15 km line: regulation and zero-regulation capacitor

Short answer

Sending end voltage is 13.72 kV, regulation 24.73%. For zero regulation, load power factor must be about 0.941 leading. A 5.54 MVAr capacitor bank (≈145.8 µF per phase, star-connected) at the receiving end reduces regulation to zero.

A 15 km long 3 phase overhead line delivers 5 MW at 11 kV at a power factor of 0.8 lagging. Line loss is 12% of the power delivered. Line inductance is 1.1 mH per km per phase. Calculate: (i) sending end voltage and regulation, (ii) power factor of the load to make regulation zero, (iii) the value of capacitor to be connected at the receiving end to reduce regulation to zero.

Short line (15 km), so shunt capacitance is neglected.

Line constants

I=5×1063×11 000×0.8=328.04 APloss=0.12×5=0.6 MW=3I2RR=0.6×1063×328.042=1.859 ΩX=2π(50)(1.1×10−3)(15)=5.184 Ω\begin{aligned} I &= \frac{5\times10^6}{\sqrt3 \times 11\,000 \times 0.8} = 328.04\ \text{A} \\ P_{loss} &= 0.12 \times 5 = 0.6\ \text{MW} = 3I^2R \\ R &= \frac{0.6\times10^6}{3\times 328.04^2} = 1.859\ \Omega \\ X &= 2\pi(50)(1.1\times10^{-3})(15) = 5.184\ \Omega \end{aligned}

(i) Sending-end voltage and regulation

VR=11 0003=6350.9∠0∘ VI=328.04∠−36.87∘ AVS=VR+I(R+jX)=6350.9+328.04∠−36.87∘ (1.859+j5.184)=7921.5∠7.21∘ V\begin{aligned} V_R &= \frac{11\,000}{\sqrt3} = 6350.9\angle0^\circ\ \text{V} \\ I &= 328.04\angle-36.87^\circ\ \text{A} \\ V_S &= V_R + I(R + jX) \\ &= 6350.9 + 328.04\angle-36.87^\circ\,(1.859 + j5.184) \\ &= 7921.5\angle7.21^\circ\ \text{V} \end{aligned}

Line value =3×7921.5=13.72= \sqrt3 \times 7921.5 = 13.72 kV.

%VR=7921.5−6350.96350.9×100=24.73%\%VR = \frac{7921.5 - 6350.9}{6350.9}\times100 = 24.73\%

(ii) Load pf for zero regulation

Using the approximate drop VS−VR≈I(Rcos⁡ϕ±Xsin⁡ϕ)V_S - V_R \approx I(R\cos\phi \pm X\sin\phi), regulation is zero when the load is leading and

IRcos⁡ϕ−IXsin⁡ϕ=0tan⁡ϕ=RX=1.8595.184=0.3585ϕ=19.73∘,cos⁡ϕ=0.941 leading\begin{aligned} IR\cos\phi - IX\sin\phi &= 0 \\ \tan\phi &= \frac{R}{X} = \frac{1.859}{5.184} = 0.3585 \\ \phi &= 19.73^\circ,\quad \cos\phi = 0.941\ \text{leading} \end{aligned}

(Solving ∣VS∣=∣VR∣|V_S| = |V_R| exactly with PP = 5 MW gives 0.890 leading.)

(iii) Capacitor at the receiving end

The 5 MW load stays at 0.8 lag (needs 3.75 MVAr). For zero regulation the net receiving-end reactive power must be

Qnet=−Ptan⁡ϕ=−5×0.3585=−1.793 MVArQ_{net} = -P\tan\phi = -5 \times 0.3585 = -1.793\ \text{MVAr}

Capacitor rating:

QC=3.75+1.793=5.543 MVAr (3-phase)Q_C = 3.75 + 1.793 = 5.543\ \text{MVAr (3-phase)}

Capacitance per phase (star connected):

C=QCωVL2=5.543×106314.16×11 0002=145.8 μFC = \frac{Q_C}{\omega V_L^2} = \frac{5.543\times10^6}{314.16\times 11\,000^2} = 145.8\ \mu\text{F}

Answer: (i) VSV_S = 13.72 kV, regulation 24.73 %; (ii) pf ≈ 0.941 leading; (iii) 5.54 MVAr bank, ≈ 145.8 µF per phase (star).