110 km, 110 kV line: sending end, regulation, efficiency

Short answer

Sending end voltage is 116.16 kV, current 108.38 A, power factor 0.947 lagging. Voltage regulation is 6.33% and efficiency 96.91%, using the nominal-π model for the 110 km line.

A 3-phase 50 Hz, 110 km long overhead line has the following line constants: resistance per phase per km = 0.153 ohm, inductance per phase per km = 1.21 mH, capacitance per phase per km = 0.00958 μF. The line supplies a load of 20 MW at 0.9 power factor lagging at a line voltage of 110 kV at the receiving end. Calculate the sending end voltage, current, power factor, regulation and efficiency.

A 110 km line is a medium line; it is solved here with the nominal-π model (half the shunt admittance at each end).

Line constants

R=0.153×110=16.83 ΩX=2π(50)(1.21×10−3)(110)=41.81 ΩY=2π(50)(0.00958×10−6)(110)=3.311×10−4 SY/2=1.655×10−4 S\begin{aligned} R &= 0.153\times110 = 16.83\ \Omega \\ X &= 2\pi(50)(1.21\times10^{-3})(110) = 41.81\ \Omega \\ Y &= 2\pi(50)(0.00958\times10^{-6})(110) = 3.311\times10^{-4}\ \text{S} \\ Y/2 &= 1.655\times10^{-4}\ \text{S} \end{aligned}

Receiving end

VR=110 000/3=63 508.5∠0∘ VIR=20×1063×63 508.5×0.9=116.64∠−25.84∘ A\begin{aligned} V_R &= 110\,000/\sqrt3 = 63\,508.5\angle0^\circ\ \text{V} \\ I_R &= \frac{20\times10^6}{3\times63\,508.5\times0.9} = 116.64\angle-25.84^\circ\ \text{A} \end{aligned}

Nominal-π steps

IC1=jY2VR=j10.51 AIL=IR+IC1=112.45∠−21.02∘ AVS=VR+ILZ=63 508.5+5068.8∠47.06∘=67 064.3∠3.17∘ VIC2=jY2VS=11.10∠93.17∘ AIS=IL+IC2=108.38∠−15.65∘ A\begin{aligned} I_{C1} &= j\frac{Y}{2}V_R = j10.51\ \text{A} \\ I_L &= I_R + I_{C1} = 112.45\angle-21.02^\circ\ \text{A} \\ V_S &= V_R + I_L Z = 63\,508.5 + 5068.8\angle47.06^\circ \\ &= 67\,064.3\angle3.17^\circ\ \text{V} \\ I_{C2} &= j\frac{Y}{2}V_S = 11.10\angle93.17^\circ\ \text{A} \\ I_S &= I_L + I_{C2} = 108.38\angle-15.65^\circ\ \text{A} \end{aligned}

Results

  • Sending-end line voltage =3×67.064=116.16= \sqrt3\times67.064 = 116.16 kV
  • Sending-end current =108.38= 108.38 A
  • Sending-end pf =cos⁡(3.17∘+15.65∘)=0.947= \cos(3.17^\circ + 15.65^\circ) = 0.947 lagging

Regulation (no-load VR=VS/∣A∣V_R = V_S/|A|, A=1+YZ/2=0.9931∠0.16∘A = 1 + YZ/2 = 0.9931\angle0.16^\circ):

%VR=67 064.3/0.9931−63 508.563 508.5×100=67 531.4−63 508.563 508.5×100=6.33%\%VR = \frac{67\,064.3/0.9931 - 63\,508.5}{63\,508.5}\times100 = \frac{67\,531.4 - 63\,508.5}{63\,508.5}\times100 = 6.33\%

Efficiency:

Ploss=3∣IL∣2R=3(112.45)2(16.83)=0.638 MWη=2020.638×100=96.91%\begin{aligned} P_{loss} &= 3|I_L|^2R = 3(112.45)^2(16.83) = 0.638\ \text{MW} \\ \eta &= \frac{20}{20.638}\times100 = 96.91\% \end{aligned}

Answer: VSV_S = 116.16 kV, ISI_S = 108.38 A, pf 0.947 lag, regulation 6.33 %, efficiency 96.91 %. (A nominal-T solution gives almost the same: 116.13 kV, 6.30 %, 96.90 %.)