Charging reactive power of line at no load
Short answer
For a lossless line at no load, sending-end current is Is = j(Es/Zc)tanβL. The per-phase reactive power magnitude is Q0 = Es²/Zc tanβL. Substituting Zc = √(l/c) and βL = 2πL/λ gives Q0 = Es²√(c/l) tan(2πL/λ).
With a mathematical justification show that charging reactive power supplied by the source per phase for a transmission line at no load is given by: Q0 = Es² √(c/l) tan(2πL/λ), where l is inductance per unit length; c is the capacitance per unit length; L is length of line; λ is wave length.
Consider a lossless line of length with inductance and capacitance per unit length, open at the receiving end (no load). Let be the sending-end phase voltage and the receiving-end voltage.
Line equations
For a lossless line the propagation constant is with
The long-line equations at distance from the receiving end are
At no load
, so at the sending end ():
Hence (this is the Ferranti rise), and
The sending-end current leads by : it is a pure charging current.
Reactive power supplied by the source
Taking as reference, the complex power per phase is
The real power is zero (lossless line). The magnitude of reactive power is
the negative sign meaning the source absorbs lagging VArs, i.e. it supplies leading (capacitive) charging VArs to the line.
Substitution
With and :
which is the required result.
Remarks
- For a short line, , giving , the usual .
- grows rapidly with length and becomes infinite at (1500 km at 50 Hz), so long EHV lines need shunt reactors to absorb charging VArs and limit the Ferranti rise.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Charging reactive power in sine form · High Voltage Engineering, chapter 3
- 6° phase shift per 100 km of lossless line · High Voltage Engineering, chapter 3
- Mid-line reactor for Vr = Vs at no load · High Voltage Engineering, chapter 3
- Wave front retardation by terminal capacitance · High Voltage Engineering, chapter 3
- Inductance matrix of 500 kV bundled line · High Voltage Engineering, chapter 5 · asked 3×
- Capacitance matrix of 400 kV bundled line · High Voltage Engineering, chapter 5 · asked 2×
- Line as source and sink of reactive power · Power System Analysis I, chapter 6
- Line as source and sink of reactive power, effects · Power System Analysis I, chapter 6
- 330 kV quad-bundle line: inductance and charging · Power System Analysis I, chapter 4
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4