Capacitor size, four-node 11 kV feeder
Short answer
Optimum capacitor size equals the resistance-weighted average of reactive flows in the sections it relieves. Sum of R_i Q_i = 1866.92, sum of R_i = 8, so Q_c = 233.4 kVAR for maximum loss reduction.
For the 11 kV primary distribution network shown below, determine the size (kVAR) of the capacitor to be placed at the location shown in diagram to achieve the maximum loss reduction. For simplifying the analysis assume voltage at each node is 1 p.u. All impedances are in p.u. at 1000 kVA.
[Figure: radial feeder from a 1000 kVA, 33/11 kV source substation S to node A through 1+j2, A to B through 2+j3, B to C through 2+j4, C to D through 3+j4. Loads through distribution transformers: 100 kVA at 0.6 p.f. lag at A, 100 kVA at 0.8 p.f. lag at B, 150 kVA at 0.9 p.f. lag at C, 200 kVA at 0.6 p.f. lag at D. The capacitor is placed at node D.]
Method (optimum single capacitor)
With all node voltages taken as 1 p.u., the reactive current in a section equals its reactive power flow (p.u.). A shunt capacitor at the end node reduces the reactive flow in every section between the source and that node from to . The loss reduction is
For maximum loss reduction, , so
i.e. the optimum capacitor equals the resistance-weighted average of the reactive flows in the sections it relieves. The ratio does not depend on whether is in ohms or p.u., so kVAR can be used directly.
S-(1+j2)-A-(2+j3)-B-(2+j4)-C-(3+j4)-D
| | | |
100kVA 100kVA 150kVA 200kVA
0.6 lag 0.8 lag 0.9 lag 0.6 lag [Qc]
Reactive load at each node
| Node | S (kVA) | p.f. | Q (kVAR) | |
|---|---|---|---|---|
| A | 100 | 0.6 | 0.8 | 80.00 |
| B | 100 | 0.8 | 0.6 | 60.00 |
| C | 150 | 0.9 | 0.4359 | 65.38 |
| D | 200 | 0.6 | 0.8 | 160.00 |
Reactive flow in each section
| Section | R (p.u.) | Q flow (kVAR) | R × Q |
|---|---|---|---|
| S–A | 1 | 365.38 | 365.38 |
| A–B | 2 | 285.38 | 570.77 |
| B–C | 2 | 225.38 | 450.77 |
| C–D | 3 | 160.00 | 480.00 |
| Total | 8 | 1866.92 |
(Section flows: S–A carries all four loads, A–B carries B+C+D, and so on.)
Optimum capacitor
In p.u. on 1000 kVA, p.u. Only the resistances matter for loss; the reactances affect voltage drop, not loss.
Answer: Capacitor at node D ≈ 233 kVAR for maximum loss reduction (nearest standard bank ≈ 240–250 kVAR).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Capacitor size for maximum loss reduction (variant) · Transmission and Distribution System Design, chapter 7 · asked 5×
- Capacitor size for maximum loss reduction · Transmission and Distribution System Design, chapter 7 · asked 5×
- Capacitor size, feeder with 500 kVA end load · Transmission and Distribution System Design, chapter 7 · asked 5×
- Capacitor size, feeder with three equal loads · Transmission and Distribution System Design, chapter 7
- Loss and drop, 15 km 11 kV feeder · Transmission and Distribution System Design, chapter 7 · asked 2×
- Power loss, 10 km 11 kV UDL feeder · Transmission and Distribution System Design, chapter 7 · asked 2×
All Transmission and Distribution System Design chapter 7 questions →