Optimum capacitor size is the weighted average of section reactive flows: Qc = ΣRiQi/ΣRi = 0.2027 p.u. = 202.7 kVAR. Place a standard 200 kVAR bank at node C to maximize loss reduction.

For the 11 kV primary distribution network shown below, determine the size (kVAR) of the capacitor to be placed at the location shown in diagram to achieve maximum loss reduction. For simplicity of analysis assume voltage at each node is 1 p.u. All impedances are in p.u. at 1000 kVA.

[Figure: radial feeder from a 1000 kVA, 33/11 kV source substation S to node A through impedance 1+j2, A to node B through 2+j3, B to node C through 3+j4. Loads through distribution transformers: 100 kVA at 0.8 p.f. lag at A, 150 kVA at 0.9 p.f. lag at B, 200 kVA at 0.6 p.f. lag at C. The capacitor is placed at node C.]

A shunt capacitor supplies reactive power locally, reducing the reactive current in every section upstream of it. The optimum size minimises the total I2RI^2R loss.

Assumptions: all node voltages = 1 p.u. (given), so section current magnitude² = P2+Q2P^2 + Q^2 in p.u.; base 1000 kVA; transformer impedances neglected.

Step 1: Loads in p.u.

NodeS (p.u.)p.f.P (p.u.)Q (p.u.)
A0.100.80.08000.10 × 0.6 = 0.0600
B0.150.90.13500.15 × 0.4359 = 0.0654
C0.200.60.12000.20 × 0.8 = 0.1600

Step 2: Section flows

SectionR (p.u.)P (p.u.)Q (p.u.)
S–A10.3350.2854
A–B20.2550.2254
B–C30.1200.1600

Step 3: Loss as a function of capacitor size

With capacitor QcQ_c at C, the reactive flow in every section reduces by QcQ_c:

PL=∑Ri[Pi2+(Qi−Qc)2]P_L = \sum R_i \left[P_i^2 + (Q_i - Q_c)^2\right]

For maximum loss reduction:

dPLdQc=−2∑Ri(Qi−Qc)=0Qc=∑RiQi∑Ri=1(0.2854)+2(0.2254)+3(0.16)1+2+3=1.21626=0.2027 p.u.\begin{aligned} \frac{dP_L}{dQ_c} &= -2\sum R_i (Q_i - Q_c) = 0 \\ Q_c &= \frac{\sum R_i Q_i}{\sum R_i} \\ &= \frac{1(0.2854) + 2(0.2254) + 3(0.16)}{1 + 2 + 3} \\ &= \frac{1.2162}{6} = 0.2027 \text{ p.u.} \end{aligned} Qc=0.2027×1000=202.7 kVARQ_c = 0.2027 \times 1000 = 202.7 \text{ kVAR}

Step 4: Check of loss reduction (p.u.)

SectionLoss beforeLoss after
S–A0.19370.1191
A–B0.23160.1311
B–C0.12000.0487
Total0.54530.2988

Loss falls from 0.545 p.u. to 0.299 p.u., a reduction of about 45%. (The given impedances are very large, so the absolute p.u. losses are only for comparison.)

Note: the optimum QcQ_c (0.203 p.u.) is larger than the reactive load at C (0.16 p.u.) because upstream sections also carry the reactive power of A and B; the result is a weighted average of section reactive flows.

Answer: Capacitor size ≈ 203 kVAR at node C (a standard 200 kVAR bank would be used).