- 2069 Poush · 6 marks
Maximum power over 20 + j30 Ω line
Short answer
Maximum power occurs when load angle equals impedance angle (56.31°). Using P_R,max = (|V_S||V_R|/|Z|) − (|V_R|²R/|Z|²) gives 13.58 MW. Efficiency is about 49.0% with receiving-end power factor 0.517 leading.
A 3-phase overhead line has a series impedance of 20 + j30 Ohm per phase. Find the maximum power that can be delivered at the receiving end keeping the receiving end voltage 31.2 kV while the sending end voltage is 33 kV. What will be the efficiency of the line under this condition?
Short line: , = 33 kV, = 31.2 kV (line kV give three-phase MW/MVAr).
Maximum power
Maximum occurs when :
Reactive power at this condition
So the receiving end must supply 22.46 MVAr (pf leading).
Efficiency
(Check: MW.)
Answer: Maximum power ≈ 13.58 MW; efficiency ≈ 49.0 % (receiving pf 0.517 leading).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Power output with 46.85 kV sending, 33 kV receiving · Power System Analysis I, chapter 6
- Maximum power over 20 + j50 Ω line · Power System Analysis I, chapter 6
- Power delivered from sending end data, nominal-π · Power System Analysis I, chapter 5
- 8 km line receiving 15000 kVA at 33 kV · Power System Analysis I, chapter 6
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- Receiving and sending end powers from ABCD, 132/134 kV · Power System Analysis I, chapter 6
- Fault at far end of 33 kV line · Power System Analysis II, chapter 3
- Fault at load end of overhead line · Power System Analysis II, chapter 3
- Fault at receiving end of 220 kV lines · Power System Analysis II, chapter 3
- Fault at receiving end of 132 kV lines · Power System Analysis II, chapter 3