Radial, loop and network distribution merits

Short answer

Radial systems are simplest, cheapest, but have low reliability and poor voltage regulation. Loop systems offer two supply paths, better reliability and voltage, but higher cost and more complex protection. Network systems provide highest reliability and best regulation but are most expensive and complex, suited only for dense city cores.

Compare the merits and demerits of radial, loop and network distribution system.

A radial system feeds the loads from one end only. A loop (ring) system feeds each load from two directions through a closed or normally-open ring. A network (mesh) system interconnects many feeders and transformers on the secondary side, so each load has several supply paths.

 Radial:   S ===+===+===+  (one path)

 Loop:     S ===+===+===+
           |            |   (two paths)
           +============+

 Network:  S1 ==+===+===+== S2
                |   |   |
              ==+===+===+==  (mesh, many paths)

Radial system

Merits

  • Simplest and cheapest system, with the lowest initial cost.
  • Simple protection (fuses, OC relays) and easy operation.
  • Easy to plan and extend.

Demerits

  • Low reliability: a fault cuts off all consumers beyond it.
  • The far-end consumers get low voltage and suffer voltage fluctuation as the load changes.
  • High losses on long feeders.

Loop (ring) system

Merits

  • Each load has two supply paths. A faulty section is isolated and supply is restored from the other side, giving good reliability.
  • Better voltage regulation and lower losses, because the load current divides between the two paths.
  • Maintenance can be done without long outages.

Demerits

  • Higher cost (extra conductor, sectionalizing switches, RMUs).
  • More complex protection (directional relays) when the loop is operated closed.
  • Each section must be sized for the full load when the loop is fed from one side.

Network system

Merits

  • Highest reliability: a single feeder or transformer outage causes no interruption.
  • Best voltage regulation and lowest losses, since the load is shared among many paths.
  • Good flexibility for load growth, and the transformers share load efficiently.

Demerits

  • Highest cost: many interconnections, network protectors and more transformers.
  • Complex design, protection and fault-current coordination; high fault levels.
  • Justified only for very high load density.
PointRadialLoopNetwork
ReliabilityLowMedium-highHighest
Voltage regulationPoorGoodBest
CostLowestMediumHighest
ProtectionSimpleModerateComplex
UseRural, small townsUrban feedersCity cores, hospitals