12 km 33 kV line: losses, zero-regulation capacitor
Short answer
With corrected R=3 Ω, X=4.90 Ω, line current is 1.173 kA. Active loss is 12.39 MW, reactive loss 20.24 MVAr. For zero regulation, a capacitor of about 22.3 µF per phase (8.1 MVAr) is required.
A 12 km long 3-phase line is supplying a load at 33 kV. The line has a resistance of 2.5 × 10⁻³ Ohms/m and inductance of 1.3 × 10⁻⁶ H/m. If the sending end voltage is maintained at 34 kV∠20°, compute the active and reactive power losses in the line. Compute the capacitance per phase that needs to be connected at the end of the line to make the voltage regulation zero.
Assumption: the printed /m gives = 30 Ω for 12 km (2.5 Ω/km), unrealistic and larger than ; with it zero regulation is impossible by any shunt capacitor. It is taken as /m (likely misprint).
Line constants
Line current
Phase values: kV, kV.
Losses
(Check: MVA, MVA; differences 12.39 MW and 20.24 MVAr.)
Capacitance for zero regulation
Zero regulation means kV at full load. Keep the load = 53.81 MW and find the net :
The load already supplies 40.01 MVAr (leading), so the capacitor must supply
(With the printed = 30 Ω the losses would be 4.43 MW and 0.72 MVAr.)
Answer: Losses ≈ 12.39 MW and 20.24 MVAr; C ≈ 22.3 µF per phase (≈ 8.1 MVAr) for zero regulation.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 12 km line at 32.5 kV: regulation and capacitor · Power System Analysis I, chapter 6
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- 33 kV, 12 MW leading load: efficiency, zero regulation · Power System Analysis I, chapter 6 · asked 2×
- 15 km line: regulation and zero-regulation capacitor · Power System Analysis I, chapter 6
- Capacitor for zero regulation, 70 km 220 kV line · Power System Analysis I, chapter 6
- 70 km, 40 MW line: regulation and zero-regulation pf · Power System Analysis I, chapter 6
- Peterson coil for 33 kV 60 km line · Switchgear and Protection, chapter 5 · asked 6×
- Fault at far end of 33 kV line · Power System Analysis II, chapter 3