemical action.
  • The void enlarges and develops into channels (trees) until the remaining solid fails.

4. Breakdown due to treeing

  • At sharp points, protrusions, contaminants or voids, the local field is very high.
  • Small discharges cut fine branched channels into the solid, looking like a tree.
  • Electrical trees grow by repeated discharges; water trees grow in polymer cables with moisture at much lower stress.
  • The tree progresses step by step and when it bridges the electrodes the insulation breaks down.

5. Breakdown due to tracking

  • A surface film of moisture and dirt on an insulator (bushing, cable termination) carries leakage current.
  • The current dries parts of the film unevenly; small arcs (dry-band arcs) form across the dry bands.
  • The arcs carbonize the surface, leaving a conducting track that grows until it bridges the electrodes, causing surface flashover.
  • Organic materials (resins, polymers) are most prone; porcelain and glass are resistant.

6. Erosion and ageing

Surface discharges and corona in air gradually erode the surface; combined with mechanical and thermal cycling, cracks form and lead to failure.

MechanismMain working causePrevention
ThermalLosses, poor coolingLow tan⁡δ\tan\delta, cooling
ChemicalHeat, oxygen, moistureTemperature limits, sealing
Internal dischargeVoidsVoid-free processing
TreeingHigh local stressSmooth electrodes, clean material
TrackingDirt and moistureTrack-resistant materials, cleaning