Two-wattmeter method star load
Short answer
Total power P = 3650 W, total Q = √3(2100-1550) = 952.63 VAR. Per-phase: P_ph = 1216.67 W, Q_ph = 317.54 VAR. Power factor cosφ = 0.9676 lagging. Phase voltage = 230.94 V, line current = 5.445 A, phase impedance = 42.41 Ω (41.04 + j10.71 Ω).
The two-wattmeter method produces wattmeter readings W and W when connected to a star-connected load. If the line voltage is 400 V, calculate: (i) the per-phase average power, (ii) the per phase reactive power, (iii) the power factor, and (iv) the phase impedance.
Given: W, W, V, star connection.
(i) Per-phase average power. Total power is the sum of the readings:
(ii) Per-phase reactive power. Total reactive power is :
(iii) Power factor.
(iv) Phase impedance. Line current from :
Then and , so .
Answer: (i) 1216.67 W, (ii) 317.54 VAR, (iii) 0.9676 lagging, (iv) 42.41 Ω ().
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 3-phase induction machine at slip 0.05 · Basic Electrical and Electronics Engineering, chapter 2
- Three coils in delta, 415 V · Basic Electrical and Electronics Engineering, chapter 1
- Zener network with two load values · Basic Electrical and Electronics Engineering, chapter 3
- Zener circuit output voltage and current · Basic Electrical and Electronics Engineering, chapter 3
- RL series circuit current, pf, power · Basic Electrical and Electronics Engineering, chapter 1
- Parallel RL and RC branch currents, power · Basic Electrical and Electronics Engineering, chapter 1
- Delta load 20∠60° power and wattmeter readings · Basic Electrical Engineering, chapter 8
- Star load (8+j6) line, phase current · Basic Electrical Engineering, chapter 8
- Charging reactive power of line at no load · High Voltage Engineering, chapter 3 · asked 2×
- Phase and line voltage in star · Basic Electrical Engineering, chapter 8
All Basic Electrical and Electronics Engineering chapter 1 questions →