- 2075 Baisakh · 5 marks
Reactive power proportional to voltage drop
Short answer
For a short line with negligible resistance, Q_R ≈ V_R(V_S−V_R)/X = V_RΔV/X, so reactive power transfer is directly proportional to the voltage magnitude drop ΔV. Because cosδ≈1 for small power angles, Q_R is nearly independent of the power angle δ.
Verify that reactive power transferred over a transmission line is directly proportional to voltage drop along the line and is independent of power angle.
Consider a short line with negligible resistance, , sending voltage and receiving voltage .
Derivation
So
Reactive power and voltage drop
In practice the power angle is small (normally below about –), so :
where is the magnitude drop along the line.
Hence:
- : reactive power transfer is set by the difference in voltage magnitudes.
- is (nearly) independent of , since changes very little.
- Conversely, depends mainly on the angle, not on the magnitude difference.
Example
kV, kV, :
| 1° | 5.23 MVAr |
| 3° | 4.80 MVAr |
| Approx. | 5.28 MVAr |
For small the value stays close to , but it would double if doubled.
This is why voltage magnitude is controlled by reactive power (Q–V coupling), and frequency/angle by active power (P–δ coupling).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Voltage 150 km along a 400 km line · Power System Analysis I, chapter 5
- Line as source and sink of reactive power · Power System Analysis I, chapter 6
- Line as source and sink of reactive power, effects · Power System Analysis I, chapter 6
- Direction of active and reactive power flow · Power System Analysis I, chapter 6
- Maximum power over 20 + j50 Ω line · Power System Analysis I, chapter 6
- Maximum power over 20 + j30 Ω line · Power System Analysis I, chapter 6
- Charging reactive power of line at no load · High Voltage Engineering, chapter 3 · asked 2×
- Reactive power and voltage balance · Power System Analysis II, chapter 1
- Generator reactive power at constant terminal voltage · Power System Analysis II, chapter 1
- Voltage regulation inversely proportional to V² · Transmission and Distribution System Design, chapter 7