Line as source and sink of reactive power
Short answer
At loads below the surge impedance loading (SIL), the line’s shunt capacitance generates more reactive power than its series inductance absorbs, making it a net source. Above SIL, the inductance dominates, so the line becomes a sink. At SIL, net reactive power is zero.
Explain how a transmission line behaves as a source and sink of reactive power.
A transmission line has series inductance (which absorbs reactive power) and shunt capacitance (which generates reactive power). Whether the line as a whole is a source or a sink of VArs depends on which of the two is larger, and that depends on the load.
Reactive power generated and absorbed
For a line of length with reactance and susceptance per unit length, at voltage carrying current :
- depends on voltage, which is nearly constant, so it is almost fixed.
- depends on , so it rises with load.
Three cases
Using the surge impedance and surge impedance loading :
| Loading | Condition | Line behaves as |
|---|---|---|
| Light load () | Source of VAr (capacitive); voltage rises along the line (Ferranti effect) | |
| (natural load) | Neither; flat voltage profile, no net Q | |
| Heavy load () | Sink of VAr (inductive); voltage drops along the line |
Q net from line
+ |\
| \ source (light load)
0 +----*------------- P
| SIL \
- | \ sink (heavy load)
Consequences
- At light load, excess VArs raise receiving-end voltage; shunt reactors are switched in to absorb them.
- At heavy load, the line absorbs VArs and voltage falls; shunt capacitors, SVCs or series capacitors supply VArs.
- Long EHV lines and cables (high ) are strong VAr sources at light load; short, heavily loaded lines are VAr sinks.
Example: a 400 kV line with has SIL = 400 MW. At 200 MW it supplies VArs to the system; at 600 MW it absorbs VArs.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Line as source and sink of reactive power, effects · Power System Analysis I, chapter 6
- Need and methods of reactive power compensation · Power System Analysis I, chapter 6 · asked 2×
- Reactive power proportional to voltage drop · Power System Analysis I, chapter 6
- Charging reactive power of line at no load · High Voltage Engineering, chapter 3 · asked 2×