Power loss, 10 km 11 kV UDL feeder
Short answer
For a uniformly distributed feeder, three-phase power loss equals I_s^2 r l. With sending-end current 100 A, r = 0.4 Ω/km, l = 10 km, loss = 40 kW.
Compute the power loss for a 10 km long 11 kV, 3-phase distribution feeder having sending end current of 100 A with uniformly distributed load (Use R = 0.4 Ω/km, X = 0.3 Ω/km). Derive any expression used.
Derivation for uniformly distributed load
Let a feeder of length carry sending-end current , with load tapped uniformly so the current falls linearly to zero at the far end:
Per-phase voltage drop, with per km:
Three-phase power loss:
So a UDL feeder behaves like the whole load lumped at the middle for voltage drop, and at one-third of the length for loss.
Why
Each small element at distance carries current . Integrating gives
so the loss is only one-third of what it would be with the whole load at the far end.
Substitution
A, /km, km, so per phase.
(For comparison, with the same current lumped at the end, loss kW.)
The reactance /km does not affect real power loss; it only enters the voltage drop, .
Answer: Power loss = 40 kW.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Loss and drop, 15 km 11 kV feeder · Transmission and Distribution System Design, chapter 7 · asked 2×
- Loss and voltage drop, 16 km uniformly varying load · Transmission and Distribution System Design, chapter 7
- Voltage drop and loss, uniformly varying load · Transmission and Distribution System Design, chapter 7 · asked 2×
- Voltage drop and loss with uniformly distributed load · Transmission and Distribution System Design, chapter 7 · asked 2×
- LT feeder options: loss and voltage drop, 50 kW · Transmission and Distribution System Design, chapter 7 · asked 3×
- Peak loss and voltage drop for LT feeder options · Transmission and Distribution System Design, chapter 7 · asked 2×
- Capacitor size, four-node 11 kV feeder · Transmission and Distribution System Design, chapter 7 · asked 5×
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- Sending end active power from ABCD, 132/130.5 kV · Power System Analysis I, chapter 6
- 400 km long line, 60 MVA at 220 kV · Power System Analysis I, chapter 5
- Sending and receiving power, 140∠10° and 132 kV · Power System Analysis I, chapter 6
All Transmission and Distribution System Design chapter 7 questions →