- 2077 Chaitra · 2+2+4 marks
15 km line: regulation and zero-regulation capacitor
Short answer
Sending end voltage is 13.72 kV, regulation 24.73%. For zero regulation, load power factor must be about 0.941 leading. A 5.54 MVAr capacitor bank (≈145.8 µF per phase, star-connected) at the receiving end reduces regulation to zero.
A 15 km long 3 phase overhead line delivers 5 MW at 11 kV at a power factor of 0.8 lagging. Line loss is 12% of the power delivered. Line inductance is 1.1 mH per km per phase. Calculate: (i) sending end voltage and regulation, (ii) power factor of the load to make regulation zero, (iii) the value of capacitor to be connected at the receiving end to reduce regulation to zero.
Short line (15 km), so shunt capacitance is neglected.
Line constants
(i) Sending-end voltage and regulation
Line value kV.
(ii) Load pf for zero regulation
Using the approximate drop , regulation is zero when the load is leading and
(Solving exactly with = 5 MW gives 0.890 leading.)
(iii) Capacitor at the receiving end
The 5 MW load stays at 0.8 lag (needs 3.75 MVAr). For zero regulation the net receiving-end reactive power must be
Capacitor rating:
Capacitance per phase (star connected):
Answer: (i) = 13.72 kV, regulation 24.73 %; (ii) pf ≈ 0.941 leading; (iii) 5.54 MVAr bank, ≈ 145.8 µF per phase (star).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 12 km 33 kV line: losses, zero-regulation capacitor · Power System Analysis I, chapter 6
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- Capacitor for zero regulation, 70 km 220 kV line · Power System Analysis I, chapter 6
- 70 km, 40 MW line: regulation and zero-regulation pf · Power System Analysis I, chapter 6
- 12 km line at 32.5 kV: regulation and capacitor · Power System Analysis I, chapter 6
- Regulation and efficiency of 100 km, 110 kV line · Power System Analysis I, chapter 6 · asked 2×
- Loss and drop, 15 km 11 kV feeder · Transmission and Distribution System Design, chapter 7 · asked 2×
- Power loss, 10 km 11 kV UDL feeder · Transmission and Distribution System Design, chapter 7 · asked 2×
- Restriking voltage numerical (11 kV, 10 mH) · Switchgear and Protection, chapter 6 · asked 2×
- Regulation and zero-regulation power factor of 100 kVA transformer · Electrical Machines I, chapter 2